Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By btrobaug Date 2007-12-12 Time 14:32 Rev Time 0.00
Received By btrobaug Date 2007-12-12 Time 13:33 Sent To I
Notes
2007-12-12 14:32:39 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.
  
 2}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND LIGHTS. 106.3.5 FBC.
  
 3}LIGHTING SYSTEM MUST COMPLY WITH CHAPTER 12 FBC
 13-400.0.C.4 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1
  
 ALSO SEE 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 SUBMIT LIGHTING DENSITIES AND FIXTURE SCHEDULES
 INDICATING COMPLIANCE WITH THIS CHAPTER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-12 Cont ID  
Sent By btrobaug Date 2007-12-12 Time 14:33 Rev Time 0.00
Received By btrobaug Date 2007-12-06 Time 10:52 Sent To I
Notes
2007-12-06 10:52:10TO "E" BOX