Plan Review Stops For Permit 07120146
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-12 Cont ID  
Sent By mjacobs Date 2008-05-12 Time 09:57 Rev Time 0.00
Received By mjacobs Date 2008-05-12 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mjacobs Date 2007-12-28 Time 16:00 Rev Time 0.00
Received By mjacobs Date 2007-12-28 Time 13:38 Sent To  
Notes
2007-12-28 15:09:37 
 BUILDING PLAN REVIEW
 PERMIT: 07120146
 ADD: 825 FERN STREET
 CONT: MALONE ELECTRICAL SOLUTIONS
 TEL: (561)644-9495
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 12/28/07
  
 1) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 2) FBC 106.1 PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3)A GENERAL CONTRACTOR IS REQUIRED TO BUILD THE WALL
 AND FOUNDATION PAD FOR THE GENERATOR. THE ELECTRICAL
 CONTRACTOR IS NOT QUALIFIED TO DO THIS TYPE OF WORK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-10 Cont ID  
Sent By dpalmer Date 2008-06-10 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2008-06-10 Time 14:06 Sent To  
Notes
2008-06-10 14:09:15SPECS AND PHOTOS SUBMITTED SHOW A SERVICE ENTRANCE
 RATED ATS WITH MANUAL MEANS OF DISCONNECT RATED FOR THE
 LOAD SERVED.
 NO LIVE PARTS APPEAR AS PLEXIGLASS DEADFRONT IS SHOWN
 ON PICS.
 SHOWS MANUAL HANDLE. INSPECTOR TO VERIFY CENTER OFF
 POSITION WHICH WILL KEEP POWER FROM SERVICE UNDER
 NORMAL OR EMERGENCY OPERATIONS.
  
 ** THIS BACK UP GENERATOR IS FOR "OPTIONAL STAND-BY
 POWER" ONLY.
 ALL EM LTS AND EXIT LIGHTS ARE BATTERY BACK AND
 EXISTING PER CONTRACRTOR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 14:01 Sent To  
Notes
2008-05-04 14:04:41** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO THE SERVICE ENTRANCE RATED ATS AND
 DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM ATS.
 PLEASE SEE 230.76,230.79 AND 225.31-225.39 AS THE
 DISCONNECTING MEANS FOR THE SERVICE SHALL MEET230.76,
 230.79.
 THE DISCONNECTING MEANS FOR THE FEEDERS NEEDS TO MEET
 225.31-225.39 UNLESS MEETING THE EXCEPTION IN THE CODE
 IN 702.11.
 PLEASE KNOW ANY GENERATOR BREAKER WHEN USED AS THE
 DISCONNECTING MEANS SHALL NOT BE IN A LOCKED ENCLOSURE
 AND BASED ON THE ATS SPECS SHOWN THERE IS NO DISCONNECT
 READILY ACCESSIBLE FOR FIRE DEPARTMENT OR OTHER
 PERSONNEL.
 PLEASE KNOW ANY INDIVIDUAL MAY NOT BE EXPOSED TO LIVE
 PARTS WHEN OPERATING THE ATS PER 110.27
 PLEASE KNOW THESE TWO ITEMS STILL NEED TO MEET CODE AND
 INSTALLATION FOR SAFE OPERATION FOR ALL OCCUPANTS AS
 WELL AS OTHER PERSONNEL.
 PAGE TWO OF THE SUBMITTAL STATES THE SERVICE DISCONNECT
 TO MECHANICALLY AND ELECTRICAL OPEN BOTH BREAKERS
 HOWEVER NEED TO VERIFY DEAD FRONT AND HOW THIS WILL
 TAKE PLACE.
 PLEASE CONTACT THIS OFFICE. CONTACT COULD NOT BE MADE
 TO CONTRACTOR AS THEIR OFFICE WAS CLOSED AT THE TIME OF
 THIS REVIEW.
  
 2) NOTE: PLEASE KNOW THIS OFFICE STILL NEEDS TO VERIFY
 WHETHER OR NOT BUILDING CONTAINS BATTERY BACK UP LIGHT
 FIXTURES FOR EMERGENCY LIGHTS AND EXIT LIGHTS. THIS
 NEEDS TO BE STATED ON PLANS. IF BUILDING IS GOING TO BE
 OCCUPIED AND IN USE UNDER EMERGENCYPOWER WHICH SEEMS
 TO BE THE INTENT OF THIS UNIT,BATTERY BACK UP
 FIXTURES AS NOTED ABOVE SHALL BE INSTALLED IF NOT
 EXISTING FOR MINIMUM LIFE SAFETY.
 NFPA-10 17.8, 7.9.
  
 PLEASE CONTACT THIS REVIEWER FOR ANY QUESTIONS AND TO
 PROVIDE INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By dpalmer Date 2007-12-12 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2007-12-12 Time 11:42 Sent To  
Notes
2007-12-12 12:33:25** DENIED **
  
 RED CROSS
 NEW GENERATOR INSTALL.
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.(ELECTRICAL PLANS)
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS SUBMITTED ARE
 REQUIRED TO CONTAIN AND PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE PER FS 471.003, 489.
  
 3) NOTE: PLEASE SPECIFY IF THE GENERATOR WILL BE A
 SEPARATELY DERIVED SYSTEM.
 PLEASE SEE NEC 250.30, 250.20 ETC AS A FOUR POLE ATS
 WOULD BE REQUIRED.
  
 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR
 THE PROPOSED ATS.
 PLEASE ALSO SEE NOTES FROM FIRE AND MECHANICAL REVIEW
 FOR SPECS/CUT SHEETS FOR FUEL TANK ALSO.
 90.7, 110.3
 FBC 106.1.2
  
 5) NOTE: PLEASE SUBMIT AN OVER VIEW OF ALL ELECTRICAL
 EQUIPMENT AND LOCATIONS.
 PLEASE KNOW SOME ITEMS FOR REVIEW OF CODE COMPLIANCE
 CAN NOT BE DONE AT THIS TIME.
 110.26,ETC
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE 225.31-225.39 FOR REQUIRED
 DISCONNECTING MEANS FOR FEEDERS AT THE BUILDING. PLEASE
 SEE THERE IS AN EXCEPTION WHICH IS PROVIDED IN 700,701
 AND 702 HOWEVER THE DISCONNECTING MEANS MUST BE *WITHIN
 SIGHT* AND *READILY ACCESSIBLE*.
  
 7) NOTE: PLEASE PROVIDE INFORMATION ON PLANS WHETHER OR
 NOT THIS PROPOSED SYSTEM FEEDS ANY LEGALLY REQUIRED OR
 LIFE SAFETY SYSTEMS PER 700 OR 701.
  
 8) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING OVER
 CURRENT PROTECTION DEVICES, CONDUCTOR SIZES ETC FOR ALL
 BRANCH CIRCUITS TO GENERATOR CONTROL PANEL OR ANY OTHER
 SYSTEMS/DEVICES WHICH ARE BEING INSTALLED.
 FOR EXAMPLE: SHEET ATTACHED TO GENERATOR SPECS
 INDICATES HEATER ETC.
 FBC 106.3.5.1.2, 106.1.2
 NEC 310.16, 240.4, 408.4
  
 9) NOTE: PLEASE PROVIDE FURTHER INFORMATION AND
 CLARIFICATION OF THE *PROTOTYPE CERTIFICATION* SHEET
 SUBMITTED.
 PLEASE VERIFY UNIT IS LISTED AND CERTIFIED BY
 MANUFACTURE BEFORE AND AFTER INSTALL.
 110.3, 90.7
 FBC 106.1.2
  
 10) NOTE: PLEASE KNOW A GENERAL CONTRACTOR WILL BE
 REQUIRED FOR THE BUILDING SCOPE OF WORK AS SHOWN ON
 PLANS.
 THIS COMMENT MAY BE PRESENT IN OTHER REVIEWS.
  
 11) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS SUBMITTED
 ARE NOT SIGNED, OR SEALED BY THE ARCHITECT.
 FS 481.221
  
 12) NOTE: PLEASE LIST OCP AT THE GENERATOR.
 310.16, 240.4, 445.13
 SIZING OF CONDUCTORS CAN NOT BE VERIFIED AT THIS TIME
 PER 445.13
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-01 Cont ID  
Sent By mawillia Date 2008-07-01 Time 15:24 Rev Time 0.00
Received By mawillia Date 2008-07-01 Time 15:14 Sent To E
Notes
2008-07-01 15:23:59*****APPROVED****
  
 ALL COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETA-2 AND A SPEC SHEET WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-27 Cont ID  
Sent By mwennerg Date 2008-05-27 Time 10:37 Rev Time 0.00
Received By mwennerg Date 2008-05-27 Time 10:37 Sent To  
Notes
2008-05-27 10:42:44***DENIED***
  
 NO RESPONSE TO FIRST FIRE REVIEW COMMENTS:
  
 1) OK
  
 2) OK
  
 3) PLEASE INDICATE IF THE NEWLY INSTALLED GENERATOR IS
 FOR EMERGENCY USE OR FOR STANDBY POWER FOR FIRE
 PROTECTION SYSTEMS OR BOTH.
  
 4) IT IS INDICATED THAT THE PROPSED EQUIPMENT WILL BE A
 500 GALLON DIESEL FUEL ENGINE GENERATOR. STORAGE AND
 HANDLING OF FLAMMABLE LIQUIDS OR GASES SHALL BE IN
 ACCORDANCE WITH NFPA 30 AND NFPA 54.
  
  
 NEW COMMENT:
  
 1) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By mawillia Date 2008-01-02 Time 18:15 Rev Time 0.00
Received By mawillia Date 2008-01-02 Time 17:36 Sent To  
Notes
2008-01-02 18:06:27*****DENIED*****
  
  
 1.SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEREOF.
  
 2.SINCE THE SCOPE OF THE WORK IS GREATER THAN
 $5,000.00, AS PER FLORIDA ADMINISTRATIVE CODES, A
 PROFESSIONAL ENGINEER SHALL SIGN HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, ETC TO BE FILED FOR PUBLIC RECORD. THE
 STAMPED ENGINEERED SEAL SHALL HAVE THE WORDING
 "LICENSE" IN LIEU OF "CERTIFICATE".
  
 3.PLEASE INDICATE IF THE NEWLY INSTALLED GENERATOR IS
 FOR EMERGENCY USE OR FOR STANDBY POWER FOR FIRE
 PROTECTION SYSTEMS OR BOTH.
  
 4.IT IS INDICATED THAT THE PROPOSED EQUIPMENT WILL BE
 A 500 GALLON DIESEL FUEL ENGINE GENERATOR.STORAGE AND
 HANDLING OF FLAMMABLE LIQUIDS OR GASES SHALL BE IN
 ACCORDANCE WITH NFPA 30 AND NFPA 54.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT.MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2008-05-16 Cont ID  
Sent By rregueir Date 2008-05-16 Time 16:50 Rev Time 0.00
Received By rregueir Date 2008-05-16 Time 16:45 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By rregueir Date 2008-01-04 Time 09:58 Rev Time 0.00
Received By rregueir Date 2008-01-04 Time 09:36 Sent To PC
Notes
2008-01-04 09:58:37REVIEW #: 1ST
 ACTION: DENIED PENDING (SEE BELOW)
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 37-02
 NFPA30-96
  
 THE PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 PASSED REVIEW PENDING SUBMITTAL OF PLANS WHICH HAVE
 BEEN SIGNED AND SEALED BY THE DESIGNER OF RECORD IN
 ACCORDANCE WITH F.S. 481 AND F.A.C. 61G1-16.003.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-12-26 Cont ID  
Sent By kstevens Date 2007-12-26 Time 08:34 Rev Time 0.00
Received By kstevens Date 2007-12-26 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 11:21 Sent To  
Notes
2008-06-09 11:24:20TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 09:04 Sent To  
Notes
2008-05-01 09:05:06TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-19 Cont ID  
Sent By lmartine Date 2008-01-04 Time 09:22 Rev Time 0.00
Received By lmartine Date 2007-12-07 Time 08:58 Sent To  
Notes
2007-12-07 09:00:11TO "COMM" BD#27

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-01-04 Cont ID  
Sent By rregueir Date 2008-01-04 Time 09:36 Rev Time 0.00
Received By rregueir Date 2008-01-04 Time 08:51 Sent To  
Notes
2008-01-04 09:36:42SEE FUEL REVIEW STOP.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-20 Cont ID  
Sent By mflis Date 2008-06-20 Time 10:47 Rev Time 0.00
Received By mflis Date 2008-06-20 Time 10:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-05-09 Cont ID  
Sent By astelly Date 2008-05-09 Time 15:48 Rev Time 0.00
Received By astelly Date 2008-05-09 Time 15:48 Sent To  
Notes
2008-05-09 16:05:17AMY STELLY
 URBAN DESIGN
 822-1440
  
 MECHANICAL EQUIPMENT CANNOT PROJECT MORE THAN 4' INTO A
 SETBACK (SEC 94-305(4)). THEREFORE, THE GENERATOR MUST
 BE RELOCATED.
  
 THE GENERATOR (MECHANICAL EQUIPMENT) MUST BE SCREENED
 WITH MATERIALS THAT ARE ARCHITECTURALLY COMPATIBLE WITH
 THE PRIMARY STRUCTURE.
  
 PLEASE SUBMIT DRAWINGS WHICH SHOW THE NEWLOCATION FOR
 THE GENERATOR AND THE PROPOSED SCREENING.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By astelly Date 2007-12-21 Time 16:30 Rev Time 0.00
Received By astelly Date 2007-12-21 Time 16:30 Sent To  
Notes
2007-12-21 16:31:30AMY STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE SUBMIT A RECENT SURVEY FOR THE PROPERTY.