Plan Review Details - Permit 08010010
Plan Review Stops For Permit 08010010
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-18 Cont ID  
Sent By mjacobs Date 2008-01-18 Time 13:36 Rev Time 0.00
Received By mjacobs Date 2008-01-18 Time 10:35 Sent To  
Notes
2008-01-18 13:36:35PROVISOR:
 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET ABOVE THE FLOOR. NOTE: PAINT ON DRYWALL IS
 NOT A HARD SURFACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-08 Cont ID  
Sent By mjacobs Date 2008-01-08 Time 16:55 Rev Time 0.00
Received By mjacobs Date 2008-01-08 Time 13:59 Sent To  
Notes
2008-01-08 16:55:48BUILDING PLAN REVIEW
 PERMIT: 08010010
 ADD: 7310 GEORGIA AVE.
 CONT: JEFFERY GOMERSALL BLDG CONTRACTOR
 TEL: (561)718-1866
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN. THE
 EXISTING PLAN SHALL SHOW ALL EXISTING WALLS AND
 SYSTEMS. ON THE EXISTING PLAN INDICATE THE WALLS AND
 SYSTEMS TO BE DEMOED. ON THE PROPOSED DRAWINGS SHOW ALL
 NEW WALLS AND SYSTEMS. A WALL LEGEND INDICATING THE
 DIFFERENT TYPES OF WALLS INCLUDING WALLS TO DEMO WILL
 BE HELPFUL WITH THE REVIEW.CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. THE
 DRAWING SHALL BE DIMENSIONED. WHAT ARE THE HEIGHT OF
 THE STRUCTURE ABOVE AND THE SIZE OF EACH NEW BAY/
 SUITE? FBC. 106.1.1
 NOTE: WOOD FRAMING MEMBERS AND FURRING STRIPS ATTATCHED
 DIRECTLY TO MASONARY OR CONCRETE WALLS SHALL BE OF
 APPROVED NATURALLY DURABLE OR PRESERVATIVE-TREATED
 WOOD. FBC 2304.11.2.2
  
 3)SPECIFY THE USE AND OCCUPANCY OF EACH BAY ALONG
 WITH THE OCCUPANT LOAD. THE OCCUPANT LOAD SHOWN ON THE
 DRAWINGS IS NOT CLEAR. CLARIFY.
  
 4)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-08 Cont ID  
Sent By btrobaug Date 2008-02-08 Time 14:34 Rev Time 0.00
Received By btrobaug Date 2008-02-08 Time 14:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-31 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 14:47 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 14:11 Sent To  
Notes
2008-01-31 10:49:01 
  
  
 THIS BUILDING IS EXEMPT UNDER 13-101.5.3 FBC./WRT.
2008-01-23 14:28:19 

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 08:47 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 07:56 Sent To  
Notes
2008-01-08 08:47:17 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-101.6 BUILDING SYSTEMS.
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR
 REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT
 MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS. SEE 13-415.2.C.1 FOR LIGHTING DENSITIES.
  
 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By mawillia Date 2008-01-25 Time 11:13 Rev Time 0.00
Received By mawillia Date 2008-01-25 Time 10:57 Sent To  
Notes
2008-01-25 11:10:24*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-09 Cont ID  
Sent By mawillia Date 2008-01-09 Time 16:14 Rev Time 0.00
Received By mawillia Date 2008-01-09 Time 16:01 Sent To  
Notes
2008-01-09 16:14:17*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.IS THE OCCUPANT LOAD LISTED ON SHEET 1 FOR THE
 BUILDING OR A TENANT SPACE?
  
 5.SPECIFY THE INTERIOR FINISH FOR THE NEW PARTITION
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) FOR EACH TENANT SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 14:24 Sent To  
Notes
2008-01-14 14:26:18TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-09 Cont ID  
Sent By mawillia Date 2008-01-09 Time 16:01 Rev Time  
Received By mawillia Date 2008-01-02 Time   Sent To  
Notes
2008-01-02 16:17:23TO "BOB" # 3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-01-03 Cont ID  
Sent By tgordon Date 2008-01-03 Time 15:22 Rev Time 0.25
Received By tgordon Date 2008-01-03 Time 15:22 Sent To  
Notes
2008-01-03 15:23:303 BATHROOMS EXHAUST FANS ONLY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By jleech Date 2008-01-23 Time 07:46 Rev Time 0.00
Received By jleech Date 2008-01-23 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By jleech Date 2008-01-04 Time 07:44 Rev Time 0.00
Received By jleech Date 2008-01-04 Time 07:40 Sent To  
Notes
2008-01-04 08:28:34DENIED;
  
 THIS PLAN WAS REVIEW WITH THE, FBC-2004 -2006
 REVISIONS PLUMBING. A DRINKING FOUNTAIN IS REQUIRED IN
 EACH BAY TO MEET THE MINIMUM PLUMBING FIXTURE
 REQUIREMENTS. SEE SECTION 410.1. IN THE 2004 CODE
 BOTTLED WATER CANNOT BE A SUBSTITUTE FOR A DRINKING
 FOUNTAIN. THIS DRINKING FOUNTAIN MUST MEET THE HANDICAP
 REQUIREMINTS OF FBC BUILDING CHAPTER 11 SECTIONS
 11-4.15.1 THRU 11-4.15.5. PLEASE SHOW A DETAIL ON PLAN
 WITH ALL REQUIRED MEASUREMENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-07 Cont ID  
Sent By choops Date 2008-01-07 Time 15:41 Rev Time 0.00
Received By choops Date 2008-01-07 Time 15:41 Sent To  
Notes
2008-01-07 15:41:15*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.