Plan Review Details - Permit 07120445
Plan Review Stops For Permit 07120445
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-12-20 Cont ID  
Sent By mperson Date 2007-12-20 Time 11:20 Rev Time 0.00
Received By mperson Date 2007-12-20 Time 11:20 Sent To PC
Notes
2007-12-20 11:27:13****************PROVISO****************
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,500 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-20 Cont ID  
Sent By mperson Date 2007-12-20 Time 11:27 Rev Time 0.00
Received By mperson Date 2007-12-18 Time 15:27 Sent To  
Notes
2007-12-18 15:27:13TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved