Plan Review Stops For Permit 07120070 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2008-01-29 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2008-01-29 |
Time |
09:23 |
Sent To |
|
|
Notes |
2008-01-29 09:24:06 | NEW SITE ADDRESS ASSIGNED TO BLDG 1 AS 1013 21ST ST , | | WEST PALM BEACH, FL 33407. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] | | |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2008-01-10 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2008-01-10 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2008-01-10 |
Time |
09:37 |
Sent To |
|
|
Notes |
2008-01-10 09:37:22 | ***FAILED*** | | | | SINCE ON THIS PROPERTY FOUR STRUCTURES ARE EXISTING AND | | TWO OF THEM ARE USING A FRACTIONAL SITE ADDRESS ,AN | | ADDRESS CHANGE WILL OCCUR ,THEREFORE TO HAVE THE | | CORRECT SITE ADDRESS ASSIGNED TO EACH OF THE | | STRUCTURES, PLEASE PROVIDE A LOCATION MAP WITH ALL | | EXISTING ADDRESSES TO THIS DEPARTMENT AND AFTER THE | | REVIEWNEW ADDRESSES WILL BE ASSIGNED IN THE CORRECT | | ORDERTO EACH STRUCTURE. | | | | QUESTIONS/COMMENTS | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-01-28 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-01-28 |
Time |
14:41 |
Sent To |
AD |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-01-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-01-08 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-01-08 |
Time |
16:34 |
Sent To |
Z |
|
Notes |
2008-01-08 16:56:58 | RESIDENTIAL RENOVATION, BUILDING REVIEW SECOND | | CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. THE PERMIT VALUATION NEEDS TO BE UPDATED TO | | INCLUDE ALL SCOPE OF WORK TO BE PERFORMED, INCLUDING | | BUILDING, PLUMBING, ELECTRICAL AND MECHANICAL WORK | | SPECIFIED ON PERMIT APPLICATION AND PLANS.SEC. | | 108.3 CITY AMENDMENTS OT FBC 2004. (REPEAT COMMENT). | | | | 2-REAR BEDROOMNEEDS TO HAVE A MINIMUM WIDTH OF | | 7'-0" AS REQUIRED BY SEC. R304.3 OF 2004 FLORIDA | | RESIDENTIALCODE.PROVIDE DIMENSIONSTO VERIFY | | COMPLIANCE WITH THIS CODE SECTION. | | | | 3-PROVIDE ONLY THE INFORMATIONTHAT IS RELEVANT TO | | THE SCOPE OF WORK TO BE PERFORMED.IF NOT WORK IS DONE | | ON EXTERIOR WALLS, THEN EXTERIOR ELEVATIONS AND TYPICAL | | WALL SECTIONS ARE NOT REQUIRED.THIS CONFUSES THE | | SCOPE OF WORK TO BE PERFORMED ANDTOTAL PERMIT | | VALUATION.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004. | | | | 4- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN.SOME DRAWINGS ARE | | MISSING THE SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN.SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004. | | | | 5-DESIGNER OF RECORDTO REVIEW AND APPROVE IN | | WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. | | 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | 6- ENERGY CALCULATIONS: REVISE ITEM #10(A)AND TABLE | | 6C-1.NEED R-30AS THE MINIMUM INSULATION.ALSO, | | REVISE MINIMUM INSULATION FOR DUCT. SEE TABLE 6C-1 AND | | COMMENTS BY MECHANICAL PLAN REVIEWER. | | | | 7-ACCORDING TO PERMIT APPLICATION SCOPE OF WORK | | INCLUDES ONLY ONE WINDOW TO BE REPLACED.SEC. 507.3 | | EXCEPTION #1 DOESN'T REQUIRE SHUTTERS IFLESS THAN 25% | | OF THEHOUSE GLASS AREA IS REPLACED. | | NOTE:IS HIGHLY RECOMMENDED TO PROTECT ALL OPENINGS, | | BUT IS NOT REQUIRED FOR THE SCOPE OF WORKSTIPULATED | | IN THE PERMIT APPLICATION. | | | | 8- PLEASE COORDINATE WITH ZONING REGARDING LOCATION OF | | A/C UNITS AND REQUIRED SETBACKS. CALL CHRIS HOOPS AT | | 805-6720 FOR REQUIRED INFORMATION. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-12-20 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-12-20 |
Time |
13:25 |
Sent To |
PC |
|
Notes |
2007-12-20 14:37:09 | RESIDENTIAL RENOVATION, BUILDING REVIEW FIRST | | CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1-A) THERE ARE FOUR INDEPENDENT BUILDINGS ON THIS | | PROPERTY. NEED TO PROVIDE A PERMIT APPLICATION FOR EACH | | DWELLING UNIT. SAME SET OF PLANS MAY BE USED FOR ALL | | FOUR UNITS, BUT SEPARATE PERMIT APPLICATION IS REQUIRED | | FOR EACH BUILDING. (2 SETS OF PLANS REQUIRED FOR EACH | | BUILDING) | | | | B) VALUATION DECLARED ON THE PERMIT APPLICATION IS | | TOO LOW. SECTION 108.3 CITY AMENDMENTS TO FBC 2004. | | VALUATION TO BE UPDATED TO INCLUDEALL SCOPE OF WORK | | TO BE PERFORMEDON EACH BUILDING SEPARATELY AND | | SPECIFIED ON EACH PERMIT APPLICATION. | | | | 2- A) INFORMATION ON CONSTRUCTION DOCUMENTS IS NOT | | CLEAR.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004.IT'S | | NOT CLEAR WHAT IS GOING TO BE REPLACED OR NOT.WHAT'S | | EXISTING AND WHAT'S NOT. PLANS NEED TO BE CLEAR TO | | DETERMINE COMPLETE SCOPE OF WORK AND TO VERIFY | | COMPLIANCE WITH AREAS TO BE RENOVATED. INDICATE ON | | PLANS SPECIFIC AREAS OF WORK AND SPECIFIC WORK TO BE | | PERFORMED. THIS WILL ALSO HELP TO DETERMINE TOTAL COST | | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | B)IS 4"X4" POST AT ENTRY PORCH GOING TO BE | | REPLACED?PROVIDE COMPLETE INFORMATION, INCLUDING | | FASTENER ON TOP AND BOTTOM AND PROVIDE THE CALCULATED | | UPLIFT LOADS TO VERIFY COMPLIANCE WITH SEC. R301 OF | | 2004. | | | | C) SHEET 3 OF 3: AREWINDOW OPENINGS AND EXTERIOR | | WALLS GOING TO BE RE-FRAMED OR THESE ARE EXISTING. IS | | NOT CLEAR WHAT'S NEW AND WHAT'S NOT.IF REFRAMING | | WINDOW OPENINGS , THEN SPECIFY NUMBER OF STUDS REQUIRED | | AT THE ENDS OF EACH OPENING. SPECIFY ALL FASTENERS TO | | VERIFY COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA | | RESIDENTIAL CODE.THIS APPLIES TO TYPICAL WALL SECTION | | ALSO. SPECIFY ALL FASTENERS SHOWING HOW LOADS GET | | TRANSFERRED FROM ROOF TO FOOTING. | | | | D) PROVIDE NAME AND SIGNATURE OF DESIGNER OF RECORD | | AS REQUIRED BY SEC. 106.1.3 CITY AMENDMENTS TO FBC | | 2004. | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | SEC. 713.13 FLORIDA STATUTE. | | NOTE: MAKE SURE ALL UNITS ARE INCLUDED. | | | | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9B-72 FOR:ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED | | ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT | | APPROVAL COVER PAGE AND PAGE WHERE CONNECTOR IS TO | | EXPEDITE REVIEW PROCESS AND SAVE PAPER. | | NOTE: ONLY 2 SETS OF PRODUCT APPROVALS ARE REQUIRED, | | NOT 4. | | | | 5- PERSON RESPONSIBLE FOR THE DESIGN TO REVIEW AND | | APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL | | PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 CITY | | AMENDMENTS TO FBC 2004. | | | | 6- ENERGY CALCULATIONS: | | A) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT AS | | REQUIRED BY SEC. 13-101.2.5.1 FBC 2004. | | | | B) REVISE ITEM #2. THIS ARE SINGLE FAMILY UNITS | | DETACHED, NOT MULTIPLE FAMILY. | | | | C) SPECIFY FLOOR AREA ON ITEM # 8(B). IT WAS LEFT | | BLANK. | | | | D) PREPARER TO SIGN AND DATE BOTTOM OF FORM. | | | | E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. | | | | F) REVISE INFORMATION ON TABLE 6C-1.NEED TO | | PROVIDE R-30 INSULATION UNDER ATTIC AREA, NOT R-19 | | UNDER SINGLE ASSEMBLY BECAUSE THIS IS NOT SINGLE | | ASSEMBLY. REVISE AS REQUIRED. | | | | G) COMPLETE INFORMATION ON TABLE 6C-2. | | | | 7- STORM SHUTTERS: | | A) REVISE INSTALLATION SCHEDULE. REVISE COLUMN FOUR. | | INFORMATION REQUESTED IS SHUTTER MOUNTING CONDITION, | | EG; WALL MOUNTED, BUILT OUT, ETC. SEE PAGES2AND 3 | | ON STORM SHUTTER DRAWINGS SUBMITTED. | | | | B) REVISE SHUTTER SPAN. SEE SHEET 1 OF 3 OF STORM | | SHUTTERS TO SEE HOW TO MEASURE THE PANEL SPAN. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER. | | (561)805-6712 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-04-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-04-30 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-04-30 |
Time |
13:26 |
Sent To |
B |
|
Notes |
2008-04-30 13:32:20 | | | | | | | | | PROVISO | | | | THE PLANS ARE BEGINNING TO LACK CLARITY DUE TO NOTES | | AND INFORMATION BEING COPIED. IF THIS PLAN IS SUBMITTED | | FOR REVISION IN THE FUTURE, SEPARATE THE ELECTRICAL | | PLAN FROM THE ARCHITECTURAL AND REMOVE ALL CLOUDS | | EXCEPT THE ONES PERTAINING TO THAT REVISION. 106.1.3 | | FBC AS AMENDED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-01-25 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-01-25 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-01-25 |
Time |
13:59 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-01-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-01-03 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-01-03 |
Time |
07:01 |
Sent To |
M |
|
Notes |
2008-01-03 08:25:41 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} LOCATE THE ELECTROCAL PANEL ON THE PLAN, IT HAS BEEN | | REMOVED. | | | | 2} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES | | "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN | | BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS | | CLEAR,106.1.1 FBC AS AMENDED. | | | | 3} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE | | PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS | | MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO | | NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL | | LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED, | | (SEE 1500 VA). | | | | 4} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT | | 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE | | SAME. | | | | 5} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. | | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND | | 422.31(B) FOR HARDWIRE REQUIREMENTS. | | | | 6} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENER) ON | | THE PLAN. ALSO SHOW COMPLIANCE WITH THE REQUIRED | | DISCONNECT PER 440.14,RECEPTACLE PER 210.63. | | | | 7} THE "A/C" PLAN AND THE FLOOR PLAN INDICATE DIFFERENT | | OPENING LOCATIONS FOR THE AIR HANDLER, CORRELATE SAME. | | | | 8} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT | | 210.52(A)(2), IN THE KITCHEN ON THE A/C WALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-14 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-12 |
Time |
10:45 |
Sent To |
M |
|
Notes |
2007-12-14 14:29:33 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THIS REVIEW IS FOR 1017 21 STREET, SEPERATE PLANS | | AND APPLICATIONS ARE REQUIRED FOR EACH OF THE SEPERATE | | ADDRESSES INDICATING THE SCOPE OF WORK PROPOSED FOR | | EACH BUILDING.106.1.3 FBC AS AMENDED. | | | | 2} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | PER 230.70, 225.32. LOCATE ON THE FLOOR PLAN AND ON THE | | RISER. SHOW ALL CONDUCTORS ON THE RISER. | | | | 3} } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR | | THE FEEDER TO THE PANEL. | | | | 4} THE 6" GROUND ROD ON THE RISER DIAGRAM DOES NOT | | COMPLY WITH 250.53(G) "ROD AND PIPE ELECTRODES THE | | ELECTRODE SHALL BE INSTALLED SUCH THAT AT LEAST 2.44 M | | (8 FT) OF LENGTH IS IN CONTACT WITH THE SOIL.---" | | | | 5}INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE | | PLAN IS NEW OR EXISTING SINCE THE SCOPE IS NOT CLEAR ON | | THE APPLICATION. | | | | 6} THE CIRCUIT MARKED A/C LISTED AT 8000W " AND 10000W | | DEMAND. CLARIFYPROVIDE A PANEL SCHEDULE PER 408.4. | | INCLUDE OCP AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE | | FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS." | | | | 7} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, | | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. | | | | 8} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | PER 210.11(C) (3), NONE SHOWN ON THE PANEL SCHEDULE. | | | | 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14,RECEPTACLE PER 210.63. | | | | 10} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).SEE | | REAR EXIT. | | | | 11} 210.52 (E) OUTDOOR OUTLETS FOR A ONE-FAMILY | | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS | | AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET | | ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ | | 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND | | BACK OF THE DWELLING. | | | | 12} PROVIDE AN ELECTRICAL LEGEND. 106.1.3.FBC AS | | AMENDED. | | | | 13} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN | | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ON PLANS | | AS REQUIRED.NOTE: NFPA-72 REQUIRES ALARMS OR DETECTORS | | WITHIN 20 FEET OF COOKING APPLIANCES BE SILENCING OR | | PHOTOELECTRIC. SEE 11.8.3.5(4).. | | | | 14} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | 15} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | DESIGNED. | | | | 16} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN | | MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. | | FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND | | 471 FS, RESPECTIVELY. | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | APPLY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | 2007-12-12 10:46:19 | | | | | TO ZONING ./WRT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-01-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-18 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-18 |
Time |
10:26 |
Sent To |
E |
|
Notes |
2008-01-18 10:27:05 | TO "BTROBAUG" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-12-31 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-12-31 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-12-31 |
Time |
12:06 |
Sent To |
E |
|
Notes |
2007-12-31 12:06:40 | TO BILL TROBAUGHS DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-12-20 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-12-06 |
Time |
10:10 |
Sent To |
|
|
Notes |
2007-12-06 10:12:05 | TO "SFR" "E" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-01 |
Time |
14:10 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-05-01 |
Time |
14:10 |
Sent To |
|
|
Notes |
2008-05-01 14:10:37 | REVISION TO MECH. PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-01-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-25 |
Time |
14:44 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-01-25 |
Time |
14:44 |
Sent To |
P |
|
Notes |
2008-01-25 14:48:07 | *** PROVISO *** | | 1) PROVIDE RETURN AIR TO ALL REQUIRED SPACES AND BACK | | TO AIR HANDLER, SEE 2004 FBC/R M1602.4. THE RETURN AIR | | MAY NOT COME FROM THE KITCHEN, SEE 2004 FBC/R M1602.2. | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-01-03 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-03 |
Time |
11:07 |
Rev Time |
0.35 |
Received By |
tgordon |
Date |
2008-01-03 |
Time |
11:07 |
Sent To |
P |
|
Notes |
2008-01-03 11:21:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | | | 1) ENERGY CALCULATIONS LINE 10A IS SHOWING R-19 FOR | | UNDER ATTIC, TABLE 6C-1 ON BACK OF ENERGY CALCULATIONS | | STATES MINIMUM INSULATION FOR UNDER ATTIC IS R-30, SEE | | 2004 FBC 13-604.1.C.1, PLEASE CORRECT. | | | | 2) SHOW ATTIC INSULATION AND R. VALUE ON BUILDING PLAN | | PAGE 2, SEE 2004 FBC 13-604.1.C.1. | | | | 3) THE RETURN AIR MAY NOT COME FROM THE KITCHEN, SEE | | 2004 FBC/R M1602.2, PLEASE RE-ROUTE | | | | 4) PROVIDE RETURN AIR TO BEDROOMS, SEE 2004 FBC/R | | M1602.4. | | | | 5) MECHANICAL PLAN SHOWS A 7" AND A12" DUCT GOING TO | | THE MIXING BOX NEAR THE AIR HANDLER, THIS APPEARS TO BE | | AN ERROR (SEE YELLOW HIGH LIGHT ON MECH. PLAN), SEE | | 2004 FBC 106.1.1, PLEASE CORRECT. | | | | 6) SHOW IN THE A/C EQUIPMENT SCHEDULE THE MODEL NUMBERS | | FOR THE AIR HANDLER AND CONDENSER UNIT, ALSO THE TOTAL | | BTU'S, SEE 2004 WPB AMEND. 106.3.5.4 (10). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-12-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-12-17 |
Time |
13:58 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-12-17 |
Time |
13:58 |
Sent To |
P |
|
Notes |
2007-12-17 14:09:01 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PERMIT APPLICATION STATES WORK TO BE DONE TO INCLUDE | | INSTALLATION OF HVAC, PLEASE SUBMIT MECHANICAL (A/C) | | PLANS FOR REVIEW WITH ALL THE PERTINENT INFORMATION, | | PER 2004 WPB AMEND. 106.3.5.4 (10). | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE | | PREPARER AND OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-05-01 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-05-01 |
Time |
08:19 |
Sent To |
M |
|
Notes |
2008-05-01 08:20:41 | REVISION SHEET 1: "OK" DELETED PLUMBING FIXTURE LAYOUT | | FROM A/C PLAN, PLUMBING FIXTURE LAYOUT PER FLOOR PLAN. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-01-28 |
Time |
08:04 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-01-28 |
Time |
08:04 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-01-04 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-01-04 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-01-04 |
Time |
08:54 |
Sent To |
B |
|
Notes |
2008-01-04 08:58:12 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | PLUMBING PLAN REVIEW: | | DENIED 2ND TIME: | | | | 1. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | SECTION *106.3.4.3. | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR | | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER | | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER | | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. **SHEETS #2 | | AND #3 ARE NOT SIGNED ON BOTH SETS. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-19 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-19 |
Time |
10:36 |
Sent To |
B |
|
Notes |
2007-12-19 11:40:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | PLUMBING PLAN REVIEW: | | DENIED: | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. PERMIT APPLICATION STATES RENOVATION AND REPAIR | | PLUMBING, HOWEVER THE SUBMITTED PLANS ON SHEET 1 (BOTH | | SETS 1017, 1017 1/2 AND 1019, 1019 1/2) ARE INDICATING | | THE FOLLOWING "NOTE, PLUMBING EXISTING" WITH A | | ISOMETRIC SANITARY RISER DIAGRAM THAT DOES NOT REFLECT | | THE FLOOR PLAN OR IS CODE COMPLIANT. PLEASE REFERENCE | | THE CORRECTED SANITARY ISOMETRIC RISER DIAGRAM THAT | | REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. CLEARLY | | INDICATE ON THE RESUBMITTED PLANS WHAT PLUMBING WORK IS | | GOING TO BE DONE. PER *106.1.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS AND *106.1.2 ADDITIONAL DATA. | | | | 2. SHEET 1, ISOMETRIC SANITARY RISER DIAGRAM:PER | | FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE | | AND TWO-FAMILY)(9) PLUMBING: PLEASE SUBMIT A PLUMBING | | SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, | | VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS.**THE | | SUBMITEED RISER DIAGRAM ALSO DOES NOT COMPLY WITH THE | | FOLLOWING AS WELL AS WHAT WAS STATED IN COMMENT 1. | | | | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND | | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | (51MM) IN DIAMETER. THE AUTOMATIC | | CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR DRAINAGE | | STACK A MINIMUM OF 3 INCHES (76MM) IN | | DIAMETER. | | (B) 708.3.4 BASE OF STACK. A CLEANOUT | | SHALL BE PROVIDED AT THE BASE OF EACH | | WASTE OR SOIL STACK | | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL | | BE THE SAME NOMINAL SIZE AS THE PIPE | | THEY SERVE UP TO 4 INCHES (102MM) | | **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". | | (D) 708.9 ACCESS. ACCESS SHALL BE | | PROVIDED TO ALL CLEANOUTS. | | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4' | | A.F.F. | | | | 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | NAME, AND ALSO DATE DRAWING. | | PLEASE DO THIS PRIOR TO RESUBMITTING. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | EXAMINER FOR REFERENCE FOR THE | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-12-13 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-12-13 |
Time |
14:00 |
Sent To |
E |
|
Notes |
|
|