Plan Review Stops For Permit 07120532 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-02-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-02-19 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-02-19 |
Time |
16:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-02-06 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-02-06 |
Time |
07:02 |
Sent To |
|
|
Notes |
2008-02-06 07:36:28 | 2004 FBC W/2007 REVISIONS | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) THE DESIGN PRESSURES FOR THE CASEMENT WINDOWS | | (CIRCLED ON PAGE 4 OF NOA 05-1129.09 ARE FOR 3/16" | | ANNEALED GLASS) ARE + & - 40 PSF. THE PLANS SUBMITTED | | SPECIFY + 35 & - 47.2AS THE REQUIRED DESIGN PRESSURES | | FOR THESE WINDOWS. THE NEGATIVE PRESSURE OF THE | | SPECIFIED PRODUCT IS NOT ADEQUATE. PLEASE CORRECT. SEE | | FBC R301.2.1. | | | | 2) SUBMIT 2 COPIES OF THE SCOPE OF WORK DOCUMENT OR | | LIST THE SCOPE OF WORK ON THE DRAWINGS. | | | | 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDING SECTION | | 604.4.3 FOR SMOKE ALARMS. | | | | 4) THE DRAWINGS SPECIFY THE 2004 FBC WITH 2006 | | REVISIONS. THE CORRECT CODE FOR THIS PROJECT IS THE | | 2004 FBC WITH 2007 REVISIONS. PLEASE CORRECT. | | | | 5) ADDRESS COMMENTS OF OTHER TRADES. | | | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-01-08 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-01-08 |
Time |
07:13 |
Sent To |
|
|
Notes |
2008-01-08 10:28:59 | 2004 FBC W/2007 REVISIONS | | | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) THE DESIGN PRESSURES FOR THE CASEMENT WINDOWS | | (CIRCLED ON PAGE 4 OF NOA 05-1129.09 ARE FOR 3/16" | | ANNEALED GLASS) ARE + & - 40 PSF. THE PLANS SUBMITTED | | SPECIFY + 35 & - 47.2AS THE REQUIRED DESIGN PRESSURES | | FOR THESE WINDOWS. THE NEGATIVE PRESSURE OF THE | | SPECIFIED PRODUCT IS NOT ADEQUATE. PLEASE CORRECT. SEE | | FBC R301.2.1. | | | | 2) THE STORM PANEL INSTALLATION SCHEDULE IS INCORRECT. | | PLEASE CLARIFY THE ANCHOR TYPE. WILL TAPCONS BE USED OR | | ELCO PANELMATES. IF TAPCONS ARE USED AND THE EDGE | | DISTANCE IS LESS THAN 3-1/2" THE ANCHOR SPACING IN THE | | TABLES ARE REQUIRED TO BE REDUCED BY THE FACTORS IN THE | | TABLE AT THE BOTTOM OF SHEET 7 OF DRAWING # 05-270. THE | | SPANS ARE INCORRECT. IF THE PANELS ARE INSTALLED | | VERTICALLY THE SPAN IS THE OPENING HEIGHT PLUS THE EDGE | | DISTANCE. ON SHEET 3 OF DRAWING # 05-270 SECTIONS 2 AND | | 2A ARE CIRCLED. USE THESE TO DETERMINE THE ANCHOR | | SPACING IN THE TABLE ON SHEET 7. | | | | 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDING SECTION | | 604.4.3 FOR SMOKE ALARMS. | | | | 4) ADDRESS COMMENTS OF OTHER TRADES. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2008-01-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-30 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2008-02-06 09:48:34 | | | FEES FOR SEPARATE ELECTRICAL PERMIT SHALL BE BASED ON | | THE VALUE OF THE ELECTRICAL WORK.RB | 2008-01-30 16:45:16 | PLANS REQUIRED FORALL ELECTRICAL INCLUDING SMOKE | | ALARMS . | | | | SCOPE OF WORK AS LISTED ON SUBMITTED SHEETS WILL DELETE | | ELECTRICAL PER ROBERT BROWN. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-28 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-28 |
Time |
11:34 |
Sent To |
M |
|
Notes |
2008-01-28 11:36:55 | ** DENIED 2ND REVIEW ** | | | | 1) NOTE: PLEASE SEE THE REVIEW COMMENTS FROM PREVIOUS | | REVIEW. | | PLEASE KNOW AS NO PLANS WERE SUBMITTED ONCE AGAIN FOR | | SCOPE OF WORK, THERE MAY VERY WELL BE NEW COMMENTS ON | | THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME. | | PLEASE SEE PREVIOUS REVIEW NOTES ATTACHED. | | | | PLEASE SUBMIT THE INFORMATION FOR REVIEW. IF THERE ARE | | ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-12-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-23 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-23 |
Time |
14:57 |
Sent To |
M |
|
Notes |
2007-12-23 14:57:21 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE | | STATED ON PLANS FOR MINIMUM DESIGN. | | 2005 NFPA-70 | | 2002 NFPA-72 | | ** FBC 2004 W/2007 REVISIONS (NOTED BY OTHER TRADES) | | | | 2) NOTE: PLEASE SUBMIT A COMPLETE PLAN INCLUDING PANEL | | SCHEDULE, RISER, LOAD CALCULATIONS ETC FOR NEW SCOPE OF | | WORK. | | PLEASE INDICATE THE NEW DEDICATED CIRCUITS WHICH ARE | | REQUIRED PER 210.52, 210.11, 220. | | AS SCOPE OF WORK IS NOT SHOWN DETERMINATION OF MINIMUM | | ELECTRICAL CODE COMPLIANCE CAN BE DONE AT THIS TIME. | | 2005 NEC. | | PLEASE SEE 210.70, LS 101 7.8 FOR CONTROLS OF NEW | | LIGHTING WHICH IS STATED ON SCOPE. | | PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS. | | PLEASE B SURE TO LIST ALL OVER CURRENT PROTECTION | | DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC | | 408.4, 240.4, 310.16 ETC | | FBC 106.3.5.4 | | | | 3) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED | | DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12 | | AWG. | | | | 4) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING | | DWELLING SLEEPING ROOMS PER FBC R313 AND NFPA-72 | | 11.5.1.1.1, 11.8.3 | | PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING | | DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE | | CURRENT VERSION OF NFPA-72 11.5.1.1.1 AND 11.8.3 OR NEW | | TO BE INSTALLED. | | | | 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C | | CONDENSING UNIT AND AH UNITPER 440.11. | | PLEASE ALSO SEE THE MISSING GFI PER 210.8, 210.63. | | | | 7) NOTE: PLEASE SHOW LAYOUT OF NEW PROPOSED KITCHEN | | CABINETS SHOWING KITCHEN COUNTER SPACE GFI RECEPTACLES | | NEW MEETING CODE OR EXISTING MEETING MINIMUM CODE PER | | 210.52B1, 210.52C1-5, 210.8A6. | | | | 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED | | LIGHTING PER FBC 13-606.ABC.1.2.4 | | | | 9) NOTE: PLAN TITLE BLOCKS MENTIONS DESIGNER FOR | | RESIDENTIAL AND COMMERCIAL WORK. PLEASE SEE FLORIDA | | STATUTES 481.229 AS SCOPE OF WORK ON COMMERCIAL | | PROJECTS REQUIRE LICENSE UNDER ARCHITECTURAL | | REGULATIONS. PLEASE COMPLETE TITLE BLOCKS WITH REQUIRED | | LICENSING PER FAC 61G1-16.004, FS 481.219. | | PLANS WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED | | BY ANY LICENSED DESIGNER OF RECORD. FS 481.221. | | | | | | *** IMPORTANT** | | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, | | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH | | CAN NOT BE MADE AT THIS TIME. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-02 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-02 |
Time |
11:52 |
Sent To |
M |
|
Notes |
2008-05-02 11:52:51 | TO "TGORDON" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-04-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-30 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-30 |
Time |
12:10 |
Sent To |
M |
|
Notes |
2008-04-30 12:10:46 | TO "M" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-21 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-21 |
Time |
08:55 |
Sent To |
M |
|
Notes |
2008-03-21 08:55:54 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-02-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-13 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-13 |
Time |
15:37 |
Sent To |
Z |
|
Notes |
2008-02-13 15:42:52 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-01-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-23 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-23 |
Time |
11:11 |
Sent To |
Z |
|
Notes |
2008-01-23 11:11:17 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-01-08 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-12-20 |
Time |
17:15 |
Sent To |
|
|
Notes |
2007-12-20 17:15:46 | SENT TO SINGLE FAMILY RACK MMILLER |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-02 |
Time |
16:14 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-05-02 |
Time |
16:14 |
Sent To |
|
|
Notes |
2008-05-02 16:14:49 | REVISION TO MECH. PLAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-01 |
Time |
09:23 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-05-01 |
Time |
09:23 |
Sent To |
|
|
Notes |
2008-05-01 09:25:12 | REVISED PLANS CAN NOT BE REVIEWED UNTIL PROPER FORM IS | | SUBMITTED AND FEES ARE PAID. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-03-21 |
Time |
13:50 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-03-21 |
Time |
13:50 |
Sent To |
|
|
Notes |
2008-03-21 13:51:14 | REVISION TO MECHANICAL PLAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-02-15 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-02-15 |
Time |
13:42 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2008-02-15 |
Time |
13:42 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-28 |
Time |
11:52 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2008-01-28 |
Time |
11:52 |
Sent To |
P |
|
Notes |
2008-01-28 11:59:04 | *** PROVISO *** | | 1) IF A/C CONDENSER UNIT IS TO BE INSTALLED IN A | | DIFFERENT LOCATION AS SHOWN ON PLAN A-1.1, THEN PLEASE | | REVISE THE MECHANICAL PLAN. | | | | 2) PROVIDE FOR RETURN AIR TO BEDROOMS, PER 2004 FBC/R | | M1602.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-12-24 |
Time |
09:38 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-12-24 |
Time |
09:38 |
Sent To |
P |
|
Notes |
2007-12-24 09:40:11 | *** PROVISO *** | | 1) PROVIDE FOR RETURN AIR TO BEDROOMS, PER 2004 FBC/R | | M1602.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2008-02-06 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-02-06 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-02-06 |
Time |
10:30 |
Sent To |
B |
|
Notes |
2008-02-06 10:51:47 | PLANS REQUIRED FOR ALL PLUMBING AND GAS. | | | | SCOPE OF WORK AS LISTED ON SUBMITTED SHEETS WILL DELETE | | PLUMBING AND GAS PER ROBERT BROWN. | | | | FEES FOR SEPERATE PLUMBING AND GAS PERMITS SHALL BE | | BASED ON THE VALUE OF THE PLUMBING AND GAS WORK. RB |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-02-01 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-02-01 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-02-01 |
Time |
08:09 |
Sent To |
B |
|
Notes |
2008-02-01 08:19:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | PLUMBING PLAN REVIEW: | | DENIED 2ND TIME: | | | | NOTE: THE PREVIOUS PLAN REVIEW COMMENTS WERE NOT | | ADDRESSED ON THE RESUBMITTAL. AT A MINIMUM PLANS SHALL | | REFLECT THE SCOPE OF WORK INDICATED ON THE CASE#: | | 06/0/-033. | | | | 1. MORE INFORMATION IS REQUIRED, PLEASE PROVIDE THE | | FOLLOWING INFORMATION IF IT PERTAINS TO YOUR JOB ON TWO | | COMPLETE SETS OF PLANS. PER *106.1 SUBMITTAL DOCUMENTS. | | PLEASE CLEARLY INDICATE THE SCOPE OF WORK ON THE | | RESUBMITTED PLANS. PER *106.1.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | A} IF PLUMBING LAYOUT IS THE SAME WITH NO CHANGES, | | PLEASE INDICATE THIS ON THE RESUBMITTED DRAWINGS. | | | | B} IF PLUMBING LAYOUT IS THE SAME AND THE PLUMBING | | FIXTURES ARE TO BE CHANGED, PLEASE INDICATE ON THE | | RESUBMITTED DRAWINGS. "EXACT FIXTURE CHANGEOUT ONLY" | | AND CLEARLY INDICATE WHAT FIXTURES ARE GOING TO BE | | CHANGED. | | | | C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT | | FROM THE EXISTING PLEASE SUBMIT THE FOLLOWING ON | | SEPERATE DRAWINGS. | | A) EXISTING FLOOR PLAN LAYOUT. | | B) NEW PROPOSED FLOOR PLAN LAYOUT AND PLEASE FOLLOW | | WHAT IS REQUIRED IN COMMENT #2. | | | | 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 | | RESIDENTIAL (ONE AND TWO-FAMILY)(9) PLUMBING: PLEASE | | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM | | INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH | | CLEANOUT LOCATIONS. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-28 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-28 |
Time |
14:44 |
Sent To |
B |
|
Notes |
2007-12-28 15:02:31 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | PLUMBING PLAN REVIEW: | | DENIED: | | | | 1. MORE INFORMATION IS REQUIRED, PLEASE PROVIDE THE | | FOLLOWING INFORMATION IF IT PERTAINS TO YOUR JOB ON TWO | | COMPLETE SETS OF PLANS. PER *106.1 SUBMITTAL DOCUMENTS. | | PLEASE CLEARLY INDICATE THE SCOPE OF WORK ON THE | | RESUBMITTED PLANS. PER *106.1.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | A} IF PLUMBING LAYOUT IS THE SAME WITH NO CHANGES, | | PLEASE INDICATE THIS ON THE RESUBMITTED DRAWINGS. | | | | B} IF PLUMBING LAYOUT IS THE SAME AND THE PLUMBING | | FIXTURES ARE TO BE CHANGED, PLEASE INDICATE ON THE | | RESUBMITTED DRAWINGS. "EXACT FIXTURE CHANGEOUT ONLY" | | AND CLEARLY INDICATE WHAT FIXTURES ARE GOING TO BE | | CHANGED. | | | | C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT | | FROM THE EXISTING PLEASE SUBMIT THE FOLLOWING ON | | SEPERATE DRAWINGS. | | A) EXISTING FLOOR PLAN LAYOUT. | | B) NEW PROPOSED FLOOR PLAN LAYOUT AND PLEASE FOLLOW | | WHAT IS REQUIRED IN COMMENT #2. | | | | 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 | | RESIDENTIAL (ONE AND TWO-FAMILY)(9) PLUMBING: PLEASE | | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM | | INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH | | CLEANOUT LOCATIONS. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | EXAMINER FOR REFERENCE FOR THE | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-02-15 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-02-15 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-02-15 |
Time |
13:03 |
Sent To |
M |
|
Notes |
2008-02-15 13:04:06 | ***APPROVED - RESUB #2*** | | | | | | | | | | SENT TO "M" - TG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2008-01-25 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-01-25 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-01-25 |
Time |
11:21 |
Sent To |
E |
|
Notes |
2008-01-25 11:23:23 | ***FAILED - RESUB #1*** | | | | | | REPEAT COMMENTS: | | | | 1)PROVIDE A FLOOR PLAN SHOWING THE PROPOSED LAYOUT | | OF THE STRUCTURE (BATHROOMS, KITCHEN, ETC. SHALL BE | | SHOWN). | | | | 2)PROVIDED LANDSCAPE PLAN INSUFFICIENT.PLAN SHALL | | INCLUDE TYPE AND SIZE OF TREE/SHRUB.MUST MEET MINIMUM | | REQUIREMENTS FOUND IN SECTION 94-442 AND 94-445 OF THE | | ZONING AND LAND DEVELOPMENT REGULATIONS. | | | | NEW COMMENTS: | | | | 1)A/C EQUIPMENT LOCATION IS INCONSISTENT BETWEEN | | PLANS.PLEASE CLARIFY.ALL PLANS SHALL BE | | CONSISTENT. | | | | 2)PLANS SHALL CONTAIN NO WHITE OUT. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | SENT TO "E" - DP |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-12-21 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-12-21 |
Time |
10:21 |
Sent To |
E |
|
Notes |
2007-12-21 10:26:30 | ***FAILED*** | | | | | | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY. | | | | 2)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF | | THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE, | | LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE | | SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION | | 94-442 AND 94-445 OF THE ZLDRS. | | | | 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | PROJECT MORE THAN 4' INTO A REQUIRED SETBACK. | | | | 4)AS NEW GUTTERS ARE BEING INSTALLED, INDICATE | | OVERHANG DIMENSIONS FROM THE WALL TO THE OUTERMOST | | POINT OF THE ROOF.AS PER SECTION 94-305(B)(2) OF THE | | ZLDRS:OVERHANGS/GUTTERS MAY NOT PROJECT MORE THAN 3' | | INTO A REQUIRED SETBACK. | | | | 5)PROVIDE A FLOOR PLAN SHOWING THE PROPOSED LAYOUT | | OF THE STRUCTURE (BATHROOMS, KITCHEN, ETC. SHALL BE | | SHOWN). | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 |
|
|