Plan Review Details - Permit 07120172
Plan Review Stops For Permit 07120172
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 11:03 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 10:36 Sent To  
Notes
2007-12-07 10:36:59TO "P" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 10:56 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 10:56 Sent To PC
Notes
2007-12-13 11:03:15****************PROVISO****************
 1002.1 FIXTURE TRAPS.
 EACH PLUMBING FIXTURE SHALL BE SEPARATELY TRAPPED BY A
 WATER-SEAL TRAP, EXCEPT AS OTHERWISE PERMITTED BY THIS
 CODE. THE TRAP SHALL BE PLACED AS CLOSE AS POSSIBLE TO
 THE FIXTURE OUTLET. THE VERTICAL DISTANCE FROM THE
 FIXTURE OUTLET TO THE TRAP WEIR SHALL NOT EXCEED 24
 INCHES (610 MM).**TRAPS ARE REQUIRED FOR THE DRINKING
 FOUNTAIN AND LAVATORY.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]