Plan Review Details - Permit 07120265
Plan Review Stops For Permit 07120265
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-05 Cont ID  
Sent By amorse Date 2008-06-05 Time 17:52 Rev Time 0.00
Received By amorse Date 2008-06-05 Time 17:52 Sent To PC
Notes
2008-06-05 17:56:41 
  
 PASSED
  
 PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN THE
 NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING, THE
 NOTICE IS VOID. PLEASE RERECORD THE NOTICE OF
 COMMENCEMENT PRIOR TO ISSUANCE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-23 Cont ID  
Sent By amorse Date 2008-04-23 Time 18:33 Rev Time 0.00
Received By amorse Date 2008-04-23 Time 18:33 Sent To PC
Notes
2008-04-23 18:36:15 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT FULLY ADDRESSED IN THE
 1ST AND 2ND REVIEWS
  
 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. *******THE DRAWINGS
 SUBMITTED ARE NOT SIGNED AND SEALED BY THE TRUSS
 MANUFACTURERS ENGINEER, PLEASE HAVE ENGINEERED SETS
 THAT ARE REVIEWED AND APPROVED BY YOUR DESIGNER OF
 RECORD AVAILABLE TO INSPECTOR PRIOR TO TRUSS
 ERECTION********
  
 ******PLEASE NOTE THAT THE TRUSS ENGINEERING THAT HAS
 BEEN SUBMITTED IS A LAYOUT SET ONLY, THE REQUIRED SETS
 SHALL HAVE ALL LOADS PRESENT TO MATCH PERMIT DRAWINGS
 AND THE DESIGNED UPLIFTS AT TRUSS BEARING POINTS ETC.
 IF NOT SUBMITTED AT PLAN REVIEW MAY BE PROVIDED TO SITE
 INSPECTOR PRIOR TO TRUSS ERECTION******
  
 10)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG ******NO
 PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS, AND
 CONNECTORS AND STRAPS. IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED******
  
 ********NO APPROVALS WERE SUBMITTED FOR WINDOW #1
 MULLIONS WHERE 2 SINGLE HUNG UNITS ARE
 INSTALLED********
  
 13)PRODUCT APPROVALS WERE SUBMITTEDEASTERN METAL
 SUPPLY,CIRCLE THE METHOD THAT WILL BE USED TO MOUNT
 THE PANELS AND FILL OUT A SHUTTER SCHEDULE WITH KEY
 PLAN FOR THE OPENINGS PER WEST PALM BEACH MEMO (SEE
 ATTACHED) *******INFORMATION AND SCHEDULE WERE INSERTED
 WITH FIRST REVIEW COMMENTS, PRODUCT APPROVALS WERE NOT
 MARKED WITH INSTALLATION METHOD AND NO INSTALLATION
 SCHEDULE HAS BEEN PROVIDED********
  
 *********THE FOLLOWING PROBLEMS REQUIRE ATTENTION ON
 THE SHUTTER SCHEDULE********
 1)THESH24 WINDOWS ARE 37" X 50 5/8" WITH 3 1/2"
 EDGE DISTANCE X 2 = 7" PLUS APPROX 1" CLEARANCE X 2 THE
 SHUTTER SPANS WOULD BE APPROX 60" NOT 46" AS STATED
  
 2) THE #1 WINDOW IS 2 - SH24 WINDOWS THEREFORE THE
 WINDOW OPENING WOULD BE APPROX 6'-2" IN WIDTH NOT 3'-0"
 AS NOTED ON SCHEDULE
  
 3)TOTAL OPENINGS ON THE DRAWING IS 5 BUT SCHEDULE AND
 ENGINEERING WIND LOAD SHEET SPECIFY 6, ALSO 3 WINDOWS
 AND 2 DOORS ON DRAWINGS WHILE SCHEDULE/ENGINEERING HAS
 2 WINDOWS AND 4 DOORS
  
 *******NEW COMMENT******
  
 1)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. ONE SET IS MISSING SEAL,SIGNATURE AND DATE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-01 Cont ID  
Sent By amorse Date 2008-03-01 Time 07:32 Rev Time 0.00
Received By amorse Date 2008-03-01 Time 07:32 Sent To E
Notes
2008-03-01 08:29:44 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST
 REVIEW:
  
  
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $208.69 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. *******THE DRAWINGS
 SUBMITTED ARE NOT SIGNED AND SEALED BY THE TRUSS
 MANUFACTURERS ENGINEER, PLEASE HAVE ENGINEERED SETS
 THAT ARE REVIEWED AND APPROVED BY YOUR DESIGNER OF
 RECORD AVAILABLE TO INSPECTOR PRIOR TO TRUSS
 ERECTION********
  
 7)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. 4" EDGES AND 6' FIELD IN ZONES 1 &
 2 AND 4" EDGES AND FIELD IN ZONE 3 ****** PLEASE NOTE
 THAT SHEETS 2 AND A HAVE CONFLICTING INFORMATION ALSO
 ZONE 3 REQUIRES 4" O/C AT EDGES AND FIELD IN 140 MPH
 WIND ZONE******
  
 10)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG ******NO
 PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS, AND
 CONNECTORS AND STRAPS. IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED******
  
 12)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
 ******NOT SUPPLIED FOR THE PGT DOORS, PGT WINDOWS,
 METAL TECH STORM PANELS,CASTCRETE LINTELS PLESE SEE
 TOP OF NOA'S FOR FLORIDA STATEWIDE PRODUCT APPROVAL
 NUMBERS. SEE ROOFING PRODUT APPROVALS FOR EXAMPLE OF
 THESE SHEETS*********
  
 13)PRODUCT APPROVALS WERE SUBMITTEDEASTERN METAL
 SUPPLY,CIRCLE THE METHOD THAT WILL BE USED TO MOUNT
 THE PANELS AND FILL OUT A SHUTTER SCHEDULE WITH KEY
 PLAN FOR THE OPENINGS PER WEST PALM BEACH MEMO (SEE
 ATTACHED) *******INFORMATION AND SCHEDULE WERE INSERTED
 WITH FIRST REVIEW COMMENTS, PRODUCT APPROVALS WERE NOT
 MARKED WITH INSTALLATION METHOD AND NO INSTALLATION
 SCHEDULE HAS BEEN PROVIDED********
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-05 Cont ID  
Sent By amorse Date 2008-01-05 Time 07:46 Rev Time 0.00
Received By amorse Date 2008-01-05 Time 07:46 Sent To PC
Notes
2008-01-05 08:02:16 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $208.69 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 3)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACK MEASUREMENTS TO THE PROPERTY LINES
  
 4)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
 THIS CAN BE ADDED TO THE LANDSCAPE PLAN REQUIRED BY
 ZONING
  
 5)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC RES.
  
 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 7)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. 4" EDGES AND 6' FIELD IN ZONES 1 &
 2 AND 4" EDGES AND FIELD IN ZONE 3
  
 8)PROVIDE MEAN ROOF HEIGHT AND TOP OF BEAM AT PORCH
 ON SHEET A
  
 9)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 10)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG ******NO
 PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS, AND
 CONNECTORS AND STRAPS. IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED******
  
 11)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 *****THIS COMMENT FOR ANY NEW PRODUCT APPROVALS AND
 SHOP DRAWINGS*****
  
 12)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
 ******NOT SUPPLIED FOR THE PGT DOORS, METAL TECH STORM
 PANELS, CASTCRETE LINTELS
  
 13)2 PRODUCT APPROVALS WERE SUBMITTED FOR THE STORM
 PANELS METALTECH AND EASTERN METAL SUPPLY, WHICH ONE OF
 THESE ARE BEING USED. ALSO CIRCLE THE METHOD THAT WILL
 BE USED TO MOUNT THE PANELS AND FILL OUT A SHUTTER
 SCHEDULE WITH KEY PLAN FOR THE OPENINGS PER WEST PALM
 BEACH MEMO (SEE ATTACHED)
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-07 Cont ID  
Sent By dpalmer Date 2008-07-07 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2008-07-07 Time 10:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-05-19 Cont ID  
Sent By dpalmer Date 2008-05-19 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2008-05-19 Time 14:01 Sent To P
Notes
2008-05-19 14:04:20NOTE ADDED: PER FS 713.13(2), THE RECORDED NOC IS NOW
 VOID AS WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING.
2008-05-19 14:01:59** DENIED4TH TIME***
  
 SEE SOME THE EXACT SAME NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:** THIS IS THE FORTH TIME THIS SAME COMMENT
 HAS BEEN MADE.
 PLEASE *LIST* ON PANEL SCHEDULE THE *REQUIRED ARC FAULT
 PROTECTED CIRCUITS*.THIS WAS REQUESTED ON PREVIOUS
 REVIEWS AND THE PLANS NOW HAVE A NOTE TO SAY AFCI
 PROTECTION IS REQUIRED AND TO SEE THE PANEL SCHEDULE
 FOR THESE CIRCUITS. HOWEVER PLEASE LOOK AT THE PANEL
 SCHEDULE, THERE ARE NO ARC FAULT PROTECTED CIRCUITS
 LISTED. MAY NOT NOTE OR QUOTE THE CODE IN LIEU OF
 REQUIRE CODE ITEMS/DETAILS ETC.
 210.12, 408.4.
 FBC 106.3.5.4
  
 2) NOTE: THIS COMMENT IS ONE AGAIN REPEATED FOR THE
 THIRD REVIEW.
 PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 COORDINATION OF THE MECHANICAL SYSTEMS IN THIS
 DWELLING. IT WAS NOTED PREVIOUSLY THAT THE SIZE AND
 HEAT STRIPS ON MECHANICAL PLANS AND EVEN SHEETS IN THE
 SETS DID NOT MATCH.
 ONCE AGAIN THE SAME COMMENT IS MADE.PLEASE LOOK AT
 THE MECHANICAL PLANS AND PLANS. THESE DO NOT SHOW THE
 SAME KW FOR HEAT STRIPS.
 ELECTRICAL PLANS SPECIFICALLY INDICATE TWO 5KW HEAT
 STRIPS ON LOAD CALCULATIONS YET PANEL SCHEDULE SHOWS
 2-10KW HEAT STRIPS.
 PLEASE SEE AS PREVIOUSLY NOTED CALCULATIONS AND
 COORDINATION OF THESE SYSTEMS SHALL MEET 220.83B.
 WHAT IS THE SIZE OF THE EXISTING ELECTRICAL
 PANEL/SERVICE?
  
 3) NOTE: PLEASE SEE MISSING SMOKE ALARM IN BEDROOM AS
 PREVIOUSLY NOTED. R313, NFPA-72 11.5.1.1, 11.8.3
 THIS WAS REDLINED ON PLANS WHICH MAY HELP TO LOCATE
 MISSING.
  
 4) NOTE: PLEASE SEE PLANS STILL DO NOT CONTAIN ANY
 SIGNATURE OF A DESIGN PROFESSIONAL AS REQUIRED UNDER FS
 471.003, 481.229, 489 ETC
 PLANS SHALL BE DESIGNED BY RESPONSIBLE PERSON. PLANS
 SHALL BE DONE BY LICENSED PROFESSIONAL OR MEETING ONE
 OF THE EXCEPTIONS UNDER THE DESIGN AND RESPONSIBILITY
 OF THOSE PERSONS.
  
 5) NOTE: PLEASE LIST THE DEDICATED CIRCUITS PER
 210.11C3, 210.52D FOR BATHROOM(S).
 MAY NOT LIST *GENERAL LIGHTS AND RECEPTS* OR *GFI*
 CIRCUITS AS THESE DO NOT PROVIDE ANY DESIGNATION.
 PLEASE SEE 408.4 AS ALL CIRCUITS ARE REQUIRED TO BE
 SPECIFIC TO ALL ROOMS AND AREAS IN WHICH THEY FEED.
 FBC 106.3.5.4, 106.1.2
  
 6) NOTE: PLEASE KNOW THERE ARE ITEMS IN EXISTING
 DWELLING WHICH DO NOT MEET CURRENT CODE AND ARE NOT
 PART OF THIS ELECTRICAL REVIEW.
 ** THIS IS ONLY NOTED FOR INFORMATION.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. AS THE DESIGNER OF RECORD HAS CHANGED THE
 FEW AT THIS TIME IS NOT ASSESSED HOWEVER WILL BE
 ASSESSED ON THE FOLLOWING REVIEW TO THE DESIGNER AS
 LISTED.
 THIS FINE WILL BE REQUIRED UNDER THE ABOVE STATUTES AND
 WILL BE $1,615 WHICH WILL BE REQUIRED TO BE PAID BEFORE
 RESUBMITTING PLANS. THIS FEE WILL BE THE RESPONSIBILITY
 OF THE DESIGNER. NOT THE OWNER OR CONTRACTOR.
 ** THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-16 Cont ID  
Sent By dpalmer Date 2008-04-16 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2008-04-16 Time 15:42 Sent To M
Notes
2008-04-16 15:43:06** DENIED3RD REVIEW**
  
 ** PLEASE SEE SEVERAL NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES
 DUE TO NEW ITEMS ONLY NOW BEING SUBMITTED FOR THE FIRST
 TIME FOR REVIEW.
  
 1) NOTE: PLEASE SEE MISSING SMOKE ALARMS INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1,
 11.8.3.
 PLEASE ALSO SEE R313.
 PLEASE SEE THE NEW LAYOUT OF THE EXISTING DWELLING
 STILL SHOWS SD FOR SMOKE DETECTORS WHICH ARE NOT SMOKE
 ALARMS.
 PLEASE SEE DEFINITIONS IN NFPA-72
 PLEASE SEE NEW ADDITION AREA IS STILL MISSING THE
 REQUIRED DEVICES.
  
 2) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED
 CIRCUITS PER 210.12. PLEASE LIST ON PANEL AS PREVIOUSLY
 REQUESTED.
  
 3) NOTE: PLEASE SEE THE WRONG TYPE OF RECESSED FIXTURE
 IS STILL BEING SHOWN ON PLANS.
 PLEASE SEE FBC 13-606.ABC.1.2.4
  
 4) NOTE: PLEASE SEE NEW MECHANICAL PLANS INDICATE 5KW
 HEAT FOR ONE AC SYSTEM YET THE NEW PANEL SCHEDULE ONLY
 NOW SUBMITTED INDICATES TWO 10KW HEAT STRIPS/ AC
 SYSTEMS.
 IN EITHER CASE NEITHER THE MECHANICAL PLANS NOR THE
 ELECTRICAL PLANS COORDINATE.
 M-SHEETS:SHOWS ONE 5KW,
 SHEET -1 SHOWS ONE 10KW,
 SHEET- B SHOWS TWO 10KW.
  
 PLEASE COMPLETE ELECTRICAL AND MECHANICAL COORDINATION
 AND PLEASE SEE 220.83B FOR CORRECTED LOAD
 CALCULATIONS.
  
 5) NOTE: PLEASE SEE ONE SET OF THE NEW PLANS SUBMITTED
 ARE NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF
 RECORD AS SHOWN ON TITLE BLOCKS AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.025.
 PLEASE ALSO SEE THAT SEVERAL OF THE SHEETS WHICH
 CONTAIN ELECTRICAL ARE SHOWN WITH A TITLE BLOCK FOR THE
 ENGINEER HOWEVER NOT ALL SHEETS FOR THE SAME SCOPE OF
 WORK IS DONE BY THE SAME DESIGNER.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B). PLEASE SEE THAT
 THE FEE AS REQUIRED PER STATUTES WILL BE CHARGED IF THE
 SAME CODE COMPLIANT COMMENTS ARE NOT ADDRESSED ON NEXT
 RE-SUBMISSION.
 THERE ARE CODE COMMENTS WHICH ARE NOW BEING REPEATED
 MORE THAN ONCE AND THIS IS BEING GIVEN AS A NOTICE AT
 THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 07:50 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 07:50 Sent To PC
Notes
2008-03-04 07:51:04** DENIED 2ND REVIEW **
  
 ** PLEASE SEE MANY COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SUBMIT A COMPLETE PLANS INCLUDING
 PANEL SCHEDULE SHOWING ALL NEW CIRCUITS ALONG WITH
 EXISTING COMPLYING WITH THE 2005 NEC.
 NO PANEL SCHEDULE WAS SUBMITTED.
 THE LOAD CALCULATIONS CAN NOT BE VERIFIED WITH THE
 CIRCUITING TO BE SHOWN ON PANEL SCHEDULE. ALSO CAN NOT
 VERIFIY WITH MINIMUM REQUIRED CIRCUIT(S) FOR NEW AND
 EXISTING.
 DOES THE DWELLING ALREADY CONTAIN AN A/C SYSTEM?
 PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS.
 PLEASE BE SURE TO LIST ALL OVER CURRENT PROTECTION
 DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC 210.52,
 210.11, 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE 210.12 FOR MISSING REQUIRED ARC
 FAULT FOR ALL OUTLETS. THIS REQUIRES *CIRCUITS* IN
 PANEL TO BE LABELED.
  
 4) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12
 AWG.
 THESE NEED TO BE LISTED ON PANEL SCHEDULE. * MAY NOT
 QUOTE THE CODE IN LIEU OF REQUIRED MINIMUM*
  
 5) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING
 DWELLING AS WELL AND THE NEW ROOMS WHICH ARE SLEEPING
 ROOMS OR ADAPTABLE SLEEPING ROOMS PER FBC R313 AND
 NFPA-72 11.5.1.1.1, 11.8.3.
 THIS WAS NOT DONE. IN FACT THE NOTE ADDED TO PLANS
 MENTIONS *SMOKE DETECTORS* WHICH WOULD BE PART OF A LOW
 VOLTAGE FIRE ALARM PANEL AND SYSTEM. IF THESE ARE GOING
 TO BE SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH ALL
 DEVICES FOR A FIRE ALARM SYSTEM WITH HORN ALARM
 DEVICES. PLEASE SEE NFPA-72 FOR DEFINITIONS FOR A SMOKE
 ALARM AND SMOKE DETECTOR. IF THESE ARE GOING TO BE
 SMOKE ALARMS, PLEASE INDICATE AND COMPLETE PLANS
 ACCORDINLY.
 THE PREVIOUS REVIEW REQUESTED TO SHOW EXISTING SHOWING
 CURRENT CODE COMPLIANCE OR NEW TO BE INSTALLED. PLANS
 SUBMITTED DO NOT SHOW EITHER.
 PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING
 DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE
 CURRENT VERSION OF NFPA-72 11.5.1.1.1 OR NEW TO BE
 INSTALLED.
 *MAY NOT QUOTE CODE IN LIEU OF SHOWING MINIMUM DETAILS
 FOR CODE COMPLIANCE.
  
 6) NOTE: THE A/C UNITS ARE NOW SHOWN HOWEVER PLEASE SEE
 210.70, 210.63 FOR REQUIRED SERVICE OUTLETS IN ATTIC
 WHICH ARE NOT SHOWN ON PLANS.
  
 7) NOTE: PLEASE SEE THE ELECTRICAL SHOWN ON SHEET 2 FOR
 REAR PORCH IS NOT THE SAME AS THE ELECTRICAL SHOWN ON
 A-SHEET.
 PLEASE COORDINATE PLANS. FBC 106.1.2, 106.3.5.4
 ** THIS IS THE SAME COMMENT. RESPONSE MENTIONS
  
 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED
 LIGHTING PER FBC 13-606.ABC.1.2.4
 THE NOTE WHICH WAS ADDED TO PLANS INDICATES A TYPE *IC*
 RATED RECESSED LUMINAIRE WHICH IS NOT THE SECTION OF
 THE CODE GIVEN IN PREVIOUS REVIEW.
 PLEASE ADJUST NOTE AND TYPE OF FIXTURE.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME TO THE DESIGN
 PROFESSIONAL.
  
  
 *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 14:31 Sent To P
Notes
2007-12-23 14:32:09** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS:
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT A COMPLETE PLANS INCLUDING PANEL
 SCHEDULE SHOWING ALL NEW CIRCUITS ALONG WITH EXISTING
 COMPLYING WITH THE 2005 NEC.
 PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS.
 PLEASE BE SURE TO LIST ALL OVER CURRENT PROTECTION
 DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC 408.4,
 240.4, 310.16 ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE 210.12 FOR MISSING REQUIRED ARC
 FAULT FOR ALL OUTLETS.
  
 4) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12
 AWG.
  
 5) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING
 DWELLING AS WELL AND THE NEW ROOMS WHICH ARE SLEEPING
 ROOMS OR ADAPTABLE SLEEPING ROOMS PER FBC R313 AND
 NFPA-72 11.5.1.1.1, 11.8.3
 PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING
 DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE
 CURRENT VERSION OF NFPA-72 11.5.1.1.1 OR NEW TO BE
 INSTALLED.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C
 CONDENSING UNITS PER 440.11.
 PLEASE ALSO SEE THE NEW AHU IS MISSING FROM ELECTRICAL
 PLANS.
 440.11, 110.26
  
 7) NOTE: PLEASE SEE THE ELECTRICAL SHOWN ON SHEET 2 FOR
 REAR PORCH IS NOT THE SAME AS THE ELECTRICAL SHOWN ON
 A-SHEET.
 PLEASE COORDINATE PLANS. FBC 106.1.2, 106.3.5.4
  
 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED
 LIGHTING PER FBC 13-606.ABC.1.2.4
  
  
 *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 12:13 Rev Time 0.00
Received By shill Date 2008-06-26 Time 12:13 Sent To E
Notes
2008-06-26 12:14:18TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 11:12 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 11:12 Sent To Z
Notes
2008-05-13 11:12:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 16:57 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 16:56 Sent To Z
Notes
2008-04-10 16:57:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 16:42 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 16:42 Sent To Z
Notes
2008-02-21 16:42:18TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-01-05 Time   Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 16:23 Sent To  
Notes
2007-12-12 16:23:29TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-17 Cont ID  
Sent By tgordon Date 2008-04-17 Time 08:06 Rev Time 0.30
Received By tgordon Date 2008-04-17 Time 08:06 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By tgordon Date 2008-02-25 Time 13:41 Rev Time 0.45
Received By tgordon Date 2008-02-25 Time 13:41 Sent To P
Notes
2008-02-25 13:52:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) ENERGY CALCULATIONS ARE CALLING FOR A 14 SEER A/C
 SYSTEM, SYSTEM LISTED ON MECHANICAL PLAN IS A 13 SEER
 (SEE ATTACHED ARI CERTIFICATE) THE PLANS CAN NOT CALL
 FOR A LOWER SEER THAN THE ENERGY CAL'S. SEE 2004 FBC
 13-607.1.ABC.3.1.1. PLEASE CORRECT.
  
 3) THE A/C HEAT PUMP SYSTEM LISTED ON THE MECHANICAL
 PLAN HAS BEEN DISCONTINUED IN THE ARI LISTING (SEE
 ATTACHED ARI CERTIFICATE) SEE 2004 FBC
 13-607.1.ABC.3.1.1. PLEASE CORRECT.
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 10:54 Rev Time 0.30
Received By tgordon Date 2007-12-21 Time 14:38 Sent To E
Notes
2007-12-21 15:08:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 13A IS CALLING FOR A HEAT
 PUMP SYSTEM, A/C UNIT LISTED ON MECHANICAL PLAN IS
 STRAIGHT COOL ONLY WITH ELECTRIC HEAT, THE TWO MUST
 COINCIDE, PER 2004 FBC 13-103.1.1, PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS LINE 12A IS CALLING FOR 17,600
 TOTAL COOLING BTU'S, MECHANICAL PLAN A/C SYSTEM IS
 25,000 TOTAL COOLING BTU'S, THE TWO MUST COINCIDE,
 PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS ARE CALLING FOR 11,224
 TOTAL COOLING BTU'S, MECHANICAL PLAN A/C SYSTEM TOTAL
 COOLING BTU'S IS 25,000. THE PLAN CAN ONLY CALL FOR 15%
 MORE THAN THE COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE MECHANICAL PLAN, PLEASE SHOW THE SIZE OF THE
 SUPPLY AIR DUCT FROM THE AIR HANDLER TO THE MIXING BOX
 (SEE YELLOW HIGH LIGHT ON MECH. PLAN).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-29 Cont ID  
Sent By kstevens Date 2008-05-28 Time 16:47 Rev Time 0.00
Received By kstevens Date 2008-05-28 Time 16:47 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-04-17 Cont ID  
Sent By jleech Date 2008-04-17 Time 13:28 Rev Time 0.00
Received By jleech Date 2008-04-17 Time 13:17 Sent To B
Notes
2008-04-17 13:30:08DENIED;
 ONE SET OF PLANS NOT SIGNED OR SEALED

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-28 Cont ID  
Sent By jleech Date 2008-02-28 Time 09:10 Rev Time 0.00
Received By jleech Date 2008-02-28 Time 09:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By jleech Date 2007-12-24 Time 09:15 Rev Time 0.00
Received By jleech Date 2007-12-24 Time 09:14 Sent To B
Notes
2007-12-24 09:23:46DENIED;
 SHOW ON PLANS WHICH ROOMS ARE EXISTING AND WHICH ARE
 ADDITIONS. THE RISER DIAGRAM IS SHOWING TWO LAVATORYS
 AND ONE TOILET, A SHOWER OR TUB SHOULD BE ON RISER
 DIAGRAM. I CANNOT REVIEW THE PLUMBING WITH THE
 INFORMATION GIVEN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2008-05-15 Cont ID  
Sent By choops Date 2008-05-15 Time 10:12 Rev Time 0.00
Received By choops Date 2008-05-15 Time 10:12 Sent To E
Notes
2008-05-15 10:12:53***APPROVED - RESUB #3 (RESTAMPED PLANS)***
  
 NOTE:PROPOSED ADDITION MUST MAINTAIN A MINIMUM
 SEPARATION DISTANCE OF 6 FEET FROM THE EXISTING
 ACCESSORY STRUCTURE.
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By choops Date 2008-04-14 Time 08:18 Rev Time 0.00
Received By choops Date 2008-04-14 Time 08:18 Sent To E
Notes
2008-04-14 08:31:28***APPROVED - RESUB #2***
  
 NOTE:PROPOSED ADDITION MUST MAINTAIN A MINIMUM
 SEPARATION DISTANCE OF 6 FEET FROM THE EXISTING
 ACCESSORY STRUCTURE.
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By choops Date 2008-02-25 Time 10:53 Rev Time 0.00
Received By choops Date 2008-02-25 Time 10:54 Sent To M
Notes
2008-02-25 11:12:31***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 2)LANDSCAPE PLAN SUBMITTED DOES NOT SHOW COMPLIANCE
 WITH CITED SECTIONS OF THE ZLDRS.PLEASE SUBMIT A
 LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION 94-442
 AND 94-445 OF THE ZLDRS.
  
 NOTE:FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHADE, FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR
 EACH 1,200 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE
 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF.SHRUBS MUST BE A MINIMUM 2
 GALLON CONTAINER SIZE, SHADE TREES MUST BE A MINIMUM OF
 8' IN HEIGHT, PLANS SHALL INDICATE SUCH.
  
 NOTE:PALM TREES DO NOT COUNT TOWARDS THE
 SHADE/FLOWERING TREE REQUIREMENT.
  
  
 NOTE:PROPOSED ADDITION MUST MAINTAIN A MINIMUM
 SEPARATION DISTANCE OF 6 FEET FROM THE EXISTING
 ACCESSORY STRUCTURE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-17 Cont ID  
Sent By choops Date 2007-12-17 Time 11:45 Rev Time 0.00
Received By choops Date 2007-12-17 Time 11:45 Sent To E
Notes
2007-12-17 11:52:13***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 3)INDICATE HEIGHT DIMENSIONS OF PROPOSED ADDITION
 FROM GRADE ON THE SHOWN ELEVATIONS.
  
 4)THE SURVEY INDICATES A REAR SETBACK DIMENSION OF
 5.77', THIS DOES NOT APPEAR ACCURATE GIVEN THE
 DIMENSIONS OF THE LOT AND THE DIMENSIONS OF THE
 PROPOSED, PLEASE CLARIFY.IF THIS IS ACCURATE, IT DOES
 NOT MEET THE MINIMUM SETBACK REQUIREMENTS SET FORTH IN
 SECTION 94-72(A)(2) OF THE ZLDRS.MUST MEET MINIMUM
 REAR SETBACK OF 10' (10% OF LOT DEPTH).PLEASE SHOW
 SETBACK DIMENSION FROM PROPOSED TO ALL PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720