Plan Review Details - Permit 07120585
Plan Review Stops For Permit 07120585
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-02-26 Cont ID  
Sent By lursu Date 2008-02-26 Time 08:17 Rev Time 0.00
Received By lursu Date 2008-02-26 Time 08:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-08 Cont ID  
Sent By jwitmer Date 2008-05-08 Time 16:34 Rev Time 3.55
Received By jwitmer Date 2008-05-08 Time 16:34 Sent To  
Notes
2008-05-08 16:39:06REVISION DATES FOR A SHEETS:
 1-17-08
 1-28-08
 2/08-08
 2/11/08
 2/14/08
 3/25/08
 4/16/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By jwitmer Date 2008-03-11 Time 16:47 Rev Time 0.56
Received By jwitmer Date 2008-03-11 Time 16:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-11 Cont ID  
Sent By jwitmer Date 2008-02-11 Time 08:47 Rev Time 1.00
Received By jwitmer Date 2008-02-11 Time 08:47 Sent To  
Notes
2008-02-11 09:00:00J. B. HGANOVER & CO.
 JAN. 04, 2008
 BUILDING PLAN REVIEW
 PERMIT: 07120585
 ADD: 525 OKEECHOBEE BLVD. SUITE 700
 CONT: PASS INTERNATIONAL
 TEL: (954)421-9000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)INFORMATIONAL
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) AT THIS POINT IN TIME THE BUILDING DEPARTMENET HAS
 NOT RECEIVED THIS LETTER, THE SHELL BUILDING HAS NOT
 ACHIEVED A CERTIFICATE OF COMPLETION, THE CONTRACTOR
 FOR THIS TENANT SPACE IS DIFFERENT FROM THE "BASE
 BUILDING" AND WILL REQUIRE A LETTER FROM THE BASE
 BUILDING CONTRACTOR ALLOWING PASS INTERNATIONAL TO
 START WORK ON THIS TENANT SPACE BEFORE THE CERTIFICATE
 OF COMPLETION FOR THE BASE BUILDING HAS BEEN ISSUED.
 THE DEVELOPER AND BOTH G.C.'S WILL HAVE TO SUBMIT A
 LETTER STATING THAT THEY UNDERSTAND THAT ANY DISPUTE
 OVER RESPONSIBILITY DOES NOT RELIEVE THEM FROM THE
 JOINT RESPONSIBILITY TO COMPLY WITH THE BUILDING CODE.
 . 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 4-8) COMPLIED.
  
 9) NEW COMMENT DEALS WITHTHE OWNER TO SUPPLY THE CITY
 WITH A LETTER OF FORM, FL S S 553.791 (4) (C)AN
 ACKNOWLEDGMENT FROM THE FEE OWNER IN SUBSTANTIALLY THE
 FOLLOWING FORM:
  
 I HAVE ELECTED TO USE ONE OR MORE PRIVATE PROVIDERS TO
 PROVIDE BUILDING CODE PLANS REVIEW AND/OR INSPECTION
 SERVICES ON THE BUILDING OR STRUCTURE THAT IS THE
 SUBJECT OF THE ENCLOSED PERMIT APPLICATION, AS
 AUTHORIZED BY S. 553.791, FLORIDA STATUTES. I
 UNDERSTAND THAT THE LOCAL BUILDING OFFICIAL MAY NOT
 REVIEW THE PLANS SUBMITTED OR PERFORM THE REQUIRED
 BUILDING INSPECTIONS TO DETERMINE COMPLIANCE WITH THE
 APPLICABLE CODES, EXCEPT TO THE EXTENT SPECIFIED IN
 SAID LAW. INSTEAD, PLANS REVIEW AND/OR REQUIRED
 BUILDING INSPECTIONS WILL BE PERFORMED BY LICENSED OR
 CERTIFIED PERSONNEL IDENTIFIED IN THE APPLICATION. THE
 LAW REQUIRES MINIMUM INSURANCE REQUIREMENTS FOR SUCH
 PERSONNEL, BUT I UNDERSTAND THAT I MAY REQUIRE MORE
 INSURANCE TO PROTECT MY INTERESTS. BY EXECUTING THIS
 FORM, I ACKNOWLEDGE THAT I HAVE MADE INQUIRY REGARDING
 THE COMPETENCE OF THE LICENSED OR CERTIFIED PERSONNEL
 AND THE LEVEL OF THEIR INSURANCE AND AM SATISFIED THAT
 MY INTERESTS ARE ADEQUATELY PROTECTED. I AGREE TO
 INDEMNIFY, DEFEND, AND HOLD HARMLESS THE LOCAL
 GOVERNMENT, THE LOCAL BUILDING OFFICIAL, AND THEIR
 BUILDING CODE ENFORCEMENT PERSONNEL FROM ANY AND ALL
 CLAIMS ARISING FROM MY USE OF THESE LICENSED OR
 CERTIFIED PERSONNEL TO PERFORM BUILDING CODE INSPECTION
 SERVICES WITH RESPECT TO THE BUILDING OR STRUCTURE THAT
 IS THE SUBJECT OF THE ENCLOSED PERMIT APPLICATION.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By jwitmer Date 2008-01-04 Time 08:20 Rev Time 3.33
Received By jwitmer Date 2008-01-04 Time 08:19 Sent To  
Notes
2008-01-04 10:36:05J. B. HGANOVER & CO.
 JAN. 04, 2008
 BUILDING PLAN REVIEW
 PERMIT: 07120585
 ADD: 525 OKEECHOBEE BLVD. SUITE 700
 CONT: PASS INTERNATIONAL
 TEL: (954)421-9000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. SHEET A-0.1.1
 PLEASE UPDATE APPLICABLE CODES TO THE CURRENT
 2007 FBC SUPPLEMENTS.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE OF
 COMPLETION, THE CONTRACTOR FOR THIS TENANT SPACE IS
 DIFFERENT FROM THE "BASE BUILDING" AND WILL REQUIRE A
 LETTER FROM THE BASE BUILDING CONTRACTOR ALLOWING PASS
 INTERNATIONAL TO START WORK ON THIS TENANT SPACE BEFORE
 THE CERTIFICATE OF COMPLETION FOR THE BASE BUILDING HAS
 BEEN ISSUED. THE DEVELOPER AND BOTH G.C.'S WILL HAVE TO
 SUBMIT A LETTER STATING THAT THEY UNDERSTAND THAT ANY
 DISPUTE OVER RESPONSIBILITY DOES NOT RELIEVE THEM FROM
 THE JOINT RESPONSIBILITY TO COMPLY WITH THE BUILDING
 CODE.
 . 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 5)PLEASE SEE DISCREPANCY BETWEEN THE SUITE NUMBER ON
 THE PERMIT APLICATION AND SHEET A-1.7.1. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 6)SHEET A-3.7.1 PLEASE SEE DETAIL NUMBER (3) THE
 RECEPTION DESK INDICATES A GRANITE STONE TRANSACTION
 TOP WITH S S POST AT A HEIGTH OF 3'-6", PLEASE PROVIDE
 COMPLIANCE WITH 11-7.2 SERVICE COUNTERS.
  
 7) SHEET A-6.7.1 & A-6.7.2 BOTH INDICATE VARIOUS WALL
 DETAILS WHERE 2X4 WOOD BACKING WILL BE REQUIRED, PLANS
 DO NOT INDICATE THAT IN TYPE I & TYPE II BUILDING NO
 COMBUSTIBLE ALLOWED IN WALLS WITH THE EXCEPTION OF FIRE
 RETARDANT TREATED WOOD, SEE 603.1(1).
  
 8) SHEET A-7.7.1 DOOR SHCEDULE UNDER THE DOOR RATING
 COLUMN INDICATE FIRE RATED DOORS AS "C" LABEL, PLEASE
 SEE TABLE 715.3 RATES DOORS IN MINUTES AND HOURS.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 16:03 Sent To PC
Notes
2008-09-30 16:03:56LIGHTING CIRCUITS 1 AND 3 ON PANEL HA ARE ON OCCUPANCY
 SENSORS AND NOT ON TCA SCHEDULE.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-08-29 Cont ID  
Sent By dpalmer Date 2008-08-29 Time 09:34 Rev Time 0.00
Received By dpalmer Date 2008-08-29 Time 09:34 Sent To  
Notes
2008-08-29 09:34:52** DENIED REVISION **
  
  
  
 1) NOTE: PLEASE SEE SHEET E6.1 WHICH INDICATES SEVERAL
 LIGHTING CIRCUITS WHICH ARE NOT LISTED ON THE LIGHTING
 CONTACTOR DETAIL. PLEASE SEE THE LIGHTING CONTACTOR
 DETAIL AND SCHEDULE ONLY INDICATES TWO CIRCUITS. PLEASE
 BE SURE TO COORDINATE WITH PLANS.
  
 ** CALLED ENGINEER AS OF REVIEW TO OVER COMMENTS
 HOWEVER WAS OUT OF THE OFFICE.
  
 ** OTHER SHEETS MAY BE OK, HOWEVER IF NO OTHER CHANGES
 ON OTHER SHEETS ARE NEEDED PLEASE BE SURE BRING BACK
 SHEETS WITH THE SIGNED AFFIDAVITS.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-07-15 Cont ID  
Sent By dpalmer Date 2008-07-15 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2008-07-15 Time 13:15 Sent To PC
Notes
2008-07-15 13:15:22** DENIEDREVISIONS **
  
  
 1) NOTE:THE SHEET E 6.1( REV 11) SUBMITTED NOW DOES
 NOT COORDINATE WITH THE PREVIOUS SUBMITTED POWER PLANS
 AND LIGHTING PLANS FOR CIRCUITING. PLEASE SUBMIT
 REVISED LIGHTING AND POWER PLANS WITH REVISED
 CIRCUITING ETC.
 408.4, 310.16, 240.4, 220, ETC
 FBC 106.1.2, 106.1.1
  
 PLEASE COORDINATE.
  
 2) NOTE: PLEASE EXPLAIN HOW/WHY THE DATE THE ENGINEER
 OF RECORD CONTAINS WHITE OUT AND IS DATED AFTER THE
 DATE OF BASE BUILDING DESIGNER AND ACTUAL DATE PLANS
 WERE SIGNED AND SEALED.
 SOME SHEETS ARE DATED 5/22 AND ONE SHEET CONTAINS THE
 WHITE OUT AND NEW DATE OF 6/4/08. NO INDIVIDUAL IS
 PERMITTED TO PLACE WHITE OUT ON PLANS AND MODIFY
 ANYTHING WHICH WAS DONE BY THE ENGINEER OF RECORD.
 FS 471.025
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-05-12 Cont ID  
Sent By dpalmer Date 2008-05-12 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2008-05-12 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 05:49 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 05:49 Sent To  
Notes
2008-05-05 05:49:07** DENIED REVISIONS **
  
 REVISIONS LABELED AS REV#2
  
  
 525 OKEECHOBEE BLVD
 SUITE #800 JB HANAUER
  
  
 1) NOTE: PLEASE COORDINATE ALL REVISIONS. PLEASE SEE
 THESE REVISIONS SUBMITTED 4/29/08 ARE LABELED AS
 *REVISIONS #2* HOWEVER *REVISIONS #1 WERE ALREADY
 SUBMITTED ON THE SAME DATE FOR REVIEW WHICH CONTAIN
 SEVERAL SHEETS WHICH SUPERSEDE SHEETS IN THIS SET.
 PLEASE SEE FOR EXAMPLE SHEETS E2.1,3.1,4.1 AND 5.1 WERE
 ALREADY DONE WITH REVISION DATES AFTER THESE.
 PLEASE ALSO SEE THERE ARE SHEETS IN THESE SETS OF PLANS
 WHICH DO NOT CONTAIN ANY REVISIONS FROM PERMITTED
 PLANS. AN EXAMPLE OF THIS WOULD BE SHEET E2.2.
 PLEASE SEE THERE ARE RESPONSE SHEETS AND COMMENTS
 SHEETS ATTACHED TO THE LEFT HAND SIDE OF PLANS WHICH
 ARE FROM BEFORE THE PERMIT WAS ISSUED. PLEASE SEE SOME
 OF THESE SHEETS INCLUDE THIS OFFICE REVIEW COMMENTS
 FROM INITIAL AUDIT.
  
 ** PLEASE ONLY SUBMIT PLANS AND DOCUMENTS WHICH ARE
 RELEVANT AND WHICH ACTUALLY HAVE BEEN REVISED FROM
 PERMITTED SETS OF PLANS.
 PLEASE COORDINATE ALL PRIVATE PROVIDER AFFIDAVITS ETC
  
 FBC 106.5, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION OF RECORD SETS OF PLANS.
 FS 553.791
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 05:30 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 17:12 Sent To  
Notes
2008-05-05 05:31:32REVISIONS LABELED AS REV #1OK WITH ELECTRICAL. THIS IS
 FOR SHEETS E2.1,3.1, 4.1 AND 5.1.
 ONCE FIRE MARSHAL IS DONE, WILL NEED TO RETAINED ONE
 SET OF ELECTRICAL FOR FILE.
  
 DO NOT RELEASE UNTIL ONE SET IS RETAINED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-11 Cont ID  
Sent By dpalmer Date 2008-03-11 Time 11:50 Rev Time 0.00
Received By dpalmer Date 2008-03-11 Time 11:49 Sent To  
Notes
2008-03-11 11:50:32MR. CARTER PERSONALLY APPEARED IN OFFICE AND SIGNED
 SHEETS IN BOTH SETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 17:48 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 17:48 Sent To  
Notes
2008-03-04 17:48:26** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE NEW SHEET E2.1IS NOT SIGNED
 BY ENGINEER AS ON OTHER SHEETS OR DOES NOT CORRELATE
 WITH SIGNATURE ALREADY ON FILE FOR SAID ENGINEER. FS
 471.025
 THERE ARE TWO OPTIONS:
 OPTION #1: ENGINEER OF RECORD MR. LON CARTER MAY SET
 UP A TIME TO COME IN PERSONALLY AND SIGN SHEETS.
 OPTION #2: NEW SHEET E2.1 MAY BE SIGNED, DATED AND
 SEALED, SENT TO PRIVATE PROVIDER FOR RE-STAMPING AND
 THEN SENT TO BASE BUILDING ENGINEER OF RECORD FOR
 RE-STAMPING AND SIGNING AS *SHOW DRAWING REVIEW*. ONCE
 THAT IS DONE PLEASE BRING SHEET INTO DEPARTMENT TO BE
 INSERTED INTO SETS.
  
 EITHER OPTION WILL NOT BE A FEE FOR RE-SUBMITTAL.
 AS THE SHEETS ARE OK, ELECTRICAL SHEETS ARE BEING
 STAMPED. PLANS WILL NOT BE RELEASED UNTIL SIGNED, OR
 NEW SHEETS ARE BROUGHT IN FOR STAMPING.
  
 2) NOTE: PLEASE SEE THE LETTER OF UNDERSTANDING BETWEEN
 CONTRACTORS FOR BASE BUILDING AND BUILD OUT IS NOT
 ORIGINAL. IN FACT THIS IS A COLOR-PHOTOCOPY. THIS WAS
 CONFIRMED WITH BUILDING OFFICIAL THAT IT DOES NEED TO
 BE ORIGINAL.
 A NEW ORIGINAL LETTER MAY BE SUBMITTED AT ANYTIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-10 Cont ID  
Sent By dpalmer Date 2008-02-10 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2008-02-10 Time 09:07 Sent To  
Notes
2008-02-11 09:07:19** DENIED REVIEW**
  
 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED
 PER FS 553.791(4)(C) WAS NOT SUBMITTED.
  
 2) NOTE: PLEASE KNOW THE LETTER OF AGREEMENT BETWEEN
 CONTRACTORS REQUIRED.
  
 3) NOTE: PLEASE SEE TWO FIXTURES MISSING DESIGNATIONS.
 PLEASE SEE ARE WORK AREA 771 AND ALSO FIXTURE IN
 BETWEEN CORRIDOR 778 AND 777.
 THESE COULD BE REDLINED AND PART OF A PROVISO HOWEVER
 THIS IS A PRIVATE PROVIDER PROJECT AND THIS MAY NOT BE
 DONE.
 PLEASE OBTAIN REVISED SHEET FOR LIGHTING IN ALL THREE
 SETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-30 Cont ID  
Sent By dpalmer Date 2007-12-30 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2007-12-30 Time 15:57 Sent To  
Notes
2007-12-30 15:57:52 
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE BASE BUILDING ELECTRICAL
 ENGINEER OF RECORD SIGNS BLOCK STAMPS FOR REVIEW.
 PLEASE KNOW THIS BUILDING DOES NOT HAVE A CERTIFICATE
 OF OCCUPANCY AND UNTIL SUCH TIME THE BASE BUILDING
 ENGINEER OF RECORD IS RESPONSIBLE AND NEEDS TO BE MADE
 AWARE OF ANY BASE BUILDING DESIGNS/LOADS/ LIGHTING
 PERFORMANCE CALCULATIONS ETC.
 FS 471
  
 2) NOTE: PLEASE KNOW THE SUITE/UNIT NUMBER WHICH WAS
 PLACED ON PERMIT APPLICATION WAS SUITE #700. PLEASE
 VERIFY AND IF DETERMINED AS ACCURATE PLEASE PLACE ON
 TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMIN 106.5,
 106.1.2
  
 3) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS AS NOTED STATE THESE ARE DONE FOR *SPACE
 BY SPACE* YET THE CALCULATIONS SHOW ONLY OFFICE AREA.
 THIS IS NOT POSSIBLE AS THERE ARE SEVERAL OTHER TYPES
 OF ROOMS WHICH ARE NOT OFFICE.
 PLEASE ADJUST CALCULATIONS.
 PLEASE ALSO SEE THE NUMBER OF FIXTURES ON PLANS NEED TO
 COORDINATE WITH THE TOTALS ON THE LIGHTING POWER
 CALCULATIONS.
 PLEASE SEE FOR EXAMPLE:
 THE NUMBER OF *A* FIXTURES DO NOT CORRELATE,
 THE *B*,*BE*,*C* AND *CE* ALSO NEED ADJUSTING.
  
 THESE WERE NOTED FOR A COUPLE OF EXAMPLES.
  
 4) NOTE: PLEASE BE SURE TO CORRELATE ROOM DESIGNATIONS
 FROM SHEET TO SHEET. PLEASE SEE FOR EXAMPLE:
 SHEET E2.1 AND 3.1 WHICH SHOWS ELECTRICAL ROOM AND DATA
 ROOM SWITCHED FROM SHEET 6.1.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE BE SURE TO GO OVER ALL LOAD ON LIGHTING
 AND OTHER LOADS SHOWN ON PANELS.
 PLEASE SEE FOR EXAMPLE: THE LIGHTING LOAD SHOWN ON
 PANEL *H7A-7* IS SHOWN AS 1.1 KVA WHICH IS NOT POSSIBLE
 BASED ON THE AMOUNT OF FIXTURES SHOWN ON THIS CIRCUIT
 ON LIGHTING PLANS E2.1.
 PLEASE ADJUST ALL LOAD CALCULATIONS.
 NEC 220.
 FBC 106.3.5.1
  
 6) NOTE: PLEASE SEE PANEL *L7A* IS BEING SHOWN AS A
 250AMP MCB PANEL WITH FEED-THRU LUGS TO PANEL *L7B* YET
 *L7B* IS SHOWN ONLY RATED AT 225AMPS. THIS PLACES OVER
 CURRENT PROTECTION ON PANEL WHICH IS HIGHER THAN THE
 MAXIMUM RATING OF ITS LISTING.
 PLEASE ADJUST.
 ( CONDUCTORS ON RISER ARE SHOWN RATED AT THE 250AMPS)
 90.7, 110.3.
  
 7) NOTE: PLEASE SEE PANEL *L7A* AS THE LOAD
 CALCULATIONS SHOWS AND INDICATES LOADS FROM PANELS
 *L8A* AND *L8B*, YET THE RISER, PLANS AND PANELS DO NOT
 SHOW ANY *8TH* LEVEL PANELS.
 THIS APPEARS TO BE A MISPRINT BASED ON PANELS AND LOADS
 SHOWN.
 PLEASE COORDINATE.
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE CODES LISTED ON SHEET E0.1 SHOW
 2006 NFPA-101 AND 2007 NFPA-72.
 PLEASE KNOW AS OF THIS DATE OF REVIEW THIS OFFICE KNOWS
 OF NO CHANGE TO THE LATEST STATE ADOPTION OF THESE
 CODES.
 PLEASE SEE THE FOLLOWING ARE THE CURRENT EDITIONS OF
 CODES STATED AND KNOWN TO THIS OFFICE.
 2003 NFPA-101
 2002 NFPA-72
 ** THIS WAS VERIFIED *ON-LINE* AT THE STATE WEBSITE AS
 OF THISREVIEW WHICH STILL SHOWS 2003 AND 2002
 EDITIONS.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-06-20 Cont ID  
Sent By mawillia Date 2008-06-20 Time 15:22 Rev Time 0.00
Received By mawillia Date 2008-06-20 Time 14:52 Sent To  
Notes
2008-06-20 15:21:08*****REVISION #1, DATED 5/15/08, APPROVED****
  
 THERE WERE NO REVISIONS/CHANGES TO SHEETS (FA-03 &
 FA-04);SHEETS FA-00, FA-01, FA-02, & FA-05 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-06-02 Cont ID  
Sent By mawillia Date 2008-06-02 Time 16:42 Rev Time 0.00
Received By mawillia Date 2008-06-02 Time 15:50 Sent To  
Notes
2008-06-02 16:55:20*****UNSAT****
  
 1.IDENTIFY THE REVISIONS/CHANGES TO SHEETS FA-03 &
 FA-04 AS SHOWN ON SHEET FA-00, FA-01, AND FA-02. PLEASE
 BE ADVISED THAT IF THERE ARE NO REVISIONS/CHANGES TO
 THESE SHEETS (FA-03 & FA-04), SUBMITTING OF THE
 UNAFFECTED SHEETS WILL NOT BE REQUIRED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 12:42 Rev Time 0.00
Received By mwennerg Date 2008-05-09 Time 12:42 Sent To  
Notes
2008-05-09 12:44:40NEW SHEETS FA0.1, FA2.1, FA5.1, FA5.2, FS0.1 AND FS2.1
 WITH NO CHANGES OR REVISIONS DOCUMENTED SINCE LAST
 REVIEW STAMPED, SIGNED AND DATED. SHEET 2.7.4 STAMPED
 WITH REVISION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-03-12 Cont ID  
Sent By mawillia Date 2008-03-12 Time 12:05 Rev Time 0.00
Received By mawillia Date 2008-03-12 Time 11:25 Sent To B
Notes
2008-03-12 11:57:15*****APPROVED*****
  
  
 PLAN SHEETS A-2.7.3 THRU A-2.7.7, E2.1, FA0.1, FA2.1,
 FA5.1, FA5.2, FS0.1, AND FS2.1 WERE STAMPED, INTIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-13 Cont ID  
Sent By mwennerg Date 2008-02-13 Time 10:41 Rev Time 0.00
Received By mwennerg Date 2008-02-13 Time 10:41 Sent To  
Notes
2008-02-13 10:43:16IT APPEARS THAT COMMENTS HAVE BEEN ADDRESSED AND PLANS
 ARE CODE COMPLIANT. PLANS WILL BE STAMPED WHEN RETURNED
 WITH CORRECTIONS FOR OTHER REVIEW COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By mwennerg Date 2008-01-02 Time 15:31 Rev Time 0.00
Received By mwennerg Date 2008-01-02 Time 15:31 Sent To  
Notes
2008-01-02 15:45:59***DENIED***
  
 1) IT WOULD APPEAR THAT THE 7TH LEVEL IS CONSIDERED
 SUITE 800. PLEASE VERIFY AND ADD APPROPRIATE SUITE
 NUMBERS IN ALL SUBMITTED SHEET TITLE BLOCKS.
  
 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) PLEASE ADVISE MINIMUM INTERIOR FINISH CLASSIFICATION
 FOR WALLS AND CEILING IN TERMS OF CLASS A,B OR C.
  
 4) PLEASE INDICATE RATING OF FIRE DOORS IN TERMS OF
 MINUTES.
  
 5) NEW DUCT SMOKE DETECTOR INSTALLATIONS WHEN ACTIVATED
 SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS. FA0.1 NOTE 17
  
 6) AS ALREADY STATED ON PLANS, SEPARATE SHOP DRAWINGS
 AND PERMITS REQUIRED PRIOR TO FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 09:18 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 09:18 Sent To E
Notes
2008-09-22 09:18:37TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:41 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:41 Sent To E
Notes
2008-06-17 16:42:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 15:05 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 15:05 Sent To FIRE
Notes
2008-06-05 15:06:19TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 11:55 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 11:55 Sent To FIRE
Notes
2008-05-19 11:56:05TO "MWENNERGREN" DESK/REV--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 14:51 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 14:51 Sent To  
Notes
2008-05-12 14:55:02TO "COMM" BD#33--EXPEDITED---

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:40 Sent To M
Notes
2008-05-08 16:40:21TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 14:41 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 14:41 Sent To  
Notes
2008-05-07 12:17:455/7/08--PER CONTRACTOR VISIT TODAY AND CONVERSATION
 WITH RON AND LUIS, REVISION#2 ON "COMM" BD#35, WAS
 COMBINED WITH REVISION#1 ON "COMM" BD#34.IT'S NOW 1
 REVISION ON "COMM" BD#34.35 HAS BEEN ERASED.
2008-04-30 14:50:06TO "COMM" BD#35(REV#2)**PRIVATE PROVIDER**

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 14:27 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 14:27 Sent To  
Notes
2008-04-30 14:30:26TO "COMM" BD#34(REV#1)***PRIVATE PROVIDER***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 11:43 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 11:40 Sent To  
Notes
2008-02-29 11:44:32TO "COMM" BD#2/--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 09:21 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 09:21 Sent To  
Notes
2008-02-07 09:34:07TO "COMM" BD#40--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-08 Cont ID  
Sent By rbrown Date 2008-01-05 Time 20:17 Rev Time 0.00
Received By rbrown Date 2007-12-26 Time 16:05 Sent To  
Notes
2007-12-26 16:06:04TO COMM BOARD # 45

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-12 Time 16:04 Rev Time 0.00
Received By rregueir Date 2008-05-12 Time 16:04 Sent To  
Notes
2008-05-12 15:59:13ENTERED IN ERROR

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-12 Time 11:54 Rev Time 0.00
Received By rregueir Date 2008-05-12 Time 11:38 Sent To PC
Notes
2008-05-12 11:39:508X11 SHEET REVISING PG M2.1 NOT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-12 Time 11:35 Rev Time 0.00
Received By rregueir Date 2008-05-12 Time 09:44 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-10 Cont ID  
Sent By rregueir Date 2008-03-10 Time 17:38 Rev Time 0.00
Received By rregueir Date 2008-03-10 Time 17:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-02-29 Cont ID  
Sent By rregueir Date 2008-02-14 Time 13:25 Rev Time 0.00
Received By rregueir Date 2008-02-14 Time 11:19 Sent To  
Notes
2008-02-14 13:20:14PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, MECHANICAL PLAN REVIEW STOP WILL
 REMAIN IN "FAILED" STATUS PENDING RECEIPT OF THE OWNER
 AFFIDAVIT REGARDING THE USE OF PRIVATE PROVIDERS AND
 THE LETTER OF UNDERSTANDING WHICH HAS TWICE BEEN
 REQUESTED BUT HAS YET TO BE PROVIDED. SEE OTHER
 DISCIPLINES PLAN REVIEW COMMENTS FOR ADDITIONAL
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-05 Cont ID  
Sent By rregueir Date 2008-01-05 Time 13:54 Rev Time 0.00
Received By rregueir Date 2008-01-04 Time 15:05 Sent To PC
Notes
2008-01-05 13:54:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M2.1 AND P2.1 SHOW NEW CONDENSER WATER AND
 CONDENSATE LINES PENETRATING FIRE RESISTANCE RATED WALL
 ASSEMBLIES. THESE PENETRATIONS ARE REQUIRED TO BE
 PROTECTED BY A THROUGH-PENETRATION FIRESTOP SYSTEM IN
 ACCORDANCE WITH FBC 712.3.1.2. THE ONLY
 THROUGH-PENETRATION FIRESTOP SYSTEM SHOWN ON PLANS WAS
 FOUND ON PG FS0.1 AND THIS SYSTEM IS NOT APPLICABLE
 BECAUSE IT IS ONLY FOR STEEL PIPE OR EMT PENETRATING
 CONCRETE WALLS AND FLOORS. CONDENSATE IS TO BE TYPE L
 COPPER AS STATED IN MECHANICAL NOTE #17. CONDENSER
 WATER MAY BE TYPE L COPPER AS STATED IN MECHANICAL NOTE
 #27. PROVIDE DETAIL FOR A THROUGH-PENETRATION FIRESTOP
 SYSTEM TO BE USED TO PROTECT THESE
 THROUGH-PENETRATIONS, ENSURING THE SYSTEM IS
 APPROPRIATE FOR THE TYPE OF MATERIAL PENETRATING THE
 WALLS AS WELL AS THE TYPE OF WALL ASSEMBLY BEING
 PENETRATED.
  
 2. PG M2.1: A COMBINATION FIRE/SMOKE DAMPER IS SHOWN IN
 THE 34X12 SUPPLY DUCT PENETRATING THE TENANT SEPARATION
 WALL (AT APPROXIMATELY COLUMN LINE K.1). THERE ARE ALSO
 6 OTHER R/A FIRE/SMOKE DAMPERS SHOWN IN THE TENANT
 SEPARATION WALLS. NONE OF THESE ARE PART OF THE
 CONTROLS OR SEQUENCE OF OPERATIONS FOR THE BASE
 BUILDING SMOKE CONTROL SYSTEM. THEY ARE ALSO NOT SHOWN
 AS PART OF THE FIRE ALARM PLANS (SEE FA0.1 THROUGH
 FA5.1). BY WHAT MEANS ARE THESE DAMPERS TO BE ACTUATED?
 SHOW THE SMOKE DAMPER ACTUATION METHOD TO BE IN
 COMPLIANCE WITH FBC, M 607.3.2.1.
 NOTE: THESE DAMPERS ARE NOT LOCATED IN A SHAFT, RATED
 CORRIDOR OR A SMOKE BARRIER.
  
 3. PG A-7.7.3: EXTERIOR WALLS ABOVE CEILING WHICH ARE
 EXPOSED TO THE RETURN AIR PLENUM SHALL BE LINED WITH AN
 AIR BARRIER AND SEALED IN ACCORDANCE WITH FMC, M 603.9
 AND SHALL BE INSULATED IN ACCORDANCE WITH TABLE
 13-410.1.ABC.2.2 OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING. SEE FBC, M 603.8. EXTERIOR WALLS
 EXPOSED TO THE PLENUM SHALL BE INSULATED TO A MINIMUM
 OF R-8, RATHER THAN THE R-4.2 AS SHOWN ON DETAILS 1 AND
 2 OF THIS PAGE.
  
 4. AS THIS IS AN UNFINISHED SHELL BUILDING, THESE PLANS
 ARE TO BE REVIEWED AND SIGNED BY THE BASE BUILDING
 DESIGNER OF RECORD FOR CONFORMANCE WITH THE BASE
 BUILDING DESIGN. THE MECHANICAL PLANS HAVE BEEN
 INITIALED BY "TWJ" RATHER THAN DANIEL A. CAMPIA. PLEASE
 CORRECT AND RESUBMIT. ALSO, PLEASE SEE PLUMBING
 COMMENTS REGARDING THE REQUIRED LETTER OF UNDERSTANDING
 TO BE SIGNED BY THE BASE BUILDING CONTRACTOR, BASE
 BUILDING DEVELOPER AND THE TENANT CONTRACTOR TO BE
 SUBMITTED WITH PERMIT APPLICATION.
 NOTE: THESE REQUIREMENTS ARE BASED ON A POLICY
 ESTABLISHED BY THE BUILDING OFFICIAL FOR THE PURPOSE OF
 CREATING A SYSTEM BY WHICH TENANT IMPROVEMENT PERMITS
 MAY BE ISSUED PRIOR TO COMPLETION OF THE SHELL/BASE
 BUILDING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status N Date 2008-05-19 Cont ID  
Sent By kstevens Date 2008-05-10 Time 06:47 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 06:47 Sent To  
Notes
2008-05-10 06:49:20DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT P2.1 NOT APPROVED AS THERE ARE NO CHANGES
 INDICATED ON SHEET SUBMITTED. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-10 Cont ID  
Sent By kstevens Date 2008-05-10 Time 06:47 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 06:47 Sent To  
Notes
2008-05-10 06:47:49REVISION OK--SHT P.01

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-04 Cont ID  
Sent By kstevens Date 2008-03-04 Time 09:55 Rev Time 0.00
Received By kstevens Date 2008-03-04 Time 09:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-08 Cont ID  
Sent By kstevens Date 2008-02-08 Time 18:08 Rev Time 0.00
Received By kstevens Date 2008-02-08 Time 18:08 Sent To  
Notes
2008-02-08 18:25:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-3.7.1 THE PANTRY AND BREAKROOM SINKS SHALL BE
 ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24
 WITH ALL SUBSECTIONS. NO CLEAR FLOOR SPACE SHOWN ON THE
 FLOOR PLAN.
 ****RESPONSE NOTED, BUT NO CLEAR FLOOR SPACE IS SHOWN
 FOR THE PANTRY SINK ON THE FLOOR PLAN.
  
 2. SHTS A3.7.2 DETAIL 7 AND A-6.7.1 DETAIL 8. CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE OF THE
 BREAK ROOM SINK, (AS WELL AS THE PANTRY SINK). SECTION
 11-4.24.5. PLEASE SHOW CLEAR FLOOR SPACE WITHOUT
 DOORS.
 ****RESPONSE NOTED, BUT THE DOORS ARE STILL SHOWN ON
 THE PANTRY ELEVATION. (SEE DETAIL 8 SHEET A-3.7.3).
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SINCE THE BUILDING HAS NOT BEEN COMPLETED, AND HAS
 NOT BEEN ISSUED A CERTIFICATE OF OCCUPATION, AS A
 CONDITION OF PERMIT, THE CONSTRUCTION SERVICES
 DEPTARMENT IS REQUIRING A LETTER OF UNDERSTANDING
 BETWEEN THE BASE BUILDING CONTRACTOR, THE TENANT
 CONTRACTOR, AND THE BASE BUILDING DEVELOPER. THE LETTER
 SHALL STATE THAT PARTIES SHALL TAKE RESPONSIBILITY FOR
 THEIR WORK AND ACKNOWLEDGE THAT THE WORK OF ONE
 CONTRACTOR HAS THE POTENTIAL TO IMPACT THE OTHER'S
 ABILITY TO OBTAIN FINAL INSPECTIONS. CODE DEFICIENCIES
 WILL NOT BE OVERLOOKED REGARDLESS OF WHO IS RESPONSIBLE
 FOR THE RELATED WORK. THE LETTER SHALL BE SIGNED BY
 EACH CONTRACTOR AND THE DEVELOPER.
 ****RESPONSE NOTED, BUT THE LETTER HAS NOT BEEN
 SUBMITTED.
  
 *********NEW COMMENT**********
  
 1B. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION
 TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE
 MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN
 OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE,
 SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY
 WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT
 THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT,
 INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF
 FLORIDA STATUTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By kstevens Date 2007-12-28 Time 08:57 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 08:57 Sent To  
Notes
2007-12-28 09:06:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3.7.1 THE PANTRY AND BREAKROOM SINKS SHALL BE
 ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24
 WITH ALL SUBSECTIONS. NO CLEAR FLOOR SPACE SHOWN ON THE
 FLOOR PLAN.
  
 2. SHTS A3.7.2 DETAIL 7 AND A-6.7.1 DETAIL 8. CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE OF THE
 BREAK ROOM SINK, (AS WELL AS THE PANTRY SINK). SECTION
 11-4.24.5. PLEASE SHOW CLEAR FLOOR SPACE WITHOUT
 DOORS.
  
 3. SUBMIT A DETAIL FOR THE PANTRY SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
  
 4. SHT P0.1 SANITARY ISOMETRIC SHOWS THE SANITARY
 CONNECTING TO THE VENT STACK. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5. SHT P0.1 SHOWS A GARBAGE DISPOSAL. THIS IS NOT SHOWN
 ON SHT A-6.7.1 DETAIL 8. PLEASE CORRELATE. SECTION
 106.1.1. THE GARBAGE DISPOSAL SHALL BE ADA APPROVED.
 PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE GARBAGE
 DISPOSAL.
  
 6. SHT P0.1 WATER ISOMETRIC. WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE ICE MAKERS. SECTION 604.9.
  
 7. SINCE THE BUILDING HAS NOT BEEN COMPLETED, AND HAS
 NOT BEEN ISSUED A CERTIFICATE OF OCCUPATION, AS A
 CONDITION OF PERMIT, THE CONSTRUCTION SERVICES
 DEPTARMENT IS REQUIRING A LETTER OF UNDERSTANDING
 BETWEEN THE BASE BUILDING CONTRACTOR, THE TENANT
 CONTRACTOR, AND THE BASE BUILDING DEVELOPER. THE LETTER
 SHALL STATE THAT PARTIES SHALL TAKE RESPONSIBILITY FOR
 THEIR WORK AND ACKNOWLEDGE THAT THE WORK OF ONE
 CONTRACTOR HAS THE POTENTIAL TO IMPACT THE OTHER'S
 ABILITY TO OBTAIN FINAL INSPECTIONS. CODE DEFICIENCIES
 WILL NOT BE OVERLOOKED REGARDLESS OF WHO IS RESPONSIBLE
 FOR THE RELATED WORK. THE LETTER SHALL BE SIGNED BY
 EACH CONTRACTOR AND THE DEVELOPER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-27 Cont ID  
Sent By eschneid Date 2007-12-27 Time 09:54 Rev Time 0.00
Received By eschneid Date 2007-12-27 Time 09:54 Sent To  
Notes
2007-12-27 09:54:447TH FLOOR BUILD-OUT.NO REVIEW REQ.