Plan Review Details - Permit 07120067
Plan Review Stops For Permit 07120067
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-03 Cont ID  
Sent By jgomez Date 2008-12-03 Time 13:54 Rev Time 0.00
Received By jgomez Date 2008-12-03 Time 13:54 Sent To P
Notes
2008-12-03 13:55:40ROOF DRAINAGE/SCUPPERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-20 Cont ID  
Sent By jgomez Date 2008-11-20 Time 10:28 Rev Time 0.00
Received By jgomez Date 2008-11-20 Time 10:28 Sent To  
Notes
2008-11-20 10:29:20ARCHITECT'S LETTER/ SUBMITTAL TO ADDRESS PROVISO ITEMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-25 Cont ID  
Sent By jgomez Date 2008-02-25 Time 16:00 Rev Time 0.00
Received By jgomez Date 2008-02-25 Time 16:00 Sent To PC
Notes
2008-02-25 16:01:45ARCHITECT BROUGHT CORRECTED ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By jgomez Date 2008-02-21 Time 16:59 Rev Time 0.00
Received By jgomez Date 2008-02-21 Time 16:59 Sent To PC
Notes
2008-02-21 17:01:29BUILDING REVIEW PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS.
 2- ROOF PITCH OF 3:12REQUIRES 2 LAYERS OF
 UNDERLAYMENT AS REQUIRED BY SEC. R905.3.3.1 2004
 FLORIDA RESIDENTIAL CODE.REVISE SPECIFICATIONS ON
 DRAWINGS AS REQUIRED.
 3- ROOF PLAN SHOWS ONLY ONE ROOF DRAIN AND SCUPPER FOR
 ENTIRE ROOF. CLARIFY IF THEY ARETHE ONLY DRAINS FOR
 THIS ROOF. AND PROVIDE DRAINAGE CALCULATIONS FOR
 PLUMBING PLAN REVIEWER PRIOR TO ROOF DRAINS
 INSTALLATION TO AVOID DELAYS OR CONFLICTS.
 4- REVISE WALL SECTIONS IN SHEET A-4PROVIDING
 COMPLETE SPECIFICATIONS FOR ANCHORS/FASTENERSSHOWING
 TRANSITION OF LOADS FROM ROOF TO FOOTINGAS REQUIRED
 BY SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 5- REVISE ROOF SHEATHING NAIL SPACING FOR ROOF ZONE 3.
 SEE SEC. R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-19 Cont ID  
Sent By jgomez Date 2007-12-19 Time 10:13 Rev Time 0.00
Received By jgomez Date 2007-12-19 Time 10:13 Sent To PC
Notes
2007-12-19 10:48:39RESIDENTIAL ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT DESCRIBING
 SCOPE OF WORK TO BE PERFORMED AS REQUIRED BY SEC.
 713.13 FLORIDA STATUTE.THERE IS AN EXISTING NOTICE OF
 COMMENCEMENT BUT IT WAS FOR INTERIOR DEMOLITION ONLY.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2.2 AND 13-101.2.3 OF FBC 2004.
 PLEASE, MAKE SUREREVISED FORM IS USED,CALCULATIONS
 ARE FILLED COMPLETELY AND OWNER/AGENT SIGNS AND DATE
 FORMS AS REQUIRED TOAVOID UNNECESSARY DELAYS.
  
 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPTIF FEES
 ARE DUE.
  
 4- PROPOSED ADDITIONEAST SIDE WALL NEEDSTO COMPLY
 WITH SEC. R302.1 AND SEC. R302.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.WALL NEEDS TO BE FIRE RATED AND
 OPENINGS ARE NOT ALLOWED.CLEARLY SHOW ON SITE PLAN
 DISTANCE OF EXISTING ADJACENT STRUCTURES TO VERIFY
 COMPLIANCE WITH THISCODE SECTION.
  
 5- IF PLANS/ELEVATIONS ARE CHANGED, THEN PLEASE BRING
 THEM TO THE HISTORIC DEPARTMENT ON THE FIFTH FLOOR FOR
 APPROVAL RE-STAMP PRIOR TO SUBMITTAL TO THIS OFFICE TO
 EXPEDITE REVIEW PROCESS.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) EXTERIOR SWING DOORS. FLORIDA PRODUCT APPROVAL
 FL1893 SUBMITTED ISFOR CODE VERSION 2001.NEED TO
 PROVIDECURRENT PRODUCT APPROVAL FOR CODE VERSION 2004
 AND MAKE SURE NOA IS NOT EXPIRED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING CONNECTOR ONLY TO SAVE
 PAPER AND EXPEDITE REVIEW PROCESS. NO NEED TO SUBMIT
 COMPLETE REPORT SHOWING ALL STRAPS.
  
 7- PROFESSIONAL DESIGNEROF RECORD NEEDS TO PROVIDE
 ORIGINAL SIGNATURE (AND PROVIDE DATE)ON THE PRODUCT
 APPROVALSREVIEW STAMP.RUBBER SIGNATURE IS NOT
 ALLOWED BY CHAPTER 481 OF FLORIDA STATUTE.
  
 8- FLAT ROOF PRODUCT APPROVAL:SELECTED ASSEMBLY ON
 PAGE 18 OF 21 OF NOA 03-0501.05 SUBMITTED IS MISSING
 THE ENHANCED NAILING CALCULATIONS FOR PERIMETER AND
 CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7.
 THERE IS A NOTE SAYING "SEE ENHANCED NAILING", BUT THIS
 INFORMATION WAS NOT PROVIDED. PLEASE, PROVIDE THIS
 INFORMATION TO VERIFY COMPLIANCE WITH UPLIFT PRESSURES
 AS REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 9- OWES $0.74 FOR NEW ADDITIONS RADON FEES.
  
 10- UPDATE GENERAL SPECIFICATIONS NOTE #1 ON SHEET A-1.
 NEED TO REFERENCE2007 REVISIONS, NOT 2006. REVISE AS
 REQUIRED.
  
 11-SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SEC.
 R905.3.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 12-ROOF DRAINAGE ON FLAT ROOF NEEDS TO COMPLY WITH
 SEC. R903.4.1 OF 2004 FLORIDA RESIDENTIALCODE.
 PROVIDE COMPLETE SPECIFICATIONS AND DETAILS SHOWING
 COMPLIANCE.
  
 13- SHEET A-4:
 A) SECTION AT UTILITY ROOM. CLARIFY WHY USING (2)2X4
 HEADERS LAID FLAT ABOVE THE DOORINSTEAD OF BEING
 VERTICAL .THIS IS NOT AN STANDARD CONSTRUCTION
 TECHNIQUE.SPECIFY WHICH TABLE WAS USED TO USE HEADER
 IN THIS WAY. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) PROVIDE COMPLETE SPECIFICATIONS SHOWINGHOW ARE
 THE WALLS CONNECTED TO THE FOOTING TO TRANSMIT ALL THE
 LOADS TO THE FOOTING.SECTIONS SHOWN ON THIS DRAWINGS
 ARE MISSING THIS INFORMATION.ALSO, MISSINGCOMPLETE
 SPECIFICATION FOR NEW PARAPET WALL CONNECTIONS SEC.
 R601.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE TYPE OF NAIL TO BE USED ON ROOF SHEATHING.
 NEED TO SPECIFY MIN.8D RING SHANK NAILS AS REQUIRED
 BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By btrobaug Date 2007-12-11 Time 09:45 Rev Time 0.00
Received By btrobaug Date 2007-12-11 Time 07:50 Sent To M
Notes
2007-12-11 09:45:06 
  
 ELECTRICAL PERMIT #07030918 WAS ISSUED FOR THIS
 ADDRESS, BUT THE FLOOR PLAN DOES NOT MATCH THE PLANS
 SUBMITTED WITH THIS APPLICATION, AND A REVISED
 ELECTRICAL PLAN WILL BE REQUIRED./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 08:27 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 08:27 Sent To P
Notes
2008-12-09 08:27:51TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-26 Cont ID  
Sent By adarroug Date 2008-11-26 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-11-26 Time 09:46 Sent To P
Notes
2008-11-26 09:46:49TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 09:41 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 09:41 Sent To Z
Notes
2008-02-19 09:42:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-19 Cont ID  
Sent By jgomez Date 2007-12-19 Time 10:48 Rev Time 0.00
Received By jgomez Date 2007-12-06 Time 10:33 Sent To  
Notes
2007-12-06 10:34:19TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By tgordon Date 2007-12-11 Time 16:47 Rev Time 0.20
Received By tgordon Date 2007-12-11 Time 16:47 Sent To P
Notes
2007-12-11 16:47:48NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-12-10 Cont ID  
Sent By kstevens Date 2008-12-10 Time 10:21 Rev Time 0.00
Received By kstevens Date 2008-12-10 Time 10:21 Sent To  
Notes
2008-12-10 10:21:38REVISION OK -- SANITARY RISER DIAGRAM ON 8-1/2" X 11"
 SHEET.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-12-03 Cont ID  
Sent By kstevens Date 2008-12-03 Time 13:48 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 13:48 Sent To B
Notes
2008-12-03 13:49:10REVISION OK -- SHTS A-2 & A-3 ROOF SCUPPERS & EMERGENCY
 ROOF SCUPPER

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-19 Cont ID  
Sent By mperson Date 2008-02-19 Time 16:12 Rev Time 0.00
Received By mperson Date 2008-02-19 Time 16:12 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 07:59 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 07:59 Sent To B
Notes
2007-12-13 09:13:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN (KITCHEN SINK IS A DOUBLE BOWL
 NOT A SINGLE BOWL) AND SUBMIT MANUFACTURER'S
 SPECIFICATION SHEET OF THE INDICATED FITIING FOR THE
 WATER CLOSET, TUB, AND VENT (REFERENCE RED LINE
 CORRECTIONS OF THIS AREA). PER *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND *106.1.2, ADDITIONAL DATA.
  
 2. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 CHAPTER 1, SECTION *106.3.5.4 RESIDENTIAL (ONE
 AND TWO-FAMILY) (9) PLUMBING, PLEASE SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE,
 VENTS, TRAPS AND SIZES WITH CLEANOUT LOCATIONS. **THE
 SUBMITTED DRAWING DOES NOT HAVE ALL WASTE AND TRAPS
 SIZED.
  
 3. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM: THE NEW
 WASHER AND DOUBLE KITCHEN SINK MUST DRAIN DOWNSTREAM OF
 THE WET VENTED BATHROOM. PER *909.1 WET VENT
 PERMITTED.
  
 4. SHEET A-1 SANITARYISOMETRIC RISER DIAGRAM: THE
 WASHER IS SIZED WRONG, PLEASE CORRECT PER THE
 FOLLOWING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4'
 A.F.F.
  
 5. SHEET A-1 SANITARY ISOMETRIC RISER DIAGRAM:PER
 *708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 6. SHEET A-1 PLUMBING NOTE #1, SLOPE OF THE HORIZONTAL
 DRAINAGE PIPE SHALL BE PER THE FOLLOWING.
 704.1 SLOPE OF HORIZONTAL DRAINAGE PIPING. HORIZONTAL
 DRAINAGE PIPING SHALL BE INSTALLED IN UNIFORM ALIGNMENT
 AT UNIFORM SLOPES. THE MINIMUM SLOPE OF A HORIZONTAL
 DRAINAGE PIPE SHALL BE IN ACCORDANCE WITH TABLE 704.1
 .
 TABLE 704.1
 SLOPE OF HORIZONTAL DRAINAGE PIPE
  
 SIZE--MINIMUM SLOPE
 (INCHES)--(INCH PER FOOT)
 2-1/2 OR LESS--1/4
 3 TO 6--1/8
 8 OR LARGER--1/16
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 13:51 Rev Time 0.00
Received By choops Date 2008-02-19 Time 13:51 Sent To E
Notes
2008-02-19 13:54:57***APPROVED - RESUB #1***
  
 APPROVAL PER AJV
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By choops Date 2007-12-07 Time 14:25 Rev Time 0.00
Received By choops Date 2007-12-07 Time 14:25 Sent To E
Notes
2007-12-07 14:31:45***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 2)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 ADDITIONS TO ALL PROPERTY LINES.NOTE:ALL NEW
 CONSTRUCTION MUST MEET CURRENT SETBACK REQUIREMENTS AS
 FOUND IN SECTION 94-94 OF THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS:
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A.FRONT: 25 FEET;
 B.CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
 C.REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER
 IS LESS;
 D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4)INDICATE HEIGHT DIMENSIONS ON ELEVATIONS (SHEET
 A-2) FROM GRADE.
  
 5)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 6)THE PROPOSED ADDITION ON THE SW SIDE OF THE HOME
 DOES NOT MATCH BETWEEN THE SITE PLAN AND SHEETS
 A-2/A-3, PLEASE CLARIFY.PROVIDE A DEMOLITION PLAN
 SHOWING WHAT EXISTING IS TO BE REMOVED/DEMOLISHED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720