Plan Review Details - Permit 08010041
Plan Review Stops For Permit 08010041
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-11 Cont ID  
Sent By mjacobs Date 2008-04-11 Time 14:03 Rev Time 0.00
Received By mjacobs Date 2008-04-11 Time 11:12 Sent To M
Notes
2008-04-11 14:04:20SENT TO TGORDON. MJ

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-09 Cont ID  
Sent By mjacobs Date 2008-01-09 Time 11:16 Rev Time 0.00
Received By mjacobs Date 2008-01-09 Time 07:01 Sent To  
Notes
2008-01-09 11:16:07BUILDING PLAN REVIEW
 PERMIT: 08010041
 ADD: 444 WEST RAILROAD AVE
 CONT: PBM DEVELOPMENT, INC.
 TEL: (561)368-2544 EXT22
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 1-9-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE MORE INFORMATION FOR THE NEW MEZZANINE
 INCLUDING THE SQUARE FOOTAGE, SPIRAL STAIRS AND THE
 HANDRAILS. THE ENGINEERED SHOP DRAWINGS ARE ALSO
 REQUIRED AS STATED ON SHEET S1.0.
  
 3)FBC 505.2 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF
 THE AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE
 LOCATED.
  
 4)A FRONT ELEVATION DETAIL DRAWING OF THE MEZZANINE
 IS REQUIRED SHOWING THE OPENNESS IN ACCORDANCE WITH FBC
 505.4 THE FLOOR LOAD OF THE MEZZANINE SHALL BE STATED
 ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-10 Cont ID  
Sent By btrobaug Date 2008-04-10 Time 13:17 Rev Time 0.00
Received By btrobaug Date 2008-04-10 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 13:46 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 11:38 Sent To  
Notes
2008-01-08 13:46:50 
  
 APPLICATION # 08010041
 ELECTRICAL PLAN REVIEW
 229 10TH STREET
 1/8/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ELECTRICAL SPECIFICATIONS ON SHEET E0.1,
 INCORRECTLY REFERENCES THE 2006 EDITION NFPA-101 AND
 2007 EDITION OF NFPA-72. SEE ABOVE FOR ADOPTED
 REFERENCES OR CHAPTER 35 OF THE FLORIDA BUILDING CODE.
 FOR RECORD RETENTION AND CLARITY IN THE FIELD CHANGE
 NOTED TO REFLECT THE CORRECT CODE CYCLES .
  
 2} THE EXIT/EMERGENCY LIGHT AT THE ENTRY AND THE
 ?SWITCH BANK? ON SHEET E2.1 IS LISTING THE LIGHTS ON
 CIRCUIT CL1A-1, THIS IS A RECEPTACLE CIRCUIT ON THE
 PANEL SCHEDULE, CIRCUITS 2 AND 4 ARE THE LISTED
 LIGHTING CIRCUITS. CORRELATE THE SAME.
  
 3} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR
 THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE
 BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY
 DEFINITION? , FORM ?A? IS NEITHER REQUIRED OR ALLOWED.
 SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL
 REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS. SEE
 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
  
 IF THERE AE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-10 Cont ID  
Sent By mawillia Date 2008-04-10 Time 15:08 Rev Time 0.00
Received By mawillia Date 2008-04-10 Time 14:13 Sent To  
Notes
2008-04-10 14:39:16*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS LS-1, FS0.1 & FS2.1, E2.1,
 AND FA0.1 & FA2.1 WERE STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-17 Time 20:34 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 15:47 Sent To  
Notes
2008-01-10 16:02:10*****DENIED*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 NUMERICAL ADDRESS LOCATED IN THE THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH ACCESS TO AND/OR EGRESS FROM OTHER AREAS OF THE
 FLOOR OR THE BUILDING.
  
 3.DISPLAY THE SUITE NUMBER SO THAT IT IS
 DISTINGUISHABLE FROM OTHER TENANT SPACES ON THE FLOOR.
 AS PER WEST PALM BEACH CODE, THE SUITE NUMBERS SHALL BE
 NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 4.PROVIDE OCCUPANT LOAD FOR THIS TENANT SPACE.
  
 5.ON SHEET LS-1, PLEASE EXPLAIN THE 3'-0" X 8'- 0"
 METAL NON-RATED DOOR IN WHAT APPEARS TO BE A RATED
 WALL.
  
 6.PROVIDE THE PRESCRIPTIVE STRENGHT FOR THE SPIRAL
 STAIR'S HANDRAIL/GUARDRAIL.DETAIL THE CRITERIA OF THE
 SPIRAL STAIRS AS PER 7.2.2.2.3.1 OF NFPA 101, LIFE
 SAFETY CODE, 2003 EDITION.
  
 7.ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO
 REFLECT THAT HVAC DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-06-10 Cont ID  
Sent By vmolina Date 2010-06-10 Time 12:24 Rev Time 0.00
Received By vmolina Date 2010-06-10 Time 12:24 Sent To  
Notes
2010-06-10 12:24:29IN PLUMBING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-05-11 Cont ID  
Sent By jgomez Date 2010-05-11 Time 08:31 Rev Time 0.00
Received By jgomez Date 2010-05-11 Time 08:31 Sent To  
Notes
2010-05-11 08:36:01SENT TO B-5.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 08:45 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 08:45 Sent To  
Notes
2008-04-02 08:47:50TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-10 Time 15:47 Rev Time 0.00
Received By mawillia Date 2008-01-03 Time 14:34 Sent To  
Notes
2008-01-03 14:36:50TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-11 Cont ID  
Sent By tgordon Date 2008-04-11 Time 14:44 Rev Time 0.30
Received By tgordon Date 2008-04-11 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-04-03 Cont ID  
Sent By tgordon Date 2008-04-03 Time 15:24 Rev Time 0.30
Received By tgordon Date 2008-04-03 Time 15:24 Sent To  
Notes
2008-04-03 15:46:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) IN LAST MECHANICAL REVIEW I REQUESTED COOLING LOAD
 CALCULATIONS, WHAT HAS BEEN SUBMITTED IS A SIZING
 SUMMARY.
 UNDER 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A SUMMARY
 SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED BY THE
 ENGINEER AND HAS THE MINIMUM INFORMATION ON IT.
 **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING
 METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY
 BULB USED... **OUTDOOR WET BULB USED... **RELATIVE
 HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING
 REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN...
 **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)...
 **TOTAL COOLING REQUIRED WITH OUTSIDE AIR. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By tgordon Date 2008-01-03 Time 15:54 Rev Time 0.30
Received By tgordon Date 2008-01-03 Time 15:54 Sent To  
Notes
2008-01-03 15:58:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status N Date 2010-06-14 Cont ID  
Sent By lwagner Date 2010-06-14 Time 14:25 Rev Time 0.00
Received By lwagner Date 2010-06-14 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-07 Cont ID  
Sent By jleech Date 2008-04-07 Time 08:50 Rev Time 0.00
Received By jleech Date 2008-04-07 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-01-07 Cont ID  
Sent By jleech Date 2008-01-07 Time 09:08 Rev Time 0.00
Received By jleech Date 2008-01-07 Time 08:19 Sent To  
Notes
2008-01-07 09:24:42DENIED;
 1. GREASE TRAP SIZE MUST BE APPROVED BY THE CITY'S
 UTILITY DEPARTMENT. CONTACT PERSON IS RODNEY COMPO;
 PHONE # 822-2272. E-MAIL [email protected].
 2. THE THREE COMPARTMENT SINK SHALL DISCHARGE
 INDIRECTLY INTO A FLOOR SINK. SEE FBC-2004 PLUMBING
 SECTION 802.1.1.
 3. EXPLAIN ICE FLAKER W/BIN (22) NO WATER TO UNITS
 SHOWN ON SANITARY RISER DIAGRAM, AND NO DRAIN ON
 SANITARY RISER DIAGRAM. PLEASE PROVIDE MANUFACTURE,S
 PAPER WORK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-07 Cont ID  
Sent By choops Date 2008-01-07 Time 15:38 Rev Time 0.00
Received By choops Date 2008-01-07 Time 15:38 Sent To  
Notes
2008-01-07 15:39:12*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.