Plan Review Details - Permit 07120426
Plan Review Stops For Permit 07120426
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status N Date 2009-03-17 Cont ID  
Sent By rmcdouga Date 2009-03-17 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2009-03-17 Time 11:35 Sent To  
Notes
2009-03-17 11:36:32NO STRUCTURAL OR ARCHITECTURAL PLANS WERE SUBMITTED.
 REVISIONS ARE FOR ELECTRICAL, PLUMBING AND MECHANICAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-08-25 Cont ID  
Sent By amorse Date 2008-08-25 Time 17:40 Rev Time 0.00
Received By amorse Date 2008-08-25 Time 17:40 Sent To PC
Notes
2008-08-25 17:41:28 
  
 REVISION CHANGE OF PRODUCT APPROVALS FOR CASEMENT
 WINDOWS AND FRENCH DOORS TO IMPACT RATED, SAME
 MANUFACTURER

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-08-12 Cont ID  
Sent By amorse Date 2008-08-12 Time 15:25 Rev Time 0.00
Received By amorse Date 2008-08-12 Time 15:25 Sent To PC
Notes
2008-08-12 15:26:22 
  
 PASSED
  
 1)REVISED SHEETS A-1 A-2 A-5 AND D-1 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-14 Cont ID  
Sent By amorse Date 2008-04-14 Time 17:55 Rev Time 0.00
Received By amorse Date 2008-04-14 Time 17:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-09 Cont ID  
Sent By amorse Date 2008-04-09 Time 17:09 Rev Time 0.00
Received By amorse Date 2008-04-09 Time 17:09 Sent To PC
Notes
2008-04-09 17:22:13 
  
 DENIED
  
 THE FOLLOWING COMMENT IS OUTSTANDING FROM THE 1ST THRU
 4TH REVIEW
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION
  
 **********PLEASE HAVE IMPACT FEE STAMP ON DRAWINGS AND
 PAID FEE RECEIPT INCLUDED WITH PERMIT APPLICATION
 BEFORE PERMIT CAN BE ISSUED, UPON COMPLETION OF THESE
 ITEMS PRESENT PAKAGE TO LUIS MARTINEZ FOR FINAL
 APPROVAL AND PERMIT PRINTING************
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-25 Cont ID  
Sent By amorse Date 2008-03-25 Time 18:37 Rev Time 0.00
Received By amorse Date 2008-03-25 Time 18:37 Sent To PC
Notes
2008-03-25 18:41:17 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST
 AND 2ND REVIEWS, ALL ARCHITECTURAL REVIEW COMMENT HAVE
 BEEN ADDRESSED
  
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)NOTE: FEES ARE DUE IN THE AMOUNT OF $505.97 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
 ******$10.00 WAS ADDED TO FEES FOR HISTORIC
 REVIEW*******
  
 NOTE: ENERGY CALC'S REQUIRE CORRECTIONS, PLEASE SEE
 MECHANICAL REVIEW
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-08 Cont ID  
Sent By amorse Date 2008-03-08 Time 07:47 Rev Time 0.00
Received By amorse Date 2008-03-08 Time 07:47 Sent To PC
Notes
2008-03-08 09:07:35 
  
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST
 REVIEW
  
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)NOTE: FEES ARE DUE IN THE AMOUNT OF $505.97 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
 ******$10.00 WAS ADDED TO FEES FOR HISTORIC
 REVIEW*******
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PLEASE NOTE
 MECHANICAL REVIEWERS COMMENT
  
 NEW COMMENTS
  
 1)PROVIDE THE SYSTEM THAT WILL BE USED FROM THE
 MODIFIED BITUMEN ROOFING PRODUCT APPROVAL
  
 2)HISTORIC APPROVAL STAMP IS REQUIRED ON THE
 DUPLICATE PERMIT APPLICATION FORM
  
 3)SHUTTER OPENING #5 IN THE SHUTTER SCHEDULE SHOULD
 HAVE A DESIGN PRESSURE OF +49/-66 PSF PERTHE
 COMPONENT AND CLADDING SCHEDULE ON SHEET S-4
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-09 Cont ID  
Sent By amorse Date 2008-01-09 Time 18:07 Rev Time 0.00
Received By amorse Date 2008-01-09 Time 18:07 Sent To  
Notes
2008-01-09 18:32:37 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $495.97 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL. *****PROVIDE SEPARATE CALC'S FOR REMODEL
 AND NEW BUILDING ALSO CHECK CEILING AND WALL TYPES AND
 THEIR VALUES*****
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 6)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
 ****NO PRODUCT APPROVALS WERE SUBMITTED FOR IMPACT
 PROTECTION, FIXED WINDOWS (LIVINGROOM AND TRANSOM ABOVE
 FRENCH DOORS), MULLION ABOVE DOOR AND FLAT ROOF
 MEMBRANE ON GUEST HOUSE PORCH****
  
 9)PROVIDE ROOF VENTILATION ON DRAWINGS THAT COMPLIES
 WITH R806.1 & 806.2 FBC RES.
  
 10)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 11)PROVIDESAFETY GLAZING PER R308.4 FBC RES. FOR
 HAZARDOUS LOCATIONS
  
 12)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 13)IF SHUTTERS ARE TO BE USE AS MEANS OF IMPACT
 PROTECTION,INSTALLATIONS REQUIRE A KEY PLAN (WITH
 EGRESS SHOWN), SHUTTER SCHEDULE AND THE PRODUCT
 APPROVALS. APPROVAL DRAWINGS CAN BE MARKED FOR MOUNTING
 METHOD AND CONNECTION TYPE AND THE SCHEDULE FILLED OUT
 WITH ALL PERTINENT INFORMATION SPECIFIC TO THE SITE
 (TYPE OF CONSTRUCTION, MOUNTING CONNECTION METHOD,
 ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR HORIZONTAL),
 ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE.
  
 14)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC *****PLEASE NOTE THAT MEP ENGINEER
 NAME AND LICENSE # ARE NOT INDICATED ON THE TITLE
 BLOCK*****
  
 15)WINDOW UNIT MARK "U" IS NOT ON THE WINDOW
 SCHEDULE
  
 16)CASEMENT WINDOW MARK "E" DOES NOT MEET THE DESIGN
 PRESSURES REQUIRED
  
 17)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 *****PLEASE REMOVE ALL OLD PAGES AND RESUBMIT 2
 COMPLETE SETS OF NEW DRAWINGS WITH REVISIONS AND
 INCLUDE 1 COPY OF THE OLD PAGES ONLY FOR
 REFERENCE.*****
  
 ******ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL, MECHANICAL AND ROOFING******
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 18:52 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 18:52 Sent To PC
Notes
2009-03-24 18:55:22SUCCESSOR ARCHITECT TO PREVIOUS ENGINEER OF RECORD.
  
 REDLINED PLANS TO VIF THE OCP FOR BOTH AHU'S AND AFCI
 PROTECTION PER 210.12 OF THE 2005 NEC

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-03-05 Cont ID  
Sent By dpalmer Date 2009-03-05 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2009-03-05 Time 08:49 Sent To M
Notes
2009-03-05 08:49:46** DENIED REVIEW **
  
 1) NOTE: PLANS ON RECORD ARE UNDER THE DESIGN OF AGILE
 ENGINEERING INC. SIGNED, DATED AND SEALED BY MR. JOHN
 SYLVIA PE. PLEASE SEE FAC 61G15-23, FS 471.025
 PLANS MUST BE REVISED BY THE DESIGNER OF RECORD OR
 PLEASE PROVIDE DOCUMENTATION AS REQUIRED BY THE FLORIDA
 ADMINISTRATIVE CODE FOR TAKING OVER THE RESPONSIBILITY
 OF ANOTHER DESIGN PROFESSIONALS WORK.
 A LETTER FROM THE ORIGINAL ENGINEERING RELEASING
 HIMSELF WOULD ALSO BE AN OPTION.
  
 2) NOTE: THERE ARE SEVERAL ITEMS WHICH WERE ON PREVIOUS
 PLANS WHICH ARE NOW MISSING.
 DISCONNECTS, WATER HEATER, PANELS ETC.
 FOR EXAMPLE: GUEST HOUSE WATER HEATER, GUEST HOUSE
 ELECTRICAL PANEL, MAIN HOUSE DISCONNECT, MISSING
 REQUIRED GFI IN BATH AT GUEST HOUSE ETC.
  
 PLEASE GO THROUGH ORIGINAL PLANS. ITEMS MAY BE DELETED
 WHICH ARE NOT REQUIRED BY NFPA-70 ( NEC) HOWEVER BOTH
 MAIN HOUSE AND GUEST HOUSE MUST SHOW THE MINIMUM
 REQUIRED BY CODE.
 PLEASE SEE
 4220.13,240.24,110.26,215.5,225.31-225.39,210.8A2,
 210.52D ETC
  
 3) NOTE: PLEASE PROVIDE REVISED PANEL SCHEDULE, RISER
 AND LOAD CALCULATIONS. 408.4,215.5,250,220
  
 4) NOTE: KITCHEN IN MAIN HOUSE NOW SHOWS RECEPTACLES
 WHICH WERE NOT ON ORIGINAL PERMITTED PLANS. ALL
 RECEPTACLES SERVICE KITCHEN COUNTER SPACE SHALL BE GFI/
 GFI PROTECTED. 210.8A6
  
 5) NOTE: PLANS MISSING WALL RECEPTACLE REQUIRED PER
 210.52 WHICH WAS ON ORIGINAL PLANS. SEE KITCHEN WALL IN
 GUEST HOUSE.
  
 6) NOTE: PLANS INDICATE A NEW MINI LIFT STATION HOWEVER
 THERE IS NO ELECTRICAL SHOWN ON THE E-SHEETS FOR ANY
 SUCH ITEM. NO ELECTRICAL DETAIL, NO DISCONNECT, NO
 REVISE PANEL, NO INCREASED LOAD.
 NEC 2005 220,215,430,ETC
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
  
 *** THESE ITEMS ABOVE ARE SOME EXAMPLES THAT HAVE
 CHANGED THE PLANS SUBSTANTIALLY WHICH NEED TO SHOW CODE
 COMPLIANCE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 10:38 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 10:38 Sent To M
Notes
2008-03-21 10:39:02ELECTRICAL PLANS STAMPED, SENT ON TO MECH.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-03 Cont ID  
Sent By dpalmer Date 2008-03-03 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2008-03-03 Time 16:01 Sent To B
Notes
2008-03-03 16:02:33** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THAT MANY COMMENTS ARE NEW AS THESE
 THINGS ARE JUST NOW BEING SHOWN.
 PLEASE ALSO SEE THE RISER HAS NOW BEEN COMPLETELY
 REVISED. SOME NEW COMMENTS HAVE NOW BEEN CREATED. MANY
 ITEMS WHICH WERE CODE COMPLIANT ON PREVIOUS REVIEW HAVE
 NOW COMPLETELY CHANGED AND ARE NOW NO LONGER CODE
 COMPLIANT.
  
 1) NOTE: PLEASE SEE THE RISER HAS BEEN REVISED REMOVING
 A MAIN FOR GROUPING OF MAINS AS REQUIRED PER 230.72. ON
 THE PREVIOUS REVIEW A COMMENT WAS MADE THAT A MAIN
 DISCONNECT WAS MISSING AT THE MAIN HOUSE AS REQUIRED
 PER 225.31-225.39. THIS MAIN WHICH WAS ON PREVIOUS
 RISER GROUPED, HAS NOW BEEN MOVED. THE CODE REQUIRES
 MAINS FOR SERVICE TO BE GROUPED PER 230.72 AND A MAIN
 AT THE DETACHED STRUCTURE PER 225.31-225.39. PLEASE
 ADJUST RISER.
  
 2) NOTE: PLEASE ALSO CORRELATE RISER AND PLANS. THE
 RISER SHOWS THE MAIN AT THE HOUSE AS 200AMPS AND THE
 PLANS CLEARLY SHOW A MAIN DISCONNECT RATED AT 125AMPS?
 PLEASE SEE THE PREVIOUS PLANS INDICATE 125AMPS FOR
 PANEL AND MAIN AND THESE NOW INDICATE 200AMP FOR
 BOTH??
 230, 225, 240.4, 310.16 ETC
 FBC 106.1.2 FOR COORDINATION. IT IS UNCLEAR AT THIS
 TIME WHAT MAINS AND PANELS ARE REALLY BEING DESIGNED.
 PLEASE ALSO SEE NEXT COMMENT AS SERVICE SIZE HAS NOW
 BEEN INCREASED.
  
 3) NOTE: PLEASE SEE PREVIOUS PLANS WHICH SHOWED ONE
 125AMP MAIN AND ONE 75AMP MAIN WHICH WAS IN LINE WITH
 THE 200AMP RATED CONDUCTORS AND SERVICE. HOWEVER PLEASE
 NOW SEE AS THE SERVICE NOW SHOWS A NEW 200AMP MAIN AND
 A NEW 100AMP MAIN THE RATING OF THE SERVICE NEEDS TO
 COORDINATE AND BE SIZED FOR THE OVER CURRENT PROTECTION
 AND CONDUCTORS. THIS IS NOW SHOWN AS A 300AMP SERVICE.
 RISER SHOWS 3/0 CONDUCTORS TO THE 100AMP MAIN AND 3/0
 CONDUCTORS TO THE 100AMP SUB PANEL?
 PLEASESEE 240.4, 310.16 ETC
 AS THERE ARE SEVERAL ITEMS WHICH WILL BE ADJUSTED, A
 FULL REVIEW OF ALL ITEMS CAN NOT BE DONE AT THIS TIME.
 FBC 106.3.5.4
 **PLEASE ALSO SEE THE METER WOULD ALSO NOW NEED TO BE
 SHOWN AS 300AMPS.
  
 4) NOTE: PLEASE SEE 240.4, 250.66, 310.15B6 AND 310.16.
 IF THE MINIMUM SERVICE IS NOW GOING TO BE 300AMPS,
 PLEASE ADJUST SERVICE ENTRANCE CONDUCTORS AND THE
 GROUNDING ELECTRODE CONDUCTOR AT THE MAIN SERVICE. IF
 SERVICE IS GOING TO BE 300AMPS, THEN BASED ON MINIMUM
 SERVICE ENTRANCE CONDUCTORS PER 310.15B6 AND THE
 SIZING ON TABLE 250.66 REQUIRES THE GEC AT #2 AWG AT
 MAIN SERVICE LOCATION.
  
 5) NOTE: PREVIOUS REVIEW NOTE REQUESTED TO SHOW THE
 GROUNDING ELECTRODE SYSTEM AT BOTH GUEST HOUSE AND
 DETACHED STRUCTURE (MAIN HOUSE). THE RESPONSE MENTIONS
 THIS IS NOW SHOWN HOWEVER ONLY SHOWS A GROUNDOF SOME
 TYPE. THIS WILL REQUIRE FOOTER STEEL, (METAL) CWP AND
 BONDING OF ANY GAS PIPING PER 250.50, 250.56, 250.52,
 AND 250.104.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 LIGHT FIXTURES OUTSIDE GUEST HOUSE AND MAIN HOUSE WHICH
 DID NOT MEET 680.22B1
 THE PLANS HAVE NOW BEEN REVISED TO SHOW THESE FIXTURES
 AT 12FT AFF YET THIS WOULD PLACE THE FIXTURES ABOVE THE
 ROOF LINE BASED ON THE ELEVATIONS ON THE ARCHITECTURAL
 PLANS.???
 PLEASE SEE THE LOCATIONS OF THE LIGHTING FIXTURES NEED
 TO BE REVISED. PLEASE ALSO SEE THAT BASED ON THE SCALE
 ON PLANS THE GFI RECEPTACLES ON BOTH THE MAIN HOUSE AND
 GUEST ARE SHOWN AT 5FT. THESE MUST BE MORE THAN 5FT
 FROM WATERS EDGE. THESE COULD BE REDLINED TO VIF
 HOWEVER BASED ON PLANS AT THIS TIME THIS NEEDS TO BE
 VERIFIED AS LIGHT FIXTURES NEED TO BE RELOCATED.
  
 7) NOTE: PLEASE SEE AS PANEL SCHEDULES ARE NOW BEING
 SUBMITTED. PLEASE SEE THAT THESE ARE REQUIRED TO BE
 DETAILED FOR ALL ROOMS AND AREAS IN WHICH THEY FEED PER
 408.4, 240.4, 310.16.
 IE; BEDRM #2 LTS, KITCHEN LTS. ETC
 FBC 106.1.2, 106.3.5.4, 106.5
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE ALONG KITCHEN
 WALL IN GUEST HOUSE AND NEW MASTER BEDROOM WALL PER
 210.52.
 ONE WAS GIVEN ON PREVIOUS REVIEW AND CODE FOR 210.52.
 THE PREVIOUS EXAMPLE FOR MISSING WAS DONE BUT NOT ALL
 LOCATIONS FOR NEW WALLS 2FT OR MORE WHERE REQUIRED PER
 210.52.
  
 9) NOTE: PLEASE GO OVER LOAD CALCULATIONS AS THE SQ FT
 FOR GUEST HOUSE ON MAIN SERVICE LOAD SUMMARY DOES NOT
 COORDINATE WITH THE SQ FT ON GUEST HOUSE PANEL
 CALCULAITONS.
 NEC 220
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2007-12-24 Time 13:06 Sent To P
Notes
2007-12-24 13:06:35** DENIEDREVIEW **
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 ** THE FOLLOWING COMMENTS ARE BASED ON PLANS SUBMITTED
 ONLY.
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING ADOPTED CODES BY THE STATE.
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING
 FIRM IS MISSING THE PRINTED NAME AND PRINTED LICENSE
 NUMBER OF THE ENGINEER AS REQUIRED BY THE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002
  
 3) NOTE: PLEASE SEE THE NEW SERVICE RISER AS SUBMITTED
 NEEDS SEVERAL ITEMS TO BE ADDRESSED:
  
 A) PLEASE SEE THE NEW MAIN DISCONNECT AND NEW PANEL FOR
 THE NEW GUEST HOUSE SHOWS 75AMP MAIN AND PANEL, HOWEVER
 THIS DOES NOT CORRELATE WITH THE STANDARD OVER CURRENT
 PROTECTION DEVICES OR EQUIPMENT AS STATED IN THE NEC
 240.6.
 PLEASE ALSO SEE 110.3, 90.7 AND ADJUST.
  
 B) PLEASE INCLUDE THE SIZE (AMPERAGE) OF NEW METER.
 90.7, 230.70, 230.71, 230.90 ETC
  
 C) PLEASE INCLUDE THE TAPPED CONDUCTORS FROM NEW
 SERVICE GUTTER TO NEW MAIN. 240.21, 240.4, 310.16 ETC
  
 D) PLEASE SEE MISSING REQUIRED DISCONNECTING MEANS AT
 THE MAIN HOUSE PER 225.31-225.39.
  
 E) PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM AT THE
 MAIN HOUSE PER 250.32, 250.50.
  
 F) PLEASE COMPLETE GROUNDING ELECTRODE AT THE SERVICE
 LOCATION. THE GROUNDING DETAIL ON E-2 NOTES GROUND RODS
 PER 250.83, AND 250.84 HOWEVER PLEASE SEE THE 2005 NEC,
 AS 250.83 DOES NOT EXIST AND 250.84 IS NOT FOR GROUND
 RODS. PLEASE ADJUST SYSTEM AND NOTES.
  
 4) NOTE: PLEASE CLARIFY THE SMOKE DEVICES ON PLANS.
 PLEASE SEE THE SYMBOL AS SHOWN WHICH IS THE *S* IN THE
 BOX IS NOTED AS A DUCT DETECTOR ON SYMBOL LEGEND.
 PLEASE SEE R313 AND NFPA-72 11.5.1.1.1 AND 11.8.3 AS
 THESE SHOULD BE NOTED AS SA FOR SMOKE ALARMS.
 PLEASE SEE MISSING SA OUTSIDE BEDROOM AT THE GUEST
 HOUSE.
 PLEASE ADJUST NOTES AND PLANS.
  
 5) NOTE: PLEASE SUBMIT PANEL SCHEDULES FOR BOTH THE NEW
 PANEL AT GUEST HOUSE AND THE NEW PANEL AT THE MAIN
 HOUSE. PLEASE SHOW ALL NEW MINIMUM CIRCUITS REQUIRED BY
 THE NEC ALONG WITH THE ADDITIONAL AND EXISTING
 CIRCUITS. PLEASE PROVIDE THE BRANCH CIRCUIT SIZE, OVER
 CURRENT PROTECTION RATING AND CONDUCTORS.
 PLEASE SEE SOME COMMENTS BELOW AS THE *LOAD SUMMARY*
 SUBMITTED CONTAIN ITEMS WHICH DO NOT MEET THE MINIMUM
 PER NEC.
 408.4, 240.4, 310.16, ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE THE WATER HEATER AS SHOWN ON LOAD
 SUMMARY DOES NOT MEET 422.1AND422.13. PLEASE SEE THE
 LOAD IS SHOWN AT 6KW YET THE OVER CURRENT PROTECTION IS
 SHOWN AS A 20AMP BREAKER.
 ** PLEASE ALSO SEE THE PLAN WHICH SHOWS 60AMP FOR THE
 WATER HEATER?
 ** IS THERE ARE WATER HEATER AT THE MAIN HOUSE?
  
 7) NOTE: PLEASE SEE THE MINIMUM LOAD WHICH THE CODE
 REQUIRES FOR THE DRYER SHALL BE 5KW. PLEASE SEE NEC
 220.54.
 PLEASE ALSO SEE THE SIZE OF THE CIRCUIT SHALL BE BASED
 ON THE LOAD AND VOLTAGE SUPPLIED. (SHOWS 20AMPS BREAKER
 WHICH IS NOT RATED FOR 5KW AT 240V). PLEASE ADJUST
  
 8) NOTE: PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR
 EACH PANEL AND FOR SERVICE. PLEASE CORRECT AS PER NOTES
 ABOVE PER NEC 220.
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE DISCONNECT(S) SHOWN FOR CONDENSING
 UNITS DO NOT COMPLIANCE FOR 110.26.
 PLEASE RE-LOCATE
  
 10) NOTE: PLEASE VERIFY THE GFI SHOWN ON PLANS AT THE
 MAIN HOUSE MEETING 210.63/210.8A FOR THE OUTSIDE
 CONDENSING UNIT. PLAN SHOWS THIS FOR A PUMP. IF THIS IS
 FOR THE PUMP, THE SERVICE RECEPTACLE AS REQUIRED PER
 SECTIONS GIVEN WOULD BE IN ADDITION TO THE DEDICATE GFI
 SUPPLIED FOR THE PUMP.
  
 11) NOTE: PLEASE SEE NEC 680.22 AS THE LIGHTING
 FIXTURES SHOWN ON MAIN HOUSE AND GUEST HOUSE DO NOT
 MEET THE MINIMUM DISTANCES PER SECTION GIVEN.
  
 12) NOTE: PLEASE SEE THE EGRESS LIGHTING CONTROL AT THE
 GUEST HOUSE MUST BE INSIDE THE ROOM (OFFICE) AS SHOWN
 PER 210.70.
  
 13) NOTE: PLEASE SEE NEC2005 210.12 WHICH REQUIRED
 AFCI PROTECTION FOR ALL OUTLETS IN BEDROOM/SLEEPING
 ROOMS. THIS INCLUDES ALL RECEPTACLES, LIGHTS, FANS,
 SMOKE ALARMS ETC.
 PLEASE SEE THE PLANS ONLY SHOW PROTECTION FOR
 RECEPTACLES WHICH WAS IN THE 2002 NEC.
 PLEASE LIST ON THE BRANCH CIRCUITS TO BE PROVIDED ON
 THE NEW PANEL SCHEDULES TO BE SUBMITTED.
  
 14) NOTE: PLEASE SUBMIT AND SHOW THE REQUIRED AIC
 RATING FOR SERVICE MAINS AND EQUIPMENT PER 110.9.
  
 15) NOTE: PLEASE PROVIDE NOTE FOR TYPE OF RECESSED
 LIGHTING FIXTURES PER 13-606.1.ABC.1.2.4
  
 16) NOTE: PLEASE SEE THERE ARE SEVERAL GFI RECEPTACLES
 ON PLAN WHICH SHOWS THE SYMBOL FOR HALF SWITCHED
 DEVICE. GFI RECEPTACLES CAN NOT BE HALF SWITCHED.
 110.3
  
 17) NOTE: PLEASE SEE MISSING RECEPTACLE IN OFFICE ALONG
 2FT OF WALL PER 210.52
  
 18) NOTE: PLEASE SEE REQUIRED DEDICATED CIRCUIT(S) FOR
 BATH ROOMS TO BE CONFIRMED ON NEW PANEL SCHEDULES.
 PLEASE SEE 210.11C3 AS THESE ARE REQUIRED TO BE 20AMP
 AND #12.
  
 ** AS NOTED ABOVE, PLEASE KNOW AS THERE ARE MANY ITEMS
 NOT SUBMITTED OR SHOWN, A COMPLETER REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.** IF THERE ARE
 QUESTIONS, PLEASE CALL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2010-09-23 Cont ID  
Sent By jgomez Date 2010-09-23 Time 11:17 Rev Time 0.00
Received By jgomez Date 2010-09-23 Time 11:17 Sent To Z
Notes
2010-09-23 11:18:17LANDSCAPE PLANS SENT TO ZONING FOR R. KUSSNER REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 13:27 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 13:27 Sent To E
Notes
2009-03-24 13:27:37SENT TO DVP DESK.

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-02-26 Cont ID  
Sent By adarroug Date 2009-02-26 Time 12:23 Rev Time 0.00
Received By adarroug Date 2009-02-26 Time 12:23 Sent To Z
Notes
2009-02-26 12:23:30TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-01-07 Cont ID  
Sent By adarroug Date 2009-01-07 Time 10:05 Rev Time 0.00
Received By adarroug Date 2009-01-07 Time 10:05 Sent To P
Notes
2009-01-07 10:06:06TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 16:10 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 16:10 Sent To M
Notes
2008-10-03 16:11:12TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 16:44 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 16:44 Sent To M
Notes
2008-09-25 16:44:38TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 16:34 Sent To M
Notes
2008-09-22 16:35:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 11:16 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 11:16 Sent To B
Notes
2008-08-25 11:17:47TO BUILDINGA.M.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-11 Cont ID  
Sent By adarroug Date 2008-08-11 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-08-11 Time 10:54 Sent To B
Notes
2008-08-11 10:55:01TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-11 Cont ID  
Sent By adarroug Date 2008-08-11 Time 10:14 Rev Time 0.00
Received By adarroug Date 2008-08-11 Time 10:11 Sent To B
Notes
2008-08-11 10:14:37TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-14 Cont ID  
Sent By adarroug Date 2008-04-14 Time 15:56 Rev Time 0.00
Received By adarroug Date 2008-04-14 Time 15:56 Sent To B
Notes
2008-04-14 15:56:51TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 09:26 Sent To M
Notes
2008-04-02 09:26:57TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 09:52 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 09:52 Sent To E
Notes
2008-03-21 09:52:33TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 10:06 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 10:06 Sent To Z
Notes
2008-02-19 10:06:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-01-09 Time   Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:22 Sent To  
Notes
2007-12-20 17:22:16SENT TO SINGLE FAMILY RACK MMILLER

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-09-27 Cont ID  
Sent By rkussner Date 2010-09-27 Time 10:12 Rev Time 0.00
Received By rkussner Date 2010-09-27 Time 10:12 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-10-22 Cont ID  
Sent By rkussner Date 2009-10-22 Time 16:30 Rev Time 0.00
Received By rkussner Date 2009-10-22 Time 16:30 Sent To  
Notes
2009-10-22 16:42:09***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 2. PURSUANT TO SECTION 94-448 (D) (2), ALL RELEVANT
 ITEMS FOUND IN THIS SECTION SHALL BE PART OF THE
 LANDSCAPE PLAN.
  
 3. PROVIDE THE SPACING FOR ALL HEDGES AND GROUND COVER.
  
 4. THE 9 FOOT HEDGE ADJACENT TO GREENWOOD LANE CREATES
 A VISIBILITY CONCERN WHEN SOMEONE IS EXITING THE
 DRIVEWAY. THE HEDGE SHALL BE REDUCED IN HEIGHT TO ALLOW
 VISIBILITY ADJACENT TO THE DRIVEWAY.
  
 5. PROVIDE A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE
 BROKEN DOWN INTO UNIT COST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-03-12 Cont ID  
Sent By rregueir Date 2009-03-12 Time 20:20 Rev Time 0.00
Received By rregueir Date 2009-03-12 Time 20:20 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-10-06 Cont ID  
Sent By tgordon Date 2008-10-06 Time 08:40 Rev Time 0.45
Received By tgordon Date 2008-10-06 Time 08:40 Sent To  
Notes
2008-10-06 08:41:25REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2008-09-26 Cont ID  
Sent By tgordon Date 2008-09-26 Time 08:48 Rev Time 0.30
Received By tgordon Date 2008-09-26 Time 08:48 Sent To  
Notes
2008-09-26 08:49:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M-1
 *** DENIED ***
  
 *AS NOTED IN LAST REVIEW 9/23/08*
  
 1) THE LETTER SUBMITTED TO TERMINATE AGILE ENGINEERING
 INC. CAN NOT BE EXCEPTED AS THE MECHANICAL CONTRACTOR
 WAS NOT THE PERSON TO HIRER THEIR FIRM, SEE F.A.C.
 61G15-27. THE PROPERTY OWNER OR THE GENERAL CONTRACTOR
 (PERSON WHO HIRED THE FIRM) NEEDS TO PREPARE AND SUBMIT
 THE LETTER TO REMOVE THE ENGINEER. PLEASE HAVE THE JOB
 ADDRESS AND PERMIT NUMBER ON THE LETTER WHEN
 SUBMITTING.
  
 2) TITLE BLOCK OF REVISED PLAN HAS THE WRONG LICENSE
 NUMBER FOR SCOTT WEBSTER.
  
 3) BE ADVISED "TROPICAL COOLING, INC." IS NOT A
 LICENSED COMPANY, PLEASE CORRECT.
  
 4) IF THIS PLAN IS TO BE SUBMITTED AFTER THE ABOVE
 CORRECTIONS ARE MADE. THE RETURN AIR TRANSFER DUCT
 (FLEX) FROM THE BEDROOM TO THE OFFICE NEEDS TO BE SIZED
 ON THE PLAN, PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-09-23 Cont ID  
Sent By tgordon Date 2008-09-23 Time 13:30 Rev Time 0.10
Received By tgordon Date 2008-09-23 Time 13:30 Sent To  
Notes
2008-09-23 14:07:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M-1
 *** DENIED ***
  
 1) THE LETTER SUBMITTED TO TERMINATE AGILE ENGINEERING
 INC. CAN NOT BE EXCEPTED AS THE MECHANICAL CONTRACTOR
 WAS NOT THE PERSON TO HIRER THEIR FIRM, SEE F.A.C.
 61G15-27. THE PROPERTY OWNER OR THE GENERAL CONTRACTOR
 (PERSON WHO HIRED THE FIRM) NEEDS TO PREPARE AND SUBMIT
 THE LETTER TO REMOVE THE ENGINEER. PLEASE HAVE THE JOB
 ADDRESS AND PERMIT NUMBER ON THE LETTER WHEN
 SUBMITTING.
  
 2) TITLE BLOCK OF REVISED PLAN HAS THE WRONG LICENSE
 NUMBER FOR SCOTT WEBSTER.
  
 3) BE ADVISED "TROPICAL COOLING, INC." IS NOT A
 LICENSED COMPANY, PLEASE CORRECT.
  
 4) IF THIS PLAN IS TO BE SUBMITTED AFTER THE ABOVE
 CORRECTIONS ARE MADE. THE RETURN AIR TRANSFER DUCT
 (FLEX) FROM THE BEDROOM TO THE OFFICE NEEDS TO BE SIZED
 ON THE PLAN, PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-04-07 Cont ID  
Sent By tgordon Date 2008-04-07 Time 08:38 Rev Time 0.20
Received By tgordon Date 2008-04-07 Time 08:38 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-04-03 Cont ID  
Sent By tgordon Date 2008-04-03 Time 08:43 Rev Time 0.40
Received By tgordon Date 2008-04-03 Time 08:43 Sent To B
Notes
2008-04-03 08:48:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 ** ENERGY CALCULATIONS FOR GUEST HOUSE HAVE NOT BEEN
 REVISED SO COMMENTS FROM LAST REVIEW STILL NEED TO BE
 ADDRESSED. **
  
 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS A
 34,200 BTU A/C SYSTEM BEING INSTALLED PLANS STATE A
 17,300 BTU SYSTEM IS BEING INSTALLED, PLEASE CORRECT
 ENERGY CAL'S.
  
 2) ENERGY CALCULATIONS FOR GUEST HOUSE SHOW UNDUCTED
 COOLING AND HEATING SYSTEM, PLANS SHOW A DUCTED SYSTEM,
 PLEASE CORRECT ENERGY CAL'S.
  
 3) ENERGY CALCULATION FOR THE GUEST HOUSE ARE TAKING
 THE CROSS VENTILATION CREDIT ON LINE 15. PLEASE SUBMIT
 CALCULATIONS FOR THE 12% BUILDING OPENINGS TO FLOOR
 AREA, SEE 2004 FBC 13-607.1.A.3.1.
  
 3A) ALSO ADD DETAIL FOR SCREEN DOORS TO BE INSTALLED AT
 DOOR OPENING IF THESE OPENINGS ARE INCLUDED IN THE
 ABOVE CALCULATIONS, PER 2004 FBC 13-607.1.A.3.1.
  
 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE
 WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR
 VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 11:48 Rev Time 0.45
Received By tgordon Date 2008-03-21 Time 11:48 Sent To B
Notes
2008-03-21 12:04:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS A
 34,200 BTU A/C SYSTEM BEING INSTALLED PLANS STATE A
 17,300 BTU SYSTEM IS BEING INSTALLED, PLEASE CORRECT
 ENERGY CAL'S.
  
 2) ENERGY CALCULATIONS FOR GUEST HOUSE SHOW UNDUCTED
 COOLING AND HEATING SYSTEM, PLANS SHOW A DUCTED SYSTEM,
 PLEASE CORRECT ENERGY CAL'S.
  
 3) ENERGY CALCULATION FOR THE MAIN HOUSE AND THE GUEST
 HOUSE ARE TAKING THE CROSS VENTILATION CREDIT ON LINE
 15. PLEASE SUBMIT CALCULATIONS FOR THE 12% BUILDING
 OPENINGS TO FLOOR AREA, SEE 2004 FBC 13-607.1.A.3.1.
  
 3A) ALSO ADD DETAIL FOR SCREEN DOORS TO BE INSTALLED AT
 DOOR OPENING IF THESE OPENINGS ARE INCLUDED IN THE
 ABOVE CALCULATIONS, PER 2004 FBC 13-607.1.A.3.1.
  
 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE
 WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR
 VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 4) PLEASE SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS
 FOR THE MAIN AND GUEST HOUSE, AS ONLY ONE COPY WAS
 SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By tgordon Date 2008-02-25 Time 08:48 Rev Time 0.30
Received By tgordon Date 2008-02-25 Time 08:48 Sent To P
Notes
2008-02-25 08:58:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 12-24-07 NOTE #1 ENERGY
 CALCULATIONS FOR MAIN HOUSE AND GUEST HOUSE LINE 13A
 ARE CALLING FOR HEAT PUMP UNITS, MECHANICAL PLAN PAGE
 M-2 IS SHOWING STRAIGHT COOLING UNITS, THE TWO MUST
 COINCIDE, SEE 2004 FBC 13-600.3.ABC.2. PLEASE CORRECT.
  
 2) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By tgordon Date 2007-12-24 Time 08:20 Rev Time 0.30
Received By tgordon Date 2007-12-24 Time 08:20 Sent To E
Notes
2007-12-24 08:30:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 13A AND B ARE CALLING FOR
 HEAT PUMP UNITS, MECHANICAL PLAN PAGE M-2 IS SHOWING
 STRAIGHT COOLING UNITS, THE TWO MUST COINCIDE, PLEASE
 CORRECT.
  
 2) THE TWO BUILDING CAN NOT BE ON THE SAME ENERGY
 CALCULATIONS, THEY MUST EACH HAVE THERE OWN ENERGY
 CALCULATIONS DONE, SEE 2004 FBC 13-101.2.5.1. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-03-16 Cont ID  
Sent By lwagner Date 2009-03-16 Time 11:36 Rev Time 0.00
Received By lwagner Date 2009-03-16 Time 11:15 Sent To B
Notes
2009-03-16 11:38:20REVISION OK
 LETTER REMOVING ENGINEER ON FILE.

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-01-30 Cont ID  
Sent By lwagner Date 2009-01-30 Time 08:47 Rev Time 0.00
Received By lwagner Date 2009-01-29 Time 09:44 Sent To  
Notes
2009-01-30 08:47:23PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 106.1 SUBMITTAL DOCUMENTS. IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF
 THIS STATE REGULATING THE PRACTICE OF
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART 1, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER
 471, FLORIDA STATUTES, THEN HE OR SHE
 SHALL AFFIX HIS OR HER SEAL, SIGNATURE
 AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES.
  
 REVIEW BY LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By mperson Date 2008-02-25 Time 13:26 Rev Time 0.00
Received By mperson Date 2008-02-25 Time 13:26 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mperson Date 2007-12-28 Time 13:40 Rev Time 0.00
Received By mperson Date 2007-12-28 Time 13:40 Sent To B
Notes
2007-12-28 14:21:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1 PLUMBING PLAN, AND SHEET P-2 SANITARY
 RISER: THE HORIZONTAL DRY VENT FOR THE GUEST HOUSE
 SHOWER IS NOT ALLOWED PER THE FOLLOWING.
  
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
  
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6
 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
 EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS.
  
 2. SHEET P-1 PLUMBING PLAN AND SHEET P-2 SANITARY
 RISER: TWO-WAY CLEANOUTS ARE REQUIRED FOR THE ADDITION
 AND GUEST HOUSE SANITARY SYSTEM PER THE FOLLOWING.
  
 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
 THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT
 SHALL BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL AND
 SHALL BE BROUGHT UP TO THE FINISHED GROUND LEVEL OR TO
 THE BASEMENT FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT
 IS ALLOWED TO BE USED AT THIS LOCATION TO SERVE AS A
 REQUIRED CLEANOUT FOR BOTH THE BUILDING DRAIN AND
 BUILDING SEWER. THE CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER SHALL NOT BE REQUIRED
 IF THE CLEANOUT ON A 3-INCH (76 MM) OR LARGER DIAMETER
 SOIL STACK IS LOCATED WITHIN A DEVELOPED LENGTH OF 10
 FEET (3048 MM) OF THE BUILDING DRAIN AND BUILDING SEWER
 CONNECTION. THE MINIMUM SIZE OF THE CLEANOUT AT THE
 JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER SHALL
 COMPLY WITH SECTION 708.7 .
  
 3. SHEET P-1 PLUMBING PLAN AND SHEET P-2 SANITARY
 RISER: PLEASE INDICATED THAT THE SANITARY CONNECTION
 FROM THE ADDITION AND GUEST HOUSE TO THE EXISTING
 SYSTEM SHALL CONNECT DOWNSTREAM OF THE EXISTING WET
 VENTED BATHROOM PER THE FOLLOWING.
  
 909.1 WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-03-03 Cont ID  
Sent By mcruz Date 2009-03-03 Time 11:55 Rev Time 0.00
Received By mcruz Date 2009-03-03 Time 11:24 Sent To E
Notes
2009-03-03 11:55:04PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE ON THE SURVEY THE SETBACK DIMENSIONS FROM
 THE PROPOSED CARPORT AND FRONT PORCH TO ALL ADJACENT
 PROPSETY LINES.
  
 4. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED ADDITION ON
 THE ELEVATION PLAN. PURSUANT TO THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-611, THE
 HEIGHT SHALL BE MEASURED AS THE VERTICAL DISTANCE FROM
 THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE
 BUILDING TO THE MEAN HEIGHT LEVEL BETWEEN EAVES AND
 RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-20 Cont ID  
Sent By choops Date 2008-02-20 Time 09:13 Rev Time 0.00
Received By choops Date 2008-02-20 Time 09:13 Sent To E
Notes
2008-02-20 09:19:29***APPROVED - RESUB #1***
  
 PROVISO:AS THE LOT FAILS TO MEET THE ADDITIONAL
 STANDARDS FOUND IN SECTION 94-303 OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS:THE ACCESSORY
 STRUCTURE SHALL NOT BE USED AS A SEPARATE DWELLING
 UNIT, AND NO RENTAL LICENSE SHALL BE ISSUED FOR THE
 ACCESSORY STRUCTURE.
  
  
  
 SENT TO "E" - BT (DP OUT)

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 09:57 Rev Time 0.00
Received By choops Date 2007-12-21 Time 09:57 Sent To E
Notes
2007-12-21 10:09:19***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 3)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 4)INDICATE SETBACK DIMENSIONS FROM PROPOSED MAIN
 HOUSE ADDITION TO PROPERTY LINES.
  
 5)THE SQUARE FOOTAGE OF THE EXISTING PAVING IS SHOWN
 ON SHEET SP-1, HOWEVER THE PROPOSED IS NOT.INDICATE
 PROPOSED SQUARE FOOTAGE OF DRIVEWAY, INCLUDING WALKWAY
 AND ANY OTHER IMPERMEABLE SURFACE WITHIN THE FRONT
 YARD.
  
 6)THE MAIN HOUSE ROOF PLAN (SHEET A-2) SHOWS
 ADDITION OVERHANG AS 2'8" , THE MAIN HOUSE WALL SECTION
 (SHEET A-5) SHOWS THE OVERHANG AS 2'0" ...PLEASE
 CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720