Plan Review Details - Permit 07120310
Plan Review Stops For Permit 07120310
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-01-24 Cont ID  
Sent By lursu Date 2007-12-24 Time 10:01 Rev Time 0.00
Received By jleech Date 2007-12-24 Time 10:01 Sent To  
Notes
2007-12-24 10:02:24PLEASE CLARIFY THE JOB LOCATION ,EITHER UNIT 800 OR 600
 , PLANS AND PERMIT APPLICATION DO NOT MATCH.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-14 Cont ID  
Sent By mjacobs Date 2008-03-14 Time 13:27 Rev Time 0.00
Received By mjacobs Date 2008-03-14 Time 10:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-02-25 Cont ID  
Sent By mjacobs Date 2008-02-25 Time 14:11 Rev Time 0.00
Received By mjacobs Date 2008-02-25 Time 13:17 Sent To  
Notes
2008-02-25 14:11:43BUILDING PLAN REVIEW
 PERMIT: 07120310
 ADD: 2090 PBL BLVD. #801-802
 CONT: S.O. ENTERPRISES INC.
 TEL: (561)827-6508
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION: 2-25-08
 ACTION: DENIED
  
 1)WPB AMENDMENTS 106.1.3 THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY
 TO ITS RERECORD RETENTION PROGRAM: NO ?HAND WRITTINN?
 IN PEN OR PENCIL ?NO WHITE-OUT CHANGES SHALL BE MADE TO
 THE DRAWINGS.
  
 2)CHANGES WERE MADE ONLY ON ONE SET WITH THE
 ABBREVIATION OF ?FD?. BOTH SHEETS SHALL HAVE THE SAME
 CHANGES SO THAT THE FILE SET AND THE FIELD SET MIRROR
 EACH OTHER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-23 Cont ID  
Sent By mjacobs Date 2008-01-23 Time 09:45 Rev Time 0.00
Received By mjacobs Date 2008-01-23 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-08 Cont ID  
Sent By mjacobs Date 2008-01-08 Time 12:49 Rev Time 0.00
Received By mjacobs Date 2008-01-08 Time 11:40 Sent To PC
Notes
2008-01-08 12:49:38BUILDING PLAN REVIEW
 PERMIT: 07120310
 ADD: 2090 PBL BLVD. SUITE #?
 CONT: S.O. ENTERPRISES
 TEL: (561)827-6508
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 12/24/07
  
 1A)OK
 2)OK
 3)OK
  
 **NEW**
 FBC. 708.1 (5) WALLS SEPARATING INDIVIDUAL TENANT
 SPACES.EXCEPTION (1)IN GROUP B AND S OCCUPANCIES
 WALL USED TO SEPARATE TENANTS SHALL NOT BE REQUIRED TO
 HAVE FIRE-RESISTANCE RATING, PROVIDED NO AREA BETWEEN
 FIRE PARTITIONS HAVING A 1-HOUR FIRE-RESISTANCE RATING
 EXCEEDS 3,000 SQUARE FEET. SUITE #802 IS OVER THE 3000
 SQUARE FOOTAGE LIMIT, THEREFORE, THE ENTIRE SEPERATION
 WALL REQUIRES A 1-HOUR SEPERATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By mjacobs Date 2007-12-24 Time 13:41 Rev Time 0.00
Received By mjacobs Date 2007-12-24 Time 10:37 Sent To  
Notes
2007-12-24 13:41:53BUILDING PLAN REVIEW
 PERMIT: 07120310
 ADD: 2090 PBL BLVD. SUITE #?
 CONT: S.O. ENTERPRISES
 TEL: (561)827-6508
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 12/24/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FBC 106.1 THE DESIGN PROFESSIONAL SHALL AFFIX HIS
 OR HER OFFICIAL SEAL, SIGNATURE AND DATE TO ALL
 INFORMATION BEING FILED FOR PUBLIC RECORD PER FAC
 61G15-23.002 AND FLORIDA STATUTES 471. ONLY ONE SET
 CONTAIN THE SEAL, DATE AND SIGNATURE OF THE DESIGN
 PROFESSIONAL.
  
 3)THE ADDRESS ON THE APPLICATION FOR THE PROJECT
 SHOWS SUITE #800 HOWEVER, THE PLANS INDICATE SUITES
 #601 AND #602. CLARIFY THE CORRECT ADDRESS AND SUITE
 NUMBERS ON THE APPLICATION AND ON THE DRAWINGS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED FBC 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-03-24 Cont ID  
Sent By dpalmer Date 2008-03-24 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2008-03-24 Time 14:19 Sent To PC
Notes
2008-03-24 14:21:09** DENIED**
  
 1) NOTE: THE PLANS WERE ISSUED WITH A PROVISO TO HAVE
 THE PANEL SCHEDULE REVISED BEFORE FINAL. THE NEW
 CIRCUITING IS STILL NOT SHOWN ON PLANS AND PANEL
 SCHEDULE ONLY SHOWS *GENERAL LTS AND RECEPTACLES*. PER
 408.4, THE ROOMS, AREAS AND CIRCUITS FOR WHICH THEY
 FEED SHALL BE SPECIFIC.
 PLEASE OBTAIN CIRCUITING INFORMATION, PLACE ON NEW
 SHEETS AND HAVE CONTRACTOR SEND IN TO CHANGE OUT
 SHEETS.
  
 ** THE ABOVE WORDING WAS E-MAIL TO THE ENGINEER OF
 RECORD AT 2:18PM ON 3/24/08.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-03-14 Cont ID  
Sent By dpalmer Date 2008-03-14 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2008-03-14 Time 09:21 Sent To  
Notes
2008-03-14 09:21:29** DENIED REVISION ***
  
 1) NOTE: PLEASE SEE PLANS NOW STATES A NEW MAIN PANEL
 BOARD HOWEVER NO INFORMATION WAS SUBMITTED SHOWING ANY
 NEW FEEDERS, RISER INFORMATION, COMPLETE LOAD
 CALCULATIONS ADDING NEW PANEL BOARD ETC.
 PLEASE SEE NEC 220,230, 215, 240 ETC
 FBC 106.3.5.1.2
 ** NO REVIEW OF MANY ITEMS COULD BE DONE AS NO
 INFORMATION WAS SUBMITTED FOR NEW PANEL.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-16 Cont ID  
Sent By dpalmer Date 2008-01-16 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2008-01-16 Time 14:50 Sent To  
Notes
2008-01-16 14:50:59PASSED PREVIOUS REVIEW, STILL NEED REVISED PANEL
 SCHEDULES BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-03 Cont ID  
Sent By dpalmer Date 2008-01-03 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2008-01-03 Time 15:24 Sent To  
Notes
2008-01-03 15:25:10REVISED CIRCUITS/PANEL SCHEDULE(S) TO BE PROVIDED TO
 INSPECTOR PER 408.4

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 15:09 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 15:09 Sent To  
Notes
2007-12-22 15:09:14** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS:
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE PLANS CALL FOR SCOPE OF WORK ON 6TH
 FLOOR SUITES 601 AND 602 YET THE PERMIT APPLICATION
 STATES SUITE 800. PLANS AND PERMIT INFORMATION HAS BEEN
 ROUTED TO THE ADDRESSING REVIEWER.
 PLEASE BE SURE TO ADJUST INFORMATION ONCE DETERMINED.
  
 3) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND
 SEALED BY THE ENGINEER OF RECORD AS SHOWN ON TITLE
 BLOCKS. PLEASE SEE FAC 61G15-23.002 AND FS 471.025
  
 4) NOTE: PLEASE VERIFY CIRCUITING OF NEW RECEPTACLES
 SHOWN ON PLANS. WHERE ARE THEY CIRCUITED FROM? HOW WILL
 THE OCCUPANT HAVE ACCESS TO CIRCUITS AND OVER CURRENT
 PROTECTION DEVICES?
 PLEASE SEE 240.24, 310.16, 240.4 ETC.
 PLEASE INDICATE CIRCUITING FOR NEW EXIT/EMERGENCY
 LIGHTS PER 700.12F.
 FBC 106.1.2, 106.3.5.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mawillia Date 2008-03-17 Time 12:03 Sent To  
Notes
2008-03-17 12:13:36*****AS BUILT APPROVED*****
  
  
 PLAN SHEET A-3 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 15:01 Sent To  
Notes
2008-02-27 15:05:07***DENIED***
  
 PLEASE SEE BUILDING REVIEW COMMENTS REGARDING
 REQUIREMENTS FOR DRAWINGS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-22 Cont ID  
Sent By mwennerg Date 2008-01-22 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2008-01-22 Time 14:48 Sent To  
Notes
2008-01-22 14:49:39PASSED REVIEW ON 1/4/08 AND STAMPED, SIGNED AND DATED
 AT THAT TIME.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-04 Cont ID  
Sent By mwennerg Date 2008-01-04 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2008-01-04 Time 14:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By mwennerg Date 2007-12-26 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2007-12-26 Time 14:16 Sent To  
Notes
2007-12-26 14:20:59***DENIED***
  
 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY
 DESIGN PROFESSIONAL.
  
 2) PLEASE CLARIFY ADDRESS AND ENSURE THAT DRAWINGS AND
 APPLICATION ILLUSTRATE ACCURATE INFORMATION. ADDRESS
 CHARACTER TO COMPLY WITH CITY OF WEST PALM BEACH
 REQUIREMENTS FOR COMMERCIAL PROPERTY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 11:59 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 11:59 Sent To M
Notes
2008-03-31 12:00:22TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 09:02 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 09:02 Sent To E
Notes
2008-03-21 09:03:08TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 11:18 Sent To  
Notes
2008-03-10 11:20:58TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 10:19 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 10:19 Sent To  
Notes
2008-02-21 10:23:44TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 10:53 Sent To  
Notes
2008-01-15 10:54:05TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-31 Cont ID  
Sent By spalmer Date 2007-12-31 Time 11:08 Rev Time 0.00
Received By spalmer Date 2007-12-31 Time 11:08 Sent To  
Notes
2007-12-31 11:09:12TO "BOB"# 4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 08:18 Rev Time 0.00
Received By tgordon Date 2007-12-13 Time 10:30 Sent To  
Notes
2007-12-13 10:33:04TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By tgordon Date 2008-04-01 Time 08:18 Rev Time 0.30
Received By tgordon Date 2008-04-01 Time 08:18 Sent To  
Notes
2008-04-01 08:20:03MECHANICAL REVISION TO PLAN A-3.
 *** PROVISO ***
 1) PER 2004 FBC/M 607.5.3DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING, OR
 MEET THE EXCEPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-02-26 Cont ID  
Sent By tgordon Date 2008-02-26 Time 09:06 Rev Time 0.25
Received By tgordon Date 2008-02-26 Time 09:06 Sent To  
Notes
2008-02-26 09:08:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO PLANS PAGE A-3 **
 *** DENIED ***
 1) SEE BUILDING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-01-15 Cont ID  
Sent By tgordon Date 2008-01-15 Time 16:44 Rev Time 0.30
Received By tgordon Date 2008-01-15 Time 16:44 Sent To  
Notes
2008-01-15 16:46:54*** PROVISO ***
 1) PER 2004 FBC/M 607.5.3DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING, OR
 MEET THE EXCEPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-02 Cont ID  
Sent By tgordon Date 2008-01-02 Time 10:32 Rev Time 0.25
Received By tgordon Date 2008-01-02 Time 10:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 08:09 Rev Time 0.25
Received By tgordon Date 2007-12-27 Time 08:09 Sent To  
Notes
2007-12-27 08:14:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE ADD A FIRE DAMPER DETAIL TO THE PLANS, SEE
 2004 FBC/M 607.2.
  
 2) SEE OTHER REVIEWER NOTES REGARDING ADDRESS AND
 ENGINEER'S SEAL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-03-11 Cont ID  
Sent By jleech Date 2008-03-11 Time 07:42 Rev Time 0.00
Received By jleech Date 2008-03-11 Time 07:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-25 Cont ID  
Sent By jleech Date 2008-02-25 Time 13:08 Rev Time 0.00
Received By jleech Date 2008-02-25 Time 13:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-24 Cont ID  
Sent By jleech Date 2008-01-24 Time 07:22 Rev Time 0.00
Received By jleech Date 2008-01-24 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By jleech Date 2008-01-24 Time 07:22 Rev Time 0.00
Received By jleech Date 2008-01-03 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-17 Cont ID  
Sent By jleech Date 2007-12-17 Time 08:33 Rev Time 0.00
Received By jleech Date 2007-12-17 Time 08:02 Sent To  
Notes
2007-12-17 08:52:04DENIED;
 1. PLANS ARE NOT SIGNED OR SEALED.
 2. NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN
 REVIEW;
 WHAT IS THE SINK, TO BE INSTALLED, TO BE USED
 FOR. IF IT? IF A BREAK SINK IT MUST COMPLY WITH FBC
 BUILDING CHAPTER 11, SECTIONS 11-4.24.1 THRU
 11-4.24.7.
 SHOW SANITARY AND WATER RISER DIAGRAM TO
 COMPLY WITH CHAPTER 1 ADMINISTRATION CODE SECTIONS
 106.3.5.1(13)AND (3).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-14 Cont ID  
Sent By choops Date 2007-12-14 Time 08:41 Rev Time 0.00
Received By choops Date 2007-12-14 Time 08:40 Sent To  
Notes
2007-12-14 08:41:17*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.