Plan Review Details - Permit 07120285
Plan Review Stops For Permit 07120285
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-18 Cont ID  
Sent By rmcdouga Date 2007-12-18 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2007-12-18 Time 13:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 10:17 Rev Time 0.00
Received By rmcdouga Date 2007-12-18 Time 13:21 Sent To  
Notes
2007-12-13 10:19:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.TWO LAYERS OF GLASPLY 4 DO NOT COMPLY WITH
 FS553.844(5)(A) REQUIREMENTS FOR A SECONDARY WATER
 BARRIER (40ML MINIMUM ASTMD1970 MODIFIED OR APPROVED
 CAP SHEET).PLEASE REVISE.YOU MAY USE ONE OF THE
 MEMBRANES LISTED IN THE PLY SHEET SECTION WHICH IS
 APPROVED FOR USE AS A CAP SHEET.