Plan Review Stops For Permit 08010010 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-01-18 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-01-18 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-01-18 |
Time |
10:35 |
Sent To |
|
|
Notes |
2008-01-18 13:36:35 | PROVISOR: | | WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT | | OF 4 FEET ABOVE THE FLOOR. NOTE: PAINT ON DRYWALL IS | | NOT A HARD SURFACE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-01-08 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-01-08 |
Time |
13:59 |
Sent To |
|
|
Notes |
2008-01-08 16:55:48 | BUILDING PLAN REVIEW | | PERMIT: 08010010 | | ADD: 7310 GEORGIA AVE. | | CONT: JEFFERY GOMERSALL BLDG CONTRACTOR | | TEL: (561)718-1866 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN. THE | | EXISTING PLAN SHALL SHOW ALL EXISTING WALLS AND | | SYSTEMS. ON THE EXISTING PLAN INDICATE THE WALLS AND | | SYSTEMS TO BE DEMOED. ON THE PROPOSED DRAWINGS SHOW ALL | | NEW WALLS AND SYSTEMS. A WALL LEGEND INDICATING THE | | DIFFERENT TYPES OF WALLS INCLUDING WALLS TO DEMO WILL | | BE HELPFUL WITH THE REVIEW.CONSTRUCTION DOCUMENTS | | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. THE | | DRAWING SHALL BE DIMENSIONED. WHAT ARE THE HEIGHT OF | | THE STRUCTURE ABOVE AND THE SIZE OF EACH NEW BAY/ | | SUITE? FBC. 106.1.1 | | NOTE: WOOD FRAMING MEMBERS AND FURRING STRIPS ATTATCHED | | DIRECTLY TO MASONARY OR CONCRETE WALLS SHALL BE OF | | APPROVED NATURALLY DURABLE OR PRESERVATIVE-TREATED | | WOOD. FBC 2304.11.2.2 | | | | 3)SPECIFY THE USE AND OCCUPANCY OF EACH BAY ALONG | | WITH THE OCCUPANT LOAD. THE OCCUPANT LOAD SHOWN ON THE | | DRAWINGS IS NOT CLEAR. CLARIFY. | | | | 4)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | REQUIREMENTS BASED ON OCCUPANCY | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-02-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-02-08 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-02-08 |
Time |
14:17 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-01-23 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-01-23 |
Time |
14:11 |
Sent To |
|
|
Notes |
2008-01-31 10:49:01 | | | | | | | THIS BUILDING IS EXEMPT UNDER 13-101.5.3 FBC./WRT. | 2008-01-23 14:28:19 | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-01-08 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-01-08 |
Time |
07:56 |
Sent To |
|
|
Notes |
2008-01-08 08:47:17 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} 13-101.6 BUILDING SYSTEMS. | | THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING | | BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR | | REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT | | MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM | | EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR | | COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL | | BUILDINGS. SEE 13-415.2.C.1 FOR LIGHTING DENSITIES. | | | | 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR | | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE | | SHOWN ON THE PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-01-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-25 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-01-25 |
Time |
10:57 |
Sent To |
|
|
Notes |
2008-01-25 11:10:24 | *****APPROVED***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;PLAN SHEET STAMPED, INITIALED, AND | | DATED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-01-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-09 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-01-09 |
Time |
16:01 |
Sent To |
|
|
Notes |
2008-01-09 16:14:17 | *****DENIED***** | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 4.IS THE OCCUPANT LOAD LISTED ON SHEET 1 FOR THE | | BUILDING OR A TENANT SPACE? | | | | 5.SPECIFY THE INTERIOR FINISH FOR THE NEW PARTITION | | WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) FOR EACH TENANT SPACE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-01-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-14 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-14 |
Time |
14:24 |
Sent To |
|
|
Notes |
2008-01-14 14:26:18 | TO "BOB"#12 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-01-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-09 |
Time |
16:01 |
Rev Time |
|
Received By |
mawillia |
Date |
2008-01-02 |
Time |
|
Sent To |
|
|
Notes |
2008-01-02 16:17:23 | TO "BOB" # 3 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2008-01-03 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-03 |
Time |
15:22 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2008-01-03 |
Time |
15:22 |
Sent To |
|
|
Notes |
2008-01-03 15:23:30 | 3 BATHROOMS EXHAUST FANS ONLY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-01-23 |
Time |
07:46 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-01-23 |
Time |
07:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-01-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-01-04 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-01-04 |
Time |
07:40 |
Sent To |
|
|
Notes |
2008-01-04 08:28:34 | DENIED; | | | | THIS PLAN WAS REVIEW WITH THE, FBC-2004 -2006 | | REVISIONS PLUMBING. A DRINKING FOUNTAIN IS REQUIRED IN | | EACH BAY TO MEET THE MINIMUM PLUMBING FIXTURE | | REQUIREMENTS. SEE SECTION 410.1. IN THE 2004 CODE | | BOTTLED WATER CANNOT BE A SUBSTITUTE FOR A DRINKING | | FOUNTAIN. THIS DRINKING FOUNTAIN MUST MEET THE HANDICAP | | REQUIREMINTS OF FBC BUILDING CHAPTER 11 SECTIONS | | 11-4.15.1 THRU 11-4.15.5. PLEASE SHOW A DETAIL ON PLAN | | WITH ALL REQUIRED MEASUREMENTS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-01-07 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-01-07 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-01-07 |
Time |
15:41 |
Sent To |
|
|
Notes |
2008-01-07 15:41:15 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|