Plan Review Stops For Permit 07120504 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-12-09 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-12-09 |
Time |
12:09 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-12-09 |
Time |
11:58 |
Sent To |
PC |
|
Notes |
2008-12-09 11:58:38 | SUBMITTAL FOR METAL ROOF (PRODUCT APPROVAL) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2008-12-05 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-12-05 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-12-05 |
Time |
07:33 |
Sent To |
PC |
|
Notes |
2008-12-05 07:33:21 | SUBMITTAL OF PRODUCT APPROVAL FOR METAL ROOFING | | ATTACHMENT ON GAZEBOS. | | | | THE PRODUCT APPROVAL SUBMITTED IS EXPIRED. PLEASE | | SUBMIT AN UPDATED AND APPROVED PRODUCT FOR THE METAL | | ROOF, AND MAKE SURE THE GAUGE OF THE METAL MATCHES THE | | ENGINEER RREPORT. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-06-26 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-06-26 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-06-26 |
Time |
15:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-03-10 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-03-10 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-03-10 |
Time |
08:11 |
Sent To |
|
|
Notes |
2008-03-10 09:56:38 | PROVISOR; | | PRIOR TO FINAL INSPECTION THE PRODUCT APPROVAL FOR THE | | CEDAR SHAKE ROOFING SHALL BE SUBMITTED AND APPROVED BY | | BUILDING DEPT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-01-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-01-07 |
Time |
07:18 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-01-04 |
Time |
16:05 |
Sent To |
|
|
Notes |
2008-01-07 07:18:01 | BUILDING PLAN REVIEW | | PERMIT: 07120504 | | ADD: 2201 45TH STREET | | CONT: LEIGHTON MCGINN CO. | | TEL: (561)863-4455 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | 1-7-08 | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | FBC 1609.1.3 PROVIDE SIGN SEAL AND DATED ENGINEERED | | DRAWINGS SHOWING THE ANCHORAGE AGAINST OVERTURNING, | | UPLIFT AND SLIDING FOR THE GAZEBOS. | | | | 1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND | | LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS | | GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM | | OF THE BUILDING: | | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | (KM/HR). | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | DIRECTION SHALL BE INDICATED. | | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | 5.COMPONENTS AND CLADDING. THE DESIGN WIND | | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE | | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS | | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | PROFESSIONAL.THIS INFORMATION IS REQUIRED FOR THE | | GAZEBOS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-20 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-20 |
Time |
08:39 |
Sent To |
PC |
|
Notes |
2008-03-20 08:39:59 | REC LTR VOIDING ELECTRICAL CONTRACTOR. NO ELECTRICAL IN | | SCOPE ON PLANS, NO PERMIT APPLIED FOR. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
18:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-04 |
Time |
18:11 |
Sent To |
|
|
Notes |
2008-03-04 18:11:58 | ** DENIEDREVIEW ** | | | | 1) NOTE: RE-SUB FORM INDICATES NO ELECTRICAL TO BE DONE | | ETC HOWEVER THE ORIGINAL APPLICATION HAD ELECTRICAL | | CONTRACTOR SIGNED ON. PLEASE KNOW BY PLACING A LINE | | THROUGH ELECTRICAL INFORMATION ON APPLICATION DOES NOT | | VOID APPLIED PERMIT. | | PLEASE SUBMIT AN ORIGINAL LETTER ON LETTER HEAD OF | | CONTRACTOR (GC) RELEASING SCOPE OF WORK DONE AND | | APPLIED FOR BY THE ELECTRICAL CONTRACTOR WHICH WAS | | SIGNED ON ORIGINAL PERMIT APPLICATION. | | PLEASE BE SURE THE LETTER IS NOTARIZED CORRECTLY PER FS | | 117.05 | | THIS LETTER MAY BE BROUGHT IN AT ANYTIME AND REVIEW | | WILL CHANGE TO *N* STATUS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-12-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-22 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-22 |
Time |
14:02 |
Sent To |
|
|
Notes |
2007-12-22 14:03:09 | ** DENIED REVIEW ** | | | | 1) NOTE: PLEASE SEE NO ELECTRICAL PLANS WERE SUBMITTED | | FOR APPLIED SCOPE OF WORK. | | PLEASE SEE NO LIGHTING, CIRCUITS, ETC WERE SHOWN. | | PLEASE SEE 225.31-225.39, 250.32. | | PLEASE PROVIDE LOCATION OF BRANCH CIRCUITS AND WHERE | | THEY ARE FED FROM ETC. | | ** AS NO ELECTRICAL SCOPE IS SHOWN AND AN ELECTRICAL | | PERMIT IS BEING APPLIED FOR PLEASE SUBMIT INFORMATION | | FOR CODE REVIEW. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-03-17 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-17 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-17 |
Time |
10:39 |
Sent To |
|
|
Notes |
2008-03-17 10:45:56 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ACKNOWLEDGED;PLAN SHEET A-2 STAMPED, INITIALED, | | AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-01-08 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-01-08 |
Time |
15:01 |
Sent To |
|
|
Notes |
2008-01-08 15:21:50 | ***DENIED*** | | | | 1) PLEASE PROVIDE MORE INFORMATION REGARDING STRUCTURES | | AND LOCATIONS. | | | | 2) WILL THESE STRUCTURES IMPACT ANY EXISTING BUILDING | | FIRE PROTECTION EQUIPMENT? IE. FIRE HYDRANTS, FDC'S, | | SPRINKLER RISERS ETC. | | | | 3) ARE THERE ANY REQUIRED FIRE LANES IN CLOSE PROXIMITY | | OF PROPOSED STRUCTURES? | | | | 4) FURTHER REVIEW MAY BE REQUIRED DUE TO ELECTRICAL | | PERMIT APPLICATION. | | | | 5) IN ADDITION TO APPLICABLE BUILDING CODES, RAMPS TO | | COMPLY WITH NFPA 101, 2003 SEC. 7.2.5. | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-12-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-09 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-09 |
Time |
09:19 |
Sent To |
B |
|
Notes |
2008-12-09 09:20:02 | TO "MJACOBS" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-12-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-04 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-04 |
Time |
15:33 |
Sent To |
B |
|
Notes |
2008-12-04 15:33:52 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-19 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-19 |
Time |
14:26 |
Sent To |
|
|
Notes |
2008-06-20 16:44:24 | TO "COMM" BD#12 | 2008-06-19 14:26:23 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-02-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-28 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-28 |
Time |
15:16 |
Sent To |
|
|
Notes |
2008-02-28 15:18:34 | TO "COMM" BD#23 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
mmiller |
Date |
2008-01-08 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-12-20 |
Time |
14:02 |
Sent To |
|
|
Notes |
2007-12-20 17:54:10 | SENT TO COM BOARD # 10 MMILLER |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-07-11 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-07-11 |
Time |
14:54 |
Sent To |
|
|
Notes |
2008-07-11 14:55:18 | MATERIAL SUBMITTED, ZONING OK PER ERIC SCHNEIDER |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-07-11 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-07-11 |
Time |
10:34 |
Sent To |
|
|
Notes |
2008-07-11 10:37:06 | TEMPORARY FAIL | | | | WAITING ON TREE ALTERATION PERMIT APPLICATION.SPOKE | | WITH SASHA BUBANJA OF FASTRACK MCI ON 7/2/08. | | | | NO RESUB FEE REQUIRED FOR ZONING TO REVIREW AFTER TREE | | ALTERATION PERMIT SUBMITTAL. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-03-12 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-03-12 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-03-12 |
Time |
10:33 |
Sent To |
|
|
Notes |
2008-03-12 14:35:48 | PASSED W/PROVISO | | | | THE TREE ALTERATION PERMIT SHALL BE APPROVED AND THE | | RELOCATED LANDSCAPE INSTALLED PRIOR TO THE CERTIFICATE | | OF OCCUPANCY. | | | | CONTACT ERIC SCHNEIDER AT (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-12-27 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-12-27 |
Time |
10:24 |
Sent To |
|
|
Notes |
2007-12-27 10:32:12 | FAILED | | | | 1) THE MINOR AMENDMENT LETTER ISSUED ON NOVEMBER 13, | | 2007, REQUIRES THAT THE APPLICANT SUBMIT AND THE | | PLANNING AND ZONING DEPARTMENT APPROVE A TREE | | ALTERATION PERMIT FOR THE TWO (2) RELOCATED TREES.NO | | TREE ALTERATION PERMIT HAS BEEN SUBMITTED OR APPROVED | | AS OF THIS REVIEW. | | | | 2) PLEASE VERIFY WITH THE ENGINEERING SERVICES | | DEPARTMENT WHETHER EROSION CONTROL AND/OR LAND | | STABILIZATION BONDS ARE REQUIRED AS PART OF THE NEW | | CONSTRUCTION. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|