Plan Review Stops For Permit 07120445 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-20 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-20 |
Time |
11:20 |
Sent To |
PC |
|
Notes |
2007-12-20 11:27:13 | ****************PROVISO**************** | | FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF | | GENERATOR PLACEMENT. | | NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET | | CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS | | 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR | | TO FINAL INSPECTION. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 3,500 CUBIC FEET REQUIRED. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-20 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-18 |
Time |
15:27 |
Sent To |
|
|
Notes |
2007-12-18 15:27:13 | TO "G" BOX |
|
|
|