Plan Review Details - Permit 07120667
Plan Review Stops For Permit 07120667
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-29 Cont ID  
Sent By lursu Date 2008-01-29 Time 09:49 Rev Time 0.00
Received By lursu Date 2008-01-29 Time 09:49 Sent To  
Notes
2008-01-29 09:50:11THE SITE ADDRESS FOR THIS BLDG 3 REMAINS AS IT IS AS
 1019 21ST ST , WEST PALM BEACH, FL 33407.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-01-10 Cont ID  
Sent By lursu Date 2008-01-10 Time 09:32 Rev Time 0.00
Received By lursu Date 2008-01-10 Time 09:32 Sent To  
Notes
2008-01-10 09:36:26***FAILED***
  
 SINCE ON THIS PROPERTY FOUR STRUCTURES ARE EXISTING AND
 TWO OF THEM ARE USING A FRACTIONAL SITE ADDRESS ,AN
 ADDRESS CHANGE WILL OCCUR ,THEREFORE TO HAVE THE
 CORRECT SITE ADDRESS ASSIGNED TO EACH OF THE
 STRUCTURES, PLEASE PROVIDE A LOCATION MAP WITH ALL
 EXISTING ADDRESSES TO THIS DEPARTMENT AND AFTER THE
 REVIEWNEW ADDRESSES WILL BE ASSIGNED IN THE CORRECT
 ORDERTO EACH STRUCTURE.
  
 QUESTIONS/COMMENTS
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-13 Cont ID  
Sent By jgomez Date 2008-06-13 Time 10:26 Rev Time 0.00
Received By jgomez Date 2008-06-13 Time 10:25 Sent To PC
Notes
2008-06-13 10:41:43PERMIT VALUATION UPDATED TO INCLUDE REVISED SCOPE OF
 WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By jgomez Date 2008-01-28 Time 15:41 Rev Time 0.00
Received By jgomez Date 2008-01-28 Time 15:41 Sent To AD
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-09 Cont ID  
Sent By jgomez Date 2008-01-09 Time 16:52 Rev Time 0.00
Received By jgomez Date 2008-01-09 Time 16:52 Sent To P
Notes
2008-01-09 16:52:50RESIDENTIAL RENOVATION, BUILDING REVIEWCHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THE PERMIT VALUATION NEEDS TO BE UPDATED TO
 INCLUDE ALL SCOPE OF WORK TO BE PERFORMED, INCLUDING
 BUILDING, PLUMBING, ELECTRICAL AND MECHANICAL WORK
 SPECIFIED ON PERMIT APPLICATION AND PLANS. SEC.
 108.3 CITY AMENDMENTS OT FBC 2004. (REPEAT COMMENT).
  
 2-PROVIDE ONLY THE INFORMATIONTHAT IS RELEVANT TO
 THE SCOPE OF WORK TO BE PERFORMED.IF NOT WORK IS DONE
 ON EXTERIOR WALLS, THEN EXTERIOR ELEVATIONS AND TYPICAL
 WALL SECTIONS ARE NOT REQUIRED.THIS CONFUSES THE
 SCOPE OF WORK TO BE PERFORMED ANDTOTAL PERMIT
 VALUATION.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004.
  
 3- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.SOME DRAWINGS ARE
 MISSING THE SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004.
  
 4-DESIGNER OF RECORDTO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- ENERGY CALCULATIONS: REVISE ITEM #10(A)AND TABLE
 6C-1.NEED R-30AS THE MINIMUM INSULATION. ALSO,
 REVISE MINIMUM INSULATION FOR DUCT. SEE TABLE 6C-1 AND
 COMMENTS BY MECHANICAL PLAN REVIEWER.
  
 6-ACCORDING TO PERMIT APPLICATION SCOPE OF WORK
 INCLUDES ONLY ONE WINDOW TO BE REPLACED.SEC. 507.3
 EXCEPTION #1 DOESN'T REQUIRE SHUTTERS IFLESS THAN 25%
 OF THEHOUSE GLASS AREA IS REPLACED.
 NOTE:IS HIGHLY RECOMMENDED TO PROTECT ALL OPENINGS,
 BUT IS NOT REQUIRED FOR THE SCOPE OF WORKSTIPULATED
 IN THE PERMIT APPLICATION.
  
 7- PLEASE COORDINATE WITH ZONING REGARDING LOCATION OF
 A/C UNITS AND REQUIRED SETBACKS. CALL CHRIS HOOPS AT
 805-6720 FOR REQUIRED INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-30 Cont ID  
Sent By btrobaug Date 2008-04-30 Time 12:54 Rev Time 0.00
Received By btrobaug Date 2008-04-30 Time 12:40 Sent To B
Notes
2008-04-30 12:53:54 
  
  
  
  
  
 PROVISO
  
 THE PLANS ARE BEGINNING TO LACK CLARITY DUE TO NOTES
 AND INFORMATION BEING COPIED. IF THIS PLAN IS SUBMITTED
 FOR REVISION IN THE FUTURE, SEPARATE THE ELECTRICAL
 PLAN FROM THE ARCHITECTURAL AND REMOVE ALL CLOUDS
 EXCEPT THE ONES PERTAINING TO THAT REVISION. 106.1.3
 FBC AS AMENDED. SEE REDLINED RECEPTACLES AS REQUIRED
 PER 210.52(A)(1).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By btrobaug Date 2008-01-25 Time 12:34 Rev Time 0.00
Received By btrobaug Date 2008-01-25 Time 06:46 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By btrobaug Date 2008-01-03 Time 09:49 Rev Time 0.00
Received By btrobaug Date 2008-01-03 Time 09:30 Sent To M
Notes
2008-01-03 09:48:55 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES
 "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN
 BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS
 CLEAR,106.1.1 FBC AS AMENDED.
  
 2} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE
 PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS
 MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO
 NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL
 LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED,
 (SEE 1500 VA).
  
 3} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT
 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE
 SAME.
  
 4} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 5} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT
 210.52(A)(1), IN THE DINING ROOM ON THE A/C WALL.
  
 6} NFPA-72 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET
 OF COOKING APPLIANCES BE SILENCING OR PHOTOELECTRIC.
 SEE 11.8.3.5(4).
  
 7} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 THE BACK BEDROOM DOES NOT HAE ONE "OUTSIDE".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-11 Cont ID  
Sent By adarroug Date 2008-06-11 Time 16:09 Rev Time 0.00
Received By adarroug Date 2008-06-11 Time 16:09 Sent To B
Notes
2008-06-11 16:10:15TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 12:03 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 12:03 Sent To E
Notes
2008-04-29 12:03:37TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 10:15 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 10:15 Sent To E
Notes
2008-01-18 10:15:34TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-10 Cont ID  
Sent By adarroug Date 2008-01-10 Time 10:14 Rev Time 0.00
Received By adarroug Date 2007-12-31 Time 12:07 Sent To E
Notes
2007-12-31 12:07:46TO BILL TROBAUGHS DESK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-01 Cont ID  
Sent By tgordon Date 2008-05-01 Time 13:53 Rev Time 0.20
Received By tgordon Date 2008-05-01 Time 13:53 Sent To  
Notes
2008-05-01 13:53:41REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By tgordon Date 2008-01-25 Time 16:12 Rev Time 0.20
Received By tgordon Date 2008-01-25 Time 16:12 Sent To P
Notes
2008-01-25 16:12:39*** PROVISO ***
 1) PROVIDE RETURN AIR TO ALL REQUIRED SPACES AND BACK
 TO AIR HANDLER, SEE 2004 FBC/R M1602.4. THE RETURN AIR
 MAY NOT COME FROM THE KITCHEN, SEE 2004 FBC/R M1602.2.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By tgordon Date 2008-01-03 Time 12:09 Rev Time 0.20
Received By tgordon Date 2008-01-03 Time 12:09 Sent To P
Notes
2008-01-03 12:11:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS LINE 10A IS SHOWING R-19 FOR
 UNDER ATTIC, TABLE 6C-1 ON BACK OF ENERGY CALCULATIONS
 STATES MINIMUM INSULATION FOR UNDER ATTIC IS R-30, SEE
 2004 FBC 13-604.1.C.1, PLEASE CORRECT.
  
 2) SHOW ATTIC INSULATION AND R. VALUE ON BUILDING PLAN
 PAGE 2, SEE 2004 FBC 13-604.1.C.1.
  
 4) PROVIDE RETURN AIR TO BEDROOMS, SEE 2004 FBC/R
 M1602.4.
  
 5) MECHANICAL PLAN SHOWS A 10" AND A12" DUCT GOING TO
 THE MIXING BOX NEAR THE AIR HANDLER, THIS APPEARS TO BE
 AN ERROR (SEE YELLOW HIGH LIGHT ON MECH. PLAN), SEE
 2004 FBC 106.1.1, PLEASE CORRECT.
  
 6) SHOW IN THE A/C EQUIPMENT SCHEDULE THE MODEL NUMBERS
 FOR THE AIR HANDLER AND CONDENSER UNIT, ALSO THE TOTAL
 BTU'S, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-30 Cont ID  
Sent By mperson Date 2008-04-30 Time 16:43 Rev Time 0.00
Received By mperson Date 2008-04-30 Time 16:43 Sent To M
Notes
2008-04-30 16:45:41REVISION SHEET 1: "OK" DELETED PLUMBING FIXTURE LAYOUT
 FROM MECHANICAL PLANS, PLUMBING FIXTURE LAYOUT PER
 APPROVED FLOOR PLAN. RELOCATED WATER HEATER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By mperson Date 2008-01-28 Time 08:31 Rev Time 0.00
Received By mperson Date 2008-01-28 Time 08:31 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By mperson Date 2008-01-04 Time 09:34 Rev Time 0.00
Received By mperson Date 2008-01-04 Time 09:34 Sent To B
Notes
2008-01-04 09:36:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 1. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY. **SHEETS #2
 AND #3 ARE NOT SIGNED ON BOTH SETS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  