Plan Review Details - Permit 07120073
Plan Review Stops For Permit 07120073
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By jgomez Date 2008-01-22 Time 16:28 Rev Time 0.00
Received By jgomez Date 2008-01-22 Time 16:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-19 Cont ID  
Sent By jgomez Date 2007-12-19 Time 16:56 Rev Time 0.00
Received By jgomez Date 2007-12-19 Time 16:56 Sent To PC
Notes
2007-12-19 16:58:12RESIDENTIAL RENOVATIONS, BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED NOTICE OF COMMENCEMENT. SEC. 713.13 FLORIDA
 STATUTE.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FORGARAGE DOOR AS SHOWN ON PLANS.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- ENGINEER TO SPECIFY TYPE OF DOOR TO BE USED FOR
 GARAGE DOOR LEADING TO THE INTERIOR OF THE HOUSE AS
 REQUIRED BY SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDEINSTALLATION KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.ALSO,
 CLEARLY MARK ON DRAWINGS SPECIFIC MOUNTING CONDITIONS,
 EG: WALL MOUNTED, BUILT OUT, ETC,AND SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED. THIS WILL EXPEDITE REVIEW
 PROCESS AND WILL SHOW COMPLIANCE WITH PROPOSED
 INSTALLATION.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 6- CLARIFY HOW R-19 INSULATION IS GOING TO BE ACHIEVED
 ON THE EXTERIOR CONCRETE BLOCK WALL AND ON THE 2X4
 ADJACENT FRAME WALL?. SEE ENERGY CALCULATIONS.
 NOTE: R-19 BATT INSULATION DOESN'T FIT IN A 2X4 WALL.
  
 7- PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 ENERGY CALCULATIONS FORM. INCLUDING CORRECT NAME OF
 BUILDER.
  
 8- INFORMATION ON PLANS AND ENERGY CALCULATIONS NEED TO
 MATCH.COORDINATEINSULATION VALUE FOR EXTERIOR AND
 ADJACENT WALLS TO MATCH.
  
 9- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS
 CREDIT. THEREFORE, CEILING FANS SHALL BE INSTALLED.
 SPECIFY CEILINGFAN SIZES IN ALL ROOMS AS REQUIRED BY
 TABLE 13-607.1.A.1 OF FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By btrobaug Date 2008-01-22 Time 09:52 Rev Time 0.00
Received By btrobaug Date 2008-01-17 Time 08:45 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By btrobaug Date 2007-12-11 Time 15:59 Rev Time 0.00
Received By btrobaug Date 2007-12-11 Time 12:15 Sent To M
Notes
2007-12-11 14:13:11 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:ALL COMMENTS RELATE TO
 SHEET E-1, UNLESS OTHERWISE NOTED. ALL CODE ARTICLES
 REFERENCED ARE 2005 NEC UNLESS OTHERWISE NOTED.
  
 1} THE RISER DIAGRAM INDICATES A 150 AMP MAIN, THE
 DISCONNECT (NOT SHOWN) INDICATED ON THE FLOOR PLAN IS
 200 AMP. IF THIS IS A METER/ MAIN CHANGE THE RISER TO
 REFLECT A METER/ MAIN.
  
 2} VERIFY THE 4/0 SERVICE CONDUCTORS SHOWN ON THE RISER
 ARE WHAT THE DESIGNER INTENDED WHEN A MINIMUM OF #1 CU
 IS ALL THATS REQUIRED FOR A 150 AMP SERVICE PER
 310.15./0 CAN BE USED BUT WILL REQUIRE A REVISION TO
 CHANGE AFTER PERMITTING.
  
 3} 210.52(B) (3) KITCHEN RECEPTACLE REQUIREMENTS:
 RECEPTACLES INSTALLED IN A KITCHEN TO SERVE COUNTERTOP
 SURFACES SHALL BE SUPPLIED BY NOT FEWER THAN TWO
 SMALL-APPLIANCE BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY RECEPTACLE
 OUTLETS IN THE SAME KITCHEN AND IN OTHER ROOMS
 SPECIFIED IN 210.52(B) (1). ADDITIONAL SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PERMITTED TO SUPPLY RECEPTACLE
 OUTLETS IN THE KITCHEN AND OTHER ROOMS SPECIFIED IN
 210.52(B)(1). NO SMALL-APPLIANCE BRANCH CIRCUIT SHALL
 SERVE MORE THAN ONE KITCHEN.BECAUSE THE COUNTERTOP
 RECEPTACLE OUTLETS GENERALLY SUPPLY MORE OF THE
 PORTABLE COOKING APPLIANCES THAN THE WALL RECEPTACLES
 IN THE KITCHEN AND DINING AREAS, THE COUNTER AREAS MUST
 BE SUPPLIED BY NO FEWER THAN TWO SMALL-APPLIANCE BRANCH
 CIRCUITS. *THE INTENT OF THIS ARTICLE IS NOT MET WITH
 CIRCUIT #22 AS THE ONLY CIRCUIT SERVING THE
 COUNTERTOP.
  
 4} 210.11(C) (2) LAUNDRY BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS
 CIRCUIT SHALL HAVE NO OTHER OUTLETS.* CIRCUIT #13 DOES
 NOT COMPLY, ALSO THE DINING ROOM IS REQUIRED TO BE ON A
 SMALL APPLIANCE CIRCUIT PER 210.11(C)(1). THE LIVING
 ROOM IS NOT.
  
 5} A RECEPTACLE IS REQUIRED IN THE GARAGE PER
 210.52(G), GFCI PROTECTED PER 210.8(A)(2).
  
 6} 210.52(E) REQUIRES A RECEPTACLE IN THE FRONT OUTSIDE
 OF THE RESIDENCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
2007-12-11 13:38:07 
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:00 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:00 Sent To  
Notes
2008-01-11 17:01:01TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-19 Cont ID  
Sent By jgomez Date 2007-12-19 Time 16:58 Rev Time 0.00
Received By jgomez Date 2007-12-06 Time 10:53 Sent To  
Notes
2007-12-06 11:00:29TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By tgordon Date 2008-01-17 Time 15:36 Rev Time 0.30
Received By tgordon Date 2008-01-17 Time 15:36 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By tgordon Date 2007-12-12 Time 08:21 Rev Time 0.30
Received By tgordon Date 2007-12-12 Time 08:21 Sent To P
Notes
2007-12-12 08:34:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE A-1 SHOWS THE WALL INSULATION AS R-4.1,
 ENERGY CALCULATIONS LINE 9A SHOWS THE WALL INSULATION
 AS R-19. THE TWO MUST COINCIDE, PLEASE CORRECT, SEE
 2004 FBC 13-103.1.1.
  
 2) PLEASE HAVE THE PAGES OF THE ENERGY CALCULATIONS IN
 THE CORRECT ORDER, THE PAGE THAT NEEDS TO BE SIGNED BY
 THE BUILDING OFFICIAL IS THE FIRST PAGE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 13:03 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 13:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-23 Cont ID  
Sent By choops Date 2008-01-23 Time 14:21 Rev Time 0.00
Received By choops Date 2008-01-23 Time 14:21 Sent To  
Notes
2008-01-23 14:22:05***APPROVED - RESUB #1 - CAME IN WITH REQUESTED
 LANDSCAPE PLAN***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-14 Cont ID  
Sent By choops Date 2008-01-14 Time 15:03 Rev Time 0.00
Received By choops Date 2008-01-14 Time 15:03 Sent To E
Notes
2008-01-14 15:10:41***FAILED- RESUB #1***
  
  
 1)THE PROVIDED LANDSCAPE PLAN DOES NOT SHOW
 COMPLIANCE WITH SECTION 94-442 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.ACCORDING TO THE CALCULATIONS
 SHOWN ON THE PROVIDED PLAN, SEVEN (7) SHADE OR
 FLOWERING TREES ARE REQUIRED.LANDSCAPE PLAN SHALL
 SHOW COMPLIANCE.
  
 NOTE:SINGLE-FAMILY DWELLING UNITS.FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 PALM TREES DO NOT COUNT AS SHADE TREES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By choops Date 2007-12-07 Time 15:49 Rev Time 0.00
Received By choops Date 2007-12-07 Time 15:49 Sent To E
Notes
2007-12-07 15:51:27***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 2)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 3)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720