Plan Review Details - Permit 07120601
Plan Review Stops For Permit 07120601
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-28 Cont ID  
Sent By mjacobs Date 2008-02-28 Time 08:14 Rev Time 0.00
Received By mjacobs Date 2008-02-28 Time 07:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-18 Cont ID  
Sent By mjacobs Date 2008-01-18 Time 07:20 Rev Time 0.00
Received By mjacobs Date 2008-01-18 Time 06:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By mjacobs Date 2008-01-04 Time 12:56 Rev Time 0.00
Received By mjacobs Date 2008-01-04 Time 11:28 Sent To  
Notes
2008-01-04 12:56:19 
  
 BUILDING PLAN REVIEW
 PERMIT: 07120601
 ADD: 900 S. DIXIE HWY.
 CONT: MINUTEMAN CONST.
 TEL: (561)791-1637
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 1-4-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING WHERE ALL THE CHANGES ARE MADE. THE PLANS
 SUBMITTED SHOW THE SAME FLOOR LAY-OUT. PROVIDE A WALL
 LEGEND INDICATING ALL WALLS TO BE DEMOED AND ALL NEW
 WALLS. SHOW THE ATTACHMENT DETAIL FOR THE NEW WALLS,
 AND INDICATE IF THE WALL WILL BE ATTACHED TO THE
 STRUCTURE ABOVE. A REFLECTED CEILING PLAN IS REQUIRED
 WITH THE HEIGHT AND TYPE OF CEILING TO BE INSTALLED
 THROUGH-OUT THE AREA. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISION OF THIS CODE. FBC
 106.1.1.
  
 3) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY. A FINISH SCHEDULE
 SHALL BE SUBMITTED FOR EACH ROOM AFFECTED BY THE NEW
 CONSTRUCTION.
  
 4)FBC 11-7.2(2)(I) A PORTION OF THE RECEPTIONIST
 COUNTER SHALL HAVE A MINIMUM OF 36 INCHES IN LENGTH AND
 SHALL HAVE A MAXIMUM HEIGHT OF 36 INCHES. PROVIDE AN
 ELEVATION DETAIL DRAWING SHOWING COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-27 Cont ID  
Sent By btrobaug Date 2008-02-25 Time 16:51 Rev Time 0.00
Received By btrobaug Date 2008-02-25 Time 16:46 Sent To  
Notes
2008-02-25 16:51:24 

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 12:49 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 11:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By btrobaug Date 2008-01-02 Time 11:31 Rev Time 0.00
Received By btrobaug Date 2008-01-02 Time 08:34 Sent To  
Notes
2008-01-02 11:31:30 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A
 CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY
 TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL,
 IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS)
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE PUT A ON
 THE PLAN FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-28 Cont ID  
Sent By mawillia Date 2008-02-28 Time 16:59 Rev Time 0.00
Received By mawillia Date 2008-02-28 Time 16:47 Sent To  
Notes
2008-02-28 16:53:46*****REVISION, FEB. 2008, APPROVED*****
  
  
 REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By mwennerg Date 2008-01-22 Time 13:49 Rev Time 0.00
Received By mwennerg Date 2008-01-22 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-01-04 Cont ID  
Sent By mwennerg Date 2008-01-04 Time 14:32 Rev Time 0.00
Received By mwennerg Date 2008-01-04 Time 14:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-25 Cont ID  
Sent By adarroug Date 2008-02-25 Time 11:47 Rev Time 0.00
Received By adarroug Date 2008-02-25 Time 11:47 Sent To  
Notes
2008-02-25 11:51:49TO "COMM" BD#58

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 10:52 Sent To  
Notes
2008-01-14 10:54:13TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-04 Cont ID  
Sent By mwennerg Date 2008-01-04 Time 14:32 Rev Time 0.00
Received By mwennerg Date 2007-12-26 Time 14:55 Sent To  
Notes
2007-12-27 08:16:29TO BOB BOARD # 12
2007-12-26 14:56:01WAITING FOR "BOB" BOARD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-26 Cont ID  
Sent By tgordon Date 2008-02-26 Time 11:53 Rev Time 0.30
Received By tgordon Date 2008-02-26 Time 11:53 Sent To  
Notes
2008-02-26 11:54:02REVISION TO MECHANICAL PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-15 Cont ID  
Sent By tgordon Date 2008-01-15 Time 13:39 Rev Time 0.20
Received By tgordon Date 2008-01-15 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 15:16 Rev Time 0.45
Received By tgordon Date 2007-12-27 Time 15:16 Sent To  
Notes
2007-12-27 15:34:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PROPOSED FLOOR PLAN SHOWS TWO NEW SUPPLY AIR GRILLS
 AND ONE NEW RETURN AIR GRILL. PLEASE SHOW ON PLAN ALL
 NEEDED SUPPLY AND RETURN AIR GRILLS, LISTED AS NEW OR
 EXISTING FOR NEW OFFICES 1, 2, 3, AND TRAINING ROOM.
 SHOW ALL NEW DUCT SIZES AND CFM'S. SEE 2004 FBC/M 401.2
 AND 601.4.
  
 2) PLAN ALSO SHOWS NEW DOORS BEING INSTALLED IN
 EXISTING OFFICES 4, 5, 6, AND LOBBY. IF DOORS ARE
 REPLACEMENTS PLEASE STATE SO ON PLAN, IF NOT, SHOW
 SUPPLY AND RETURN AIR TO THESE IN-CLOSED SPACES, LISTED
 AS NEW OR EXISTING. SEE 2004 FBC/M 401.2 AND 601.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-26 Cont ID  
Sent By jleech Date 2008-02-26 Time 08:03 Rev Time 0.00
Received By jleech Date 2008-02-26 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By jleech Date 2008-01-22 Time 07:38 Rev Time 0.00
Received By jleech Date 2008-01-22 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-01-03 Cont ID  
Sent By jleech Date 2008-01-03 Time 07:41 Rev Time 0.00
Received By jleech Date 2008-01-03 Time 07:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-28 Cont ID  
Sent By choops Date 2007-12-28 Time 11:11 Rev Time 0.00
Received By choops Date 2007-12-28 Time 11:11 Sent To  
Notes
2007-12-28 11:12:06*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.