Plan Review Details - Permit 07120627
Plan Review Stops For Permit 07120627
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-15 Cont ID  
Sent By rmcdouga Date 2008-01-15 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2008-01-15 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-09 Cont ID  
Sent By rmcdouga Date 2008-01-09 Time 07:37 Rev Time 0.00
Received By rmcdouga Date 2008-01-09 Time 07:13 Sent To  
Notes
2008-01-09 08:08:022004 FBC W/2007 REVISIONS
 BATH REMODELROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE APPLICABLE CODE UNDER WHICH THE PROJECT
 HAS BEEN DESIGNED (2004 FBC W/2007 REVISIONS).
  
 3) SPECIFY TEMPERED GLASS AT THE NEW SHOWER ENCLOSURE
 AS REQUIRED BY FBC R 308.3.
  
 4) SHOW COMPLIANCE WITH FBC R307.2 BATHTUB AND SHOWER
 SPACES.
 BATHTUB AND SHOWER FLOORS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS AND IN SHOWER COMPARTMENTS SHALL
 BE FINISHED WITH A NONABSORBENT SURFACE. SUCH WALL
 SURFACES SHALL EXTEND TO A HEIGHT OF NOT LESS THAN 6
 FEET (1829 MM) ABOVE THE FLOOR.
  
 5) COMPLY WITH COMMENTS OF OTHER REVIEWERS.
  
 -ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-11 Cont ID  
Sent By btrobaug Date 2008-01-11 Time 10:26 Rev Time 0.00
Received By btrobaug Date 2008-01-11 Time 10:26 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By btrobaug Date 2007-12-31 Time 12:52 Rev Time 0.00
Received By btrobaug Date 2007-12-31 Time 12:43 Sent To P
Notes
2007-12-31 12:52:44 
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 2} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.INDICATE
 SAME ON PLANS, SHOW LOCATIONS OR MAKE A NOTE.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 09:01 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 09:01 Sent To E
Notes
2008-01-10 09:01:28TO BILL TROBAUGHS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-09 Cont ID  
Sent By rmcdouga Date 2008-01-09 Time 07:37 Rev Time 0.00
Received By rmcdouga Date 2007-12-27 Time 15:39 Sent To  
Notes
2007-12-27 15:39:23TO SFR "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 16:06 Rev Time 0.20
Received By tgordon Date 2007-12-27 Time 16:06 Sent To E
Notes
2007-12-27 16:07:26NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-11 Cont ID  
Sent By mperson Date 2008-01-11 Time 16:34 Rev Time 0.00
Received By mperson Date 2008-01-11 Time 16:34 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By btrobaug Date 2008-01-02 Time 12:24 Rev Time 0.00
Received By mperson Date 2008-01-04 Time 14:31 Sent To B
Notes
2008-01-04 14:33:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FOR THE
 SHOWER ON THE RESUBMITTAL.
 A} 417.4.1 WALL AREA.
 THE WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER
 HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED
 OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF
 MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT
 THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT
 WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR
 SHOWER FLOOR.
  
 B} 424.3 SHOWER VALVES.
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR CSA B125.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]