Plan Review Details - Permit 07120070
Plan Review Stops For Permit 07120070
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-29 Cont ID  
Sent By lursu Date 2008-01-29 Time 09:23 Rev Time 0.00
Received By lursu Date 2008-01-29 Time 09:23 Sent To  
Notes
2008-01-29 09:24:06NEW SITE ADDRESS ASSIGNED TO BLDG 1 AS 1013 21ST ST ,
 WEST PALM BEACH, FL 33407.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-01-10 Cont ID  
Sent By lursu Date 2008-01-10 Time 09:37 Rev Time 0.00
Received By lursu Date 2008-01-10 Time 09:37 Sent To  
Notes
2008-01-10 09:37:22***FAILED***
  
 SINCE ON THIS PROPERTY FOUR STRUCTURES ARE EXISTING AND
 TWO OF THEM ARE USING A FRACTIONAL SITE ADDRESS ,AN
 ADDRESS CHANGE WILL OCCUR ,THEREFORE TO HAVE THE
 CORRECT SITE ADDRESS ASSIGNED TO EACH OF THE
 STRUCTURES, PLEASE PROVIDE A LOCATION MAP WITH ALL
 EXISTING ADDRESSES TO THIS DEPARTMENT AND AFTER THE
 REVIEWNEW ADDRESSES WILL BE ASSIGNED IN THE CORRECT
 ORDERTO EACH STRUCTURE.
  
 QUESTIONS/COMMENTS
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By jgomez Date 2008-01-28 Time 14:46 Rev Time 0.00
Received By jgomez Date 2008-01-28 Time 14:41 Sent To AD
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-08 Cont ID  
Sent By jgomez Date 2008-01-08 Time 16:35 Rev Time 0.00
Received By jgomez Date 2008-01-08 Time 16:34 Sent To Z
Notes
2008-01-08 16:56:58RESIDENTIAL RENOVATION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THE PERMIT VALUATION NEEDS TO BE UPDATED TO
 INCLUDE ALL SCOPE OF WORK TO BE PERFORMED, INCLUDING
 BUILDING, PLUMBING, ELECTRICAL AND MECHANICAL WORK
 SPECIFIED ON PERMIT APPLICATION AND PLANS.SEC.
 108.3 CITY AMENDMENTS OT FBC 2004. (REPEAT COMMENT).
  
 2-REAR BEDROOMNEEDS TO HAVE A MINIMUM WIDTH OF
 7'-0" AS REQUIRED BY SEC. R304.3 OF 2004 FLORIDA
 RESIDENTIALCODE.PROVIDE DIMENSIONSTO VERIFY
 COMPLIANCE WITH THIS CODE SECTION.
  
 3-PROVIDE ONLY THE INFORMATIONTHAT IS RELEVANT TO
 THE SCOPE OF WORK TO BE PERFORMED.IF NOT WORK IS DONE
 ON EXTERIOR WALLS, THEN EXTERIOR ELEVATIONS AND TYPICAL
 WALL SECTIONS ARE NOT REQUIRED.THIS CONFUSES THE
 SCOPE OF WORK TO BE PERFORMED ANDTOTAL PERMIT
 VALUATION.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004.
  
 4- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.SOME DRAWINGS ARE
 MISSING THE SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004.
  
 5-DESIGNER OF RECORDTO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- ENERGY CALCULATIONS: REVISE ITEM #10(A)AND TABLE
 6C-1.NEED R-30AS THE MINIMUM INSULATION.ALSO,
 REVISE MINIMUM INSULATION FOR DUCT. SEE TABLE 6C-1 AND
 COMMENTS BY MECHANICAL PLAN REVIEWER.
  
 7-ACCORDING TO PERMIT APPLICATION SCOPE OF WORK
 INCLUDES ONLY ONE WINDOW TO BE REPLACED.SEC. 507.3
 EXCEPTION #1 DOESN'T REQUIRE SHUTTERS IFLESS THAN 25%
 OF THEHOUSE GLASS AREA IS REPLACED.
 NOTE:IS HIGHLY RECOMMENDED TO PROTECT ALL OPENINGS,
 BUT IS NOT REQUIRED FOR THE SCOPE OF WORKSTIPULATED
 IN THE PERMIT APPLICATION.
  
 8- PLEASE COORDINATE WITH ZONING REGARDING LOCATION OF
 A/C UNITS AND REQUIRED SETBACKS. CALL CHRIS HOOPS AT
 805-6720 FOR REQUIRED INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-20 Cont ID  
Sent By jgomez Date 2007-12-20 Time 13:25 Rev Time 0.00
Received By jgomez Date 2007-12-20 Time 13:25 Sent To PC
Notes
2007-12-20 14:37:09RESIDENTIAL RENOVATION, BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-A) THERE ARE FOUR INDEPENDENT BUILDINGS ON THIS
 PROPERTY. NEED TO PROVIDE A PERMIT APPLICATION FOR EACH
 DWELLING UNIT. SAME SET OF PLANS MAY BE USED FOR ALL
 FOUR UNITS, BUT SEPARATE PERMIT APPLICATION IS REQUIRED
 FOR EACH BUILDING. (2 SETS OF PLANS REQUIRED FOR EACH
 BUILDING)
  
 B) VALUATION DECLARED ON THE PERMIT APPLICATION IS
 TOO LOW. SECTION 108.3 CITY AMENDMENTS TO FBC 2004.
 VALUATION TO BE UPDATED TO INCLUDEALL SCOPE OF WORK
 TO BE PERFORMEDON EACH BUILDING SEPARATELY AND
 SPECIFIED ON EACH PERMIT APPLICATION.
  
 2- A) INFORMATION ON CONSTRUCTION DOCUMENTS IS NOT
 CLEAR.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004.IT'S
 NOT CLEAR WHAT IS GOING TO BE REPLACED OR NOT.WHAT'S
 EXISTING AND WHAT'S NOT. PLANS NEED TO BE CLEAR TO
 DETERMINE COMPLETE SCOPE OF WORK AND TO VERIFY
 COMPLIANCE WITH AREAS TO BE RENOVATED. INDICATE ON
 PLANS SPECIFIC AREAS OF WORK AND SPECIFIC WORK TO BE
 PERFORMED. THIS WILL ALSO HELP TO DETERMINE TOTAL COST
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 B)IS 4"X4" POST AT ENTRY PORCH GOING TO BE
 REPLACED?PROVIDE COMPLETE INFORMATION, INCLUDING
 FASTENER ON TOP AND BOTTOM AND PROVIDE THE CALCULATED
 UPLIFT LOADS TO VERIFY COMPLIANCE WITH SEC. R301 OF
 2004.
  
 C) SHEET 3 OF 3: AREWINDOW OPENINGS AND EXTERIOR
 WALLS GOING TO BE RE-FRAMED OR THESE ARE EXISTING. IS
 NOT CLEAR WHAT'S NEW AND WHAT'S NOT.IF REFRAMING
 WINDOW OPENINGS , THEN SPECIFY NUMBER OF STUDS REQUIRED
 AT THE ENDS OF EACH OPENING. SPECIFY ALL FASTENERS TO
 VERIFY COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.THIS APPLIES TO TYPICAL WALL SECTION
 ALSO. SPECIFY ALL FASTENERS SHOWING HOW LOADS GET
 TRANSFERRED FROM ROOF TO FOOTING.
  
 D) PROVIDE NAME AND SIGNATURE OF DESIGNER OF RECORD
 AS REQUIRED BY SEC. 106.1.3 CITY AMENDMENTS TO FBC
 2004.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: MAKE SURE ALL UNITS ARE INCLUDED.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE WHERE CONNECTOR IS TO
 EXPEDITE REVIEW PROCESS AND SAVE PAPER.
 NOTE: ONLY 2 SETS OF PRODUCT APPROVALS ARE REQUIRED,
 NOT 4.
  
 5- PERSON RESPONSIBLE FOR THE DESIGN TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- ENERGY CALCULATIONS:
 A) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT AS
 REQUIRED BY SEC. 13-101.2.5.1 FBC 2004.
  
 B) REVISE ITEM #2. THIS ARE SINGLE FAMILY UNITS
 DETACHED, NOT MULTIPLE FAMILY.
  
 C) SPECIFY FLOOR AREA ON ITEM # 8(B). IT WAS LEFT
 BLANK.
  
 D) PREPARER TO SIGN AND DATE BOTTOM OF FORM.
  
 E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 F) REVISE INFORMATION ON TABLE 6C-1.NEED TO
 PROVIDE R-30 INSULATION UNDER ATTIC AREA, NOT R-19
 UNDER SINGLE ASSEMBLY BECAUSE THIS IS NOT SINGLE
 ASSEMBLY. REVISE AS REQUIRED.
  
 G) COMPLETE INFORMATION ON TABLE 6C-2.
  
 7- STORM SHUTTERS:
 A) REVISE INSTALLATION SCHEDULE. REVISE COLUMN FOUR.
 INFORMATION REQUESTED IS SHUTTER MOUNTING CONDITION,
 EG; WALL MOUNTED, BUILT OUT, ETC. SEE PAGES2AND 3
 ON STORM SHUTTER DRAWINGS SUBMITTED.
  
 B) REVISE SHUTTER SPAN. SEE SHEET 1 OF 3 OF STORM
 SHUTTERS TO SEE HOW TO MEASURE THE PANEL SPAN.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER.
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-30 Cont ID  
Sent By btrobaug Date 2008-04-30 Time 13:32 Rev Time 0.00
Received By btrobaug Date 2008-04-30 Time 13:26 Sent To B
Notes
2008-04-30 13:32:20 
  
  
  
 PROVISO
  
 THE PLANS ARE BEGINNING TO LACK CLARITY DUE TO NOTES
 AND INFORMATION BEING COPIED. IF THIS PLAN IS SUBMITTED
 FOR REVISION IN THE FUTURE, SEPARATE THE ELECTRICAL
 PLAN FROM THE ARCHITECTURAL AND REMOVE ALL CLOUDS
 EXCEPT THE ONES PERTAINING TO THAT REVISION. 106.1.3
 FBC AS AMENDED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-25 Cont ID  
Sent By btrobaug Date 2008-01-25 Time 14:13 Rev Time 0.00
Received By btrobaug Date 2008-01-25 Time 13:59 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-03 Cont ID  
Sent By btrobaug Date 2008-01-03 Time 08:25 Rev Time 0.00
Received By btrobaug Date 2008-01-03 Time 07:01 Sent To M
Notes
2008-01-03 08:25:41 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} LOCATE THE ELECTROCAL PANEL ON THE PLAN, IT HAS BEEN
 REMOVED.
  
 2} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES
 "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN
 BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS
 CLEAR,106.1.1 FBC AS AMENDED.
  
 3} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE
 PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS
 MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO
 NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL
 LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED,
 (SEE 1500 VA).
  
 4} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT
 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE
 SAME.
  
 5} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 6} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENER) ON
 THE PLAN. ALSO SHOW COMPLIANCE WITH THE REQUIRED
 DISCONNECT PER 440.14,RECEPTACLE PER 210.63.
  
 7} THE "A/C" PLAN AND THE FLOOR PLAN INDICATE DIFFERENT
 OPENING LOCATIONS FOR THE AIR HANDLER, CORRELATE SAME.
  
 8} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT
 210.52(A)(2), IN THE KITCHEN ON THE A/C WALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By btrobaug Date 2007-12-14 Time 14:48 Rev Time 0.00
Received By btrobaug Date 2007-12-12 Time 10:45 Sent To M
Notes
2007-12-14 14:29:33 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THIS REVIEW IS FOR 1017 21 STREET, SEPERATE PLANS
 AND APPLICATIONS ARE REQUIRED FOR EACH OF THE SEPERATE
 ADDRESSES INDICATING THE SCOPE OF WORK PROPOSED FOR
 EACH BUILDING.106.1.3 FBC AS AMENDED.
  
 2} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. LOCATE ON THE FLOOR PLAN AND ON THE
 RISER. SHOW ALL CONDUCTORS ON THE RISER.
  
 3} } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR
 THE FEEDER TO THE PANEL.
  
 4} THE 6" GROUND ROD ON THE RISER DIAGRAM DOES NOT
 COMPLY WITH 250.53(G) "ROD AND PIPE ELECTRODES THE
 ELECTRODE SHALL BE INSTALLED SUCH THAT AT LEAST 2.44 M
 (8 FT) OF LENGTH IS IN CONTACT WITH THE SOIL.---"
  
 5}INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE
 PLAN IS NEW OR EXISTING SINCE THE SCOPE IS NOT CLEAR ON
 THE APPLICATION.
  
 6} THE CIRCUIT MARKED A/C LISTED AT 8000W " AND 10000W
 DEMAND. CLARIFYPROVIDE A PANEL SCHEDULE PER 408.4.
 INCLUDE OCP AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE
 FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 7} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
  
 8} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), NONE SHOWN ON THE PANEL SCHEDULE.
  
 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 10} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).SEE
 REAR EXIT.
  
 11} 210.52 (E) OUTDOOR OUTLETS FOR A ONE-FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/
 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND
 BACK OF THE DWELLING.
  
 12} PROVIDE AN ELECTRICAL LEGEND. 106.1.3.FBC AS
 AMENDED.
  
 13} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ON PLANS
 AS REQUIRED.NOTE: NFPA-72 REQUIRES ALARMS OR DETECTORS
 WITHIN 20 FEET OF COOKING APPLIANCES BE SILENCING OR
 PHOTOELECTRIC. SEE 11.8.3.5(4)..
  
 14} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 15} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 16} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3.
 FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND
 471 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
2007-12-12 10:46:19 
  
 TO ZONING ./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 10:26 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 10:26 Sent To E
Notes
2008-01-18 10:27:05TO "BTROBAUG" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-31 Cont ID  
Sent By spalmer Date 2007-12-31 Time 12:06 Rev Time 0.00
Received By spalmer Date 2007-12-31 Time 12:06 Sent To E
Notes
2007-12-31 12:06:40TO BILL TROBAUGHS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-20 Cont ID  
Sent By jgomez Date 2007-12-20 Time 14:37 Rev Time 0.00
Received By jgomez Date 2007-12-06 Time 10:10 Sent To  
Notes
2007-12-06 10:12:05TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-01 Cont ID  
Sent By tgordon Date 2008-05-01 Time 14:10 Rev Time 0.20
Received By tgordon Date 2008-05-01 Time 14:10 Sent To  
Notes
2008-05-01 14:10:37REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-01-25 Cont ID  
Sent By tgordon Date 2008-01-25 Time 14:44 Rev Time 0.30
Received By tgordon Date 2008-01-25 Time 14:44 Sent To P
Notes
2008-01-25 14:48:07*** PROVISO ***
 1) PROVIDE RETURN AIR TO ALL REQUIRED SPACES AND BACK
 TO AIR HANDLER, SEE 2004 FBC/R M1602.4. THE RETURN AIR
 MAY NOT COME FROM THE KITCHEN, SEE 2004 FBC/R M1602.2.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-03 Cont ID  
Sent By tgordon Date 2008-01-03 Time 11:07 Rev Time 0.35
Received By tgordon Date 2008-01-03 Time 11:07 Sent To P
Notes
2008-01-03 11:21:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS LINE 10A IS SHOWING R-19 FOR
 UNDER ATTIC, TABLE 6C-1 ON BACK OF ENERGY CALCULATIONS
 STATES MINIMUM INSULATION FOR UNDER ATTIC IS R-30, SEE
 2004 FBC 13-604.1.C.1, PLEASE CORRECT.
  
 2) SHOW ATTIC INSULATION AND R. VALUE ON BUILDING PLAN
 PAGE 2, SEE 2004 FBC 13-604.1.C.1.
  
 3) THE RETURN AIR MAY NOT COME FROM THE KITCHEN, SEE
 2004 FBC/R M1602.2, PLEASE RE-ROUTE
  
 4) PROVIDE RETURN AIR TO BEDROOMS, SEE 2004 FBC/R
 M1602.4.
  
 5) MECHANICAL PLAN SHOWS A 7" AND A12" DUCT GOING TO
 THE MIXING BOX NEAR THE AIR HANDLER, THIS APPEARS TO BE
 AN ERROR (SEE YELLOW HIGH LIGHT ON MECH. PLAN), SEE
 2004 FBC 106.1.1, PLEASE CORRECT.
  
 6) SHOW IN THE A/C EQUIPMENT SCHEDULE THE MODEL NUMBERS
 FOR THE AIR HANDLER AND CONDENSER UNIT, ALSO THE TOTAL
 BTU'S, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-17 Cont ID  
Sent By tgordon Date 2007-12-17 Time 13:58 Rev Time 0.20
Received By tgordon Date 2007-12-17 Time 13:58 Sent To P
Notes
2007-12-17 14:09:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PERMIT APPLICATION STATES WORK TO BE DONE TO INCLUDE
 INSTALLATION OF HVAC, PLEASE SUBMIT MECHANICAL (A/C)
 PLANS FOR REVIEW WITH ALL THE PERTINENT INFORMATION,
 PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER AND OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-01 Cont ID  
Sent By mperson Date 2008-05-01 Time 08:19 Rev Time 0.00
Received By mperson Date 2008-05-01 Time 08:19 Sent To M
Notes
2008-05-01 08:20:41REVISION SHEET 1: "OK" DELETED PLUMBING FIXTURE LAYOUT
 FROM A/C PLAN, PLUMBING FIXTURE LAYOUT PER FLOOR PLAN.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By mperson Date 2008-01-28 Time 08:04 Rev Time 0.00
Received By mperson Date 2008-01-28 Time 08:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-04 Cont ID  
Sent By mperson Date 2008-01-04 Time 08:54 Rev Time 0.00
Received By mperson Date 2008-01-04 Time 08:54 Sent To B
Notes
2008-01-04 08:58:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 1. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY. **SHEETS #2
 AND #3 ARE NOT SIGNED ON BOTH SETS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-19 Cont ID  
Sent By mperson Date 2007-12-19 Time 10:36 Rev Time 0.00
Received By mperson Date 2007-12-19 Time 10:36 Sent To B
Notes
2007-12-19 11:40:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PERMIT APPLICATION STATES RENOVATION AND REPAIR
 PLUMBING, HOWEVER THE SUBMITTED PLANS ON SHEET 1 (BOTH
 SETS 1017, 1017 1/2 AND 1019, 1019 1/2) ARE INDICATING
 THE FOLLOWING "NOTE, PLUMBING EXISTING" WITH A
 ISOMETRIC SANITARY RISER DIAGRAM THAT DOES NOT REFLECT
 THE FLOOR PLAN OR IS CODE COMPLIANT. PLEASE REFERENCE
 THE CORRECTED SANITARY ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. CLEARLY
 INDICATE ON THE RESUBMITTED PLANS WHAT PLUMBING WORK IS
 GOING TO BE DONE. PER *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND *106.1.2 ADDITIONAL DATA.
  
 2. SHEET 1, ISOMETRIC SANITARY RISER DIAGRAM:PER
 FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE
 AND TWO-FAMILY)(9) PLUMBING: PLEASE SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE,
 VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS.**THE
 SUBMITEED RISER DIAGRAM ALSO DOES NOT COMPLY WITH THE
 FOLLOWING AS WELL AS WHAT WAS STATED IN COMMENT 1.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4'
 A.F.F.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-13 Cont ID  
Sent By choops Date 2007-12-13 Time 14:00 Rev Time 0.00
Received By choops Date 2007-12-13 Time 14:00 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved