Plan Review Details - Permit 07120104
Plan Review Stops For Permit 07120104
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-04 Cont ID  
Sent By shill Date 2008-02-04 Time 10:37 Rev Time 0.00
Received By shill Date 2008-02-04 Time 10:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-18 Cont ID  
Sent By shill Date 2007-12-18 Time 16:02 Rev Time 0.00
Received By shill Date 2007-12-18 Time 16:02 Sent To  
Notes
2007-12-18 16:03:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SUBMIT TWO IDENTICAL COLLATED SETS FOR PERMIT
 ISSUANCE.
  
 2.ONLY ONE SLAB DETAIL WAS SUBMITTED.PLEASE PROVIDE
 TWO.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-30 Cont ID  
Sent By btrobaug Date 2008-01-30 Time 11:34 Rev Time 0.00
Received By btrobaug Date 2008-01-30 Time 11:10 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By btrobaug Date 2007-12-12 Time 12:57 Rev Time 0.00
Received By btrobaug Date 2007-12-12 Time 12:33 Sent To M
Notes
2007-12-12 12:56:55 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE THE PHYSICAL LOCATION OF THE TRANSFER SWITCH
 AND EXISTING PANEL ON THE SITE PLAN. 106.1.3 FBC
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-02-01 Cont ID  
Sent By mperson Date 2008-02-01 Time 10:44 Rev Time 0.00
Received By mperson Date 2008-02-01 Time 10:44 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 09:40 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 09:40 Sent To B
Notes
2007-12-13 10:04:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE
 INDICATE THE FOLLOWING ON THE REQUIRED GAS ISOMETRIC.
 PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT
 APPLICATION REQUIREMENTS FOR PERMIT APPLICATIONS
 ATTACHED TO THESE COMMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **THE SUBMITTED GAS ISOMETRIC IS INCOMPLETE, AND DOES
 NOT INDICATE THE CORRESPONDING LENGTHS FOR THE CUT
 SECTIONS OF PIPE. PLEASE RESUBMIT WITH A COMPLETE RISER
 DIAGRAM OF THE PROPOSED GAS FOR THE GENERATOR FROM
 METER TO GENERATOR WITH THE REQUIRED INFORMATION.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 **THE INCOMPLETE GAS ISOMETRIC RISER DIAGRAM DOES NOT
 INDICATE PIPE SIZES.
  
 3. TYPE OF GAS, (LP OR NATURAL)
 **THE SUBMITTED GAS RISER DOES NOT INDICATE THE GAS
 TYPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THE SUBMITTED GAS RISER DOES NOT INDICATE THE BTU
 LOADS.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **PLEASE REFERENCE COMMENT ONE AND COMPLY.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 **THE SUBMITTED GAS RISER DOES NOT INDICATE THIS.
  
 **IMPROTANT**
 THE ABOVE INFORMATION NEEDS TO BE ON THE GAS ISOMETRIC
 RISER DIAGRAM, PLEASE COMPLY ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 10:15 Rev Time 0.00
Received By shill Date 2008-01-25 Time 10:15 Sent To Z
Notes
2008-01-25 10:15:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-18 Cont ID  
Sent By shill Date 2007-12-18 Time 16:04 Rev Time 0.00
Received By shill Date 2007-12-06 Time 14:26 Sent To  
Notes
2007-12-06 14:27:02TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-01 Cont ID  
Sent By tgordon Date 2008-02-01 Time 11:29 Rev Time 0.20
Received By tgordon Date 2008-02-01 Time 11:29 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By tgordon Date 2007-12-12 Time 13:33 Rev Time 0.20
Received By tgordon Date 2007-12-12 Time 13:33 Sent To G
Notes
2007-12-12 13:35:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By choops Date 2008-01-28 Time 13:17 Rev Time 0.00
Received By choops Date 2008-01-28 Time 13:17 Sent To E
Notes
2008-01-28 13:28:34***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By choops Date 2007-12-10 Time 10:22 Rev Time 0.00
Received By choops Date 2007-12-10 Time 10:22 Sent To E
Notes
2007-12-10 10:29:28***FAILED***
  
  
 1)PLEASE PROVIDE TWO FULL SURVEYS (NOT PARTIAL
 COPIES), SHOWING THE LOCATION OF THE PROPOSED GENERATOR
 WITH SETBACK DIMENSIONS TO ALL PROPERTY LINES.
  
 2)PROPOSED LOCATION DOES NOT MEET MINIMUM SETBACK
 REQUIREMENTS.AS PER SECTION 94-305(B)(4) OF THE
 ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN
 4' INTO A REQUIRED SETBACK.THE REQUIRED FRONT SETBACK
 IS 25', YIELDING A MINIMUM REQUIRED FRONT SETBACK OF
 21' TO THE PROPOSED GENERATOR.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - GEN. BOX