Plan Review Details - Permit 07120567
Plan Review Stops For Permit 07120567
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-11 Cont ID  
Sent By mjacobs Date 2008-02-11 Time 13:24 Rev Time 0.00
Received By mjacobs Date 2008-02-11 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-11 Cont ID  
Sent By mjacobs Date 2008-01-11 Time 14:43 Rev Time 0.00
Received By mjacobs Date 2008-01-11 Time 12:45 Sent To  
Notes
2008-01-11 14:42:59 
 BUILDING PLAN REVIEW
 PERMIT: 07120567
 ADD: 1400 CENTRE PARK BLVD
 CONT: REGENCY COMMUNICATION INC.
 TEL: (865)300-3003
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL. THIS INFORMATION SHALL BE CLEARLY
 INDICATED ON THE PLANS. PLEASE INDICATE THE EXPOSURE
 CATEGORY #3 ABOVE.
  
 4)ALL PLANS, SPECIFICATIONS, REPORTS, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY A DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD, SHALL CONTAIN THE
 DATE, SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS
 AND LICENSE NUMBER ON EACH SHEET. SHEET T1 IS MISSING
 THE DATE SEAL AND SIGNATURE OF THE ENGINEER. THE SEAL
 OF P.E MARTIN H. SAHN IS NOT LEGIBLE ON THE SHEETS.
 F.A.C 61G15-23.002
  
 5)5)THE ADDRESS ON THE PLAN FOR MACTEC ENGINEERING
 AND CONSULTING, INC. NEEDS TO CORRESPOND WITH THE DBPR
 WEBSITE. SEE INFORMATION SHEET ATTACH.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:18 Sent To  
Notes
2008-02-11 08:19:10ELECTRICAL OK, STAMPED ELECTRICAL SHEETS.
 VALUE SEEMS OK, BASED ON MOST OF THE ITEMS ON PLANS
 ALREADY EXISTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 12:00 Sent To  
Notes
2007-12-23 12:00:34** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE SHEET T-I IN BOTH SETS ARE NOT
 SIGNED, DATED AND SEALED AS REQUIRED PER FS 481.221,
 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE THE RISER MENTIONS PANEL EXISTS AND
 12 CIRCUITS AND THE PANEL SCHEDULE PROVIDED IS 16
 CIRCUITS. IS THIS THE SAME PANEL?
 PLEASE COORDINATE.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE THERE ARE TWO PROJECTS SUBMITTED BY
 THE SAME CONTRACTOR FOR SOME OF THE SAME SCOPE OF WORK
 HOWEVER THE ACTUAL WORK INVOLVED IN MORE ON ONE PROJECT
 INCLUDING LARGER EQUIPMENT. HOW IS IT THAT THE VALUE
 FOR THE SCOPE OF WORK AND EQUIPMENT IS BEING SHOWN THE
 SAME ON BOTH PROJECTS?
 PLEASE SEE FBC 108.3 AS VALUE SHALL INCLUDE ALL LABOR,
 MATERIALS, EQUIPMENT, AND DESIGN COST ETC EVEN IF ANY
 IS OWNER SUPPLIED.
 PLEASE SUBMIT SIGNED CONTRACT SHOWING AND INCLUDING
 ALL.
 THIS NOTE WILL ALSO BE PLACED ON OTHER APPLIED PERMIT
 SCOPE #07120563
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-14 Cont ID  
Sent By mawillia Date 2008-02-14 Time 11:50 Rev Time 0.00
Received By mawillia Date 2008-02-14 Time 10:24 Sent To  
Notes
2008-02-14 11:36:31*****PROVISO*****
  
 PLAN SHEET E3 STAMPED, INITIALED, AND DATED WITH THE
 FOLLOWING PROVISO:
  
 1.NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE
 REQUIRED EXIT STAIRTOWERS.
  
 2.ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR
 DEVICES.
  
 3.ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT
 INTERFERE ANY STANDPIPE ROOF MANIFOLDS.
  
 4.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK
 TO COMPLY WITH NFPA 241.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-25 Cont ID  
Sent By mawillia Date 2008-01-25 Time 10:47 Rev Time 0.00
Received By mawillia Date 2008-01-25 Time 10:28 Sent To  
Notes
2008-01-25 10:40:55*****DENIED*****
  
  
 1.NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE
 REQUIRED EXIT STAIRTOWERS.PLEASE PROVIDE A NOTE ON
 THE PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY
 EXIT STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY.
  
 2.ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR
 DEVICES.
  
 3.ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT
 INTERFERE ANY STANDPIPE ROOF MANIFOLDS.
  
 4.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK
 TO COMPLY WITH NFPA 241.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 10:25 Sent To  
Notes
2008-02-07 10:25:31TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-25 Cont ID  
Sent By mawillia Date 2008-01-25 Time 10:28 Rev Time 0.00
Received By mawillia Date 2007-12-21 Time 16:48 Sent To  
Notes
2007-12-21 16:48:53SENT TO COMMERCIAL BOARD # 58 MMILLER

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-28 Cont ID  
Sent By jroach Date 2008-03-28 Time 15:42 Rev Time 0.00
Received By jroach Date 2008-03-28 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-18 Cont ID  
Sent By jroach Date 2008-02-18 Time 17:12 Rev Time 0.00
Received By jroach Date 2008-02-18 Time 17:12 Sent To  
Notes
2008-02-18 17:12:29***FAILED***
  
 THE FOLLOWING ARE REPEAT COMMENTS...
  
 1) MINOR AMENDMENT TO THE CENTREPARK COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-07 Cont ID  
Sent By jroach Date 2008-01-07 Time 16:42 Rev Time 0.00
Received By jroach Date 2008-01-07 Time 16:42 Sent To  
Notes
2008-01-07 16:43:06***FAILED***
  
 1) MINOR AMENDMENT TO THE CENTREPARK COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.