Plan Review Details - Permit 07120384
Plan Review Stops For Permit 07120384
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-13 Cont ID  
Sent By mjacobs Date 2008-03-13 Time 08:46 Rev Time 0.00
Received By mjacobs Date 2008-03-13 Time 07:52 Sent To PC
Notes
2008-03-13 08:46:56PROCESSING PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-12 Cont ID  
Sent By mjacobs Date 2008-03-12 Time 16:04 Rev Time 0.00
Received By mjacobs Date 2008-03-12 Time 14:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By mjacobs Date 2007-12-26 Time 11:59 Rev Time 0.00
Received By mjacobs Date 2007-12-26 Time 06:18 Sent To  
Notes
2007-12-26 11:59:19 
 BUILDING PLAN REVIEW
 PERMIT: 07120384
 ADD: 2800 N. FLAGLER DR. #412
 CONT: R.W. MORRELL
 TEL: (561)714-8216
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE CERTIFICATE OF AUTHORIZATION IS MISSING FROM
 THE DRAWINGS. ANY PERSON PRACTICING UNDER A FICTITIOUS
 NAME, OFFERING ARCHITECTURAL SERVICES TO THE PUBLIC
 SHALL DISPLAY THEIR CERTIFICATE OF AUTHORIZATION NUMBER
 ON SAID INFORMATION. FLORIDA STATUTES 481.219 AND
 F.A.C. 61G1-16.004.
  
 3)THE DIMENSION OF THE WINDOW SHALL BE INDICATED ON
 THE DRAWINGS PER FBC 106.1.1.
  
 4)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS ARE
 MISSING THE APPROVAL SIGNATURE OF THE DESIGNER OF
 RECORD.
  
 NOTE: SEE MIAMI DADE NOA #05-1018-01 WHICH HAS MORE
 INFORMATION THE WINDOW SUBMITTED. YOU MAY ALSO SUBMIT
 NOA ALONG THE FL#2769.FROM THE NOA CIRCLE THE WINDOW
 WHICH WILL BE INSTALLED AND ALL INFORMATION PERTAINING
 TO THE INSTALLATION.
  
 5) THE DESIGN PRESSURES FOR ALL BUILDINGS OVER 60 FEET
 SHALL BE CALCULATED BY A PROFESSIONAL ENGINEER USING
 ASCE 7 AND EXPOSURE A, B OR C DEPENDING ON THE LOCATION
 OF THE BUILDING. THE DESIGN PROFESSIONAL SHALL INDICATE
 THE DESIGN PRESSURES FOR THE WINDOWS. THE MEAN ROOF
 HEIGHT AND EXPOSURE CATEGORY SHALL BE STATED ON THE
 PLANS PER FBC 1609.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-06 Cont ID  
Sent By btrobaug Date 2008-03-06 Time 15:11 Rev Time 0.00
Received By btrobaug Date 2008-03-06 Time 15:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 16:56 Sent To  
Notes
2007-12-22 16:56:11** DENIED**
  
 *
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70 (SHOWS 2002)
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER PER FAC 61G1-16.004
 AND FS 481.219.
 PLEASE CONFIRM.
  
 3) NOTE: PLEASE CLARIFY IF ALL CIRCUITS FROM EXISTING
 PANEL LOCATION WILL BE ROUTED TO NEW PANEL LOCATION.
 PLEASE SEE IF UNIT AND ALL BRANCH CIRCUIT CONDUCTORS
 ARE NOT BEING ROUTED AND RE-WIRED TO NEW PANEL LOCATION
 THE ONE INCH CONDUIT BEING SHOWN AS NEW TO BE INSTALLED
 IS NOT LARGE ENOUGH FOR PIPE FILL.
 PLEASE SEE TABLES IN CHAPTER NINE OF THE NEC.
  
 4) NOTE: PLEASE SEE NOTE ON THE BOTTOM OF THE PANEL
 SCHEDULE MENTIONS ALL BEDROOM CIRCUITS TO BE ARC FAULT
 WHICH IS OK, HOWEVER PLEASE SEE ONLY CIRCUIT #12 IS
 SHOWN AS AFCI ON PANEL SCHEDULE.
 210.12 OF THE 2005 NEC REQUIRE ALL OUTLETS INCLUDING
 LIGHTING AND SMOKE ALARMS.
  
 5) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE DEVICES
 ON PLANS SHOW SMOKE DETECTORS WHICH ARE DEVICES WHICH
 DETECT AND DO NOT SOUND AN ALARM. IF THE DEVICES ARE
 UNITS WHICH DETECT AND SOUND AN ALARM PLEASE ADJUST
 DESIGNATION TO SA.
 ** NOTE ON LEFT OF PLANS LEND TO THESE AS BEING SMOKE
 ALARMS**
  
 6) NOTE: PLEASE CLARIFY KITCHEN CIRCUITING AS THE
 KITCHEN ONLY INDICATES ONE SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210.52B1, 210.11C1. IF RE-WIRE OF BRANCH
 CIRCUITS TO PANEL IS BEING DONE, THIS WILL BE REQUIRED
 TO MEET THE MINIMUM. THIS IS A SAFETY ISSUE DUE TO OVER
 LOADING OF CIRCUIT IN KITCHEN IF ONLY ONE IS PRESENT.
  
 7) NOTE: PLEASE SEE NEC 210.4B AS THE DISHWASHER AND
 DISPOSAL IS BEING SHOWN ON THE SAME YOKE YET THE PANEL
 SCHEDULE SHOWS BOTH OF THESE CIRCUITS ON SINGLE POLE
 BREAKERS. THIS WOULD BE REQUIRED TO BE A DOUBLE POLE
 BREAKER IF FEEDING A SINGLE YOKE/DEVICE.
 PLEASE ADJUST.
  
 8) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND LOAD
 CALCULATIONS.
 PLEASE SEE THE PANEL SCHEDULE INDICATES AN OVEN, YET
 NOT IN LOAD CALCULATIONS.
 PLEASE ALSO SEE THE OVEN IS NOT SHOWN ON PLANS.
 PLEASE SEE THE CALCULATIONS INDICATES A LAUNDRY
 CIRCUIT, HOWEVER NO LAUNDRY ON PLANS OR PANEL
 SCHEDULE.
 PLEASE SEE THE WATER HEATER IS SHOWN AS 3KW ON
 CALCULATIONS, YET THE PANEL SCHEDULE SHOWS THIS AS
 4.5KW.
 PLEASE ALSO SEE THIS SAME WATER HEATER WITH A 4.5KW
 LOAD IS SHOWN ON A SINGLE POLE 20AMP BREAKER WITH #12
 CONDUCTORS.
 PLEASE SEE 408.4, 240.4, 310.16 ETC AND ADJUST AND
 CORRELATE ALL.
 THE ABOVE WAS A FEW EXAMPLES, PLEASE BE SURE TO GO OVER
 ALL.
  
 9) NOTE: PLEASE KNOW DEPENDING ON SCOPE WORK A NEW GFI
 RECEPTACLE MAY BE REQUIRED ALONG KITCHEN COUNTER SPACE
 AS THIS DOES NOT MEET 210.52C1.
 PLEASE SEE THE CODE HAS REQUIRED SPACE ALONG COUNTERS
 TO MEET 210.52C1 FOR DECADES.
 PLEASE SEE AS IT APPEARS THE EXISTING PANEL WAS PLACED
 INSIDE THE OLDER KITCHEN CABINETS WHICH WAS NEVER
 PERMITTED UNDER THE NEC, THE COUNTER SPACE/CABINETS
 APPEAR TO HAVE BEEN ADDED AT SOME POINT.
 IF SPACING EXISTS AND MEETS NEC, PLEASE SHOW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-03-12 Cont ID  
Sent By mawillia Date 2008-03-12 Time 16:40 Rev Time 0.00
Received By mawillia Date 2008-03-12 Time 16:35 Sent To B1
Notes
2008-03-12 16:39:41*****APPROVED*****
  
 THE PLAN SHEET WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-01-02 Cont ID  
Sent By mwennerg Date 2008-01-02 Time 10:55 Rev Time 0.00
Received By mwennerg Date 2008-01-02 Time 10:55 Sent To  
Notes
2008-01-02 10:58:05***PROVISO***
  
 1) PLEASE SEE ELECTRICAL COMMENT #5 REGARDING DEFINITON
 OF APPLIANCES AND MAKE APPROPRIATE CORRECTION. PLANS
 WILL BE STAMPED AND DATED WHEN RETURNED FOR
 CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 10:18 Sent To  
Notes
2008-03-03 10:21:30TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-12-26 Time   Rev Time 0.00
Received By adarroug Date 2007-12-17 Time 10:31 Sent To  
Notes
2007-12-20 17:48:11BOB # 10 AS OF 12/20/2007
2007-12-17 10:33:20WAITING FOR "BOB"

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-24 Cont ID  
Sent By choops Date 2007-12-24 Time 10:20 Rev Time 0.00
Received By choops Date 2007-12-24 Time 10:20 Sent To  
Notes
2007-12-24 10:20:50*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.