2007-12-12 14:32:39 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE |
| SAME ON PLANS. |
| |
| 2}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| DEVICES AND LIGHTS. 106.3.5 FBC. |
| |
| 3}LIGHTING SYSTEM MUST COMPLY WITH CHAPTER 12 FBC |
| 13-400.0.C.4 RENOVATED BUILDINGS. |
| RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION |
| 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR |
| COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE |
| ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR |
| THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT |
| MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW |
| HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING |
| SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE |
| MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE |
| SYSTEM(S) BEING CHANGED. |
| 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES, |
| GENERAL. |
| THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF |
| INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE |
| BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION |
| HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR |
| LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION |
| 415.2.C.1 OR 415.2.B.1 |
| |
| ALSO SEE 13-415.1.ABC.1.2 SPACE CONTROL. |
| EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. |
| SUBMIT LIGHTING DENSITIES AND FIXTURE SCHEDULES |
| INDICATING COMPLIANCE WITH THIS CHAPTER. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |