Plan Review Details - Permit 07120063
Plan Review Stops For Permit 07120063
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-09 Cont ID  
Sent By shill Date 2008-01-09 Time 15:07 Rev Time 0.00
Received By shill Date 2008-01-09 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-02 Cont ID  
Sent By shill Date 2008-01-02 Time 17:10 Rev Time 0.00
Received By shill Date 2008-01-02 Time 17:10 Sent To  
Notes
2008-01-02 17:14:12****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE INSTALLATION SCHEDULE IS NOT COMPLETE.IT
 SHOULD LIST EVERY OPENING AND CORRELATE WITH THE FLOOR
 PLAN.
  
 2.THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH THE ANCHOR SCHEDULE ON THE PRODUCT
 APPROVAL; IN THIS CASE, 1 THROUGH 5.
  
 3.SPECIFY SUBSTRATE, TOP AND BOTTOM, FOR EACH
 OPENING."BOTH" WAS WRITTEN.AS THE 12" SPACING IS
 NOT COMPLIANT FOR ALL CONNECTIONS, ALL SUBSTRATES,
 SPECIFY WHICH CONNECTION TYPE YOU ARE USING AND WHICH
 SUBSTRATE APPLIES TO THAT OPENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By shill Date 2007-12-11 Time 07:53 Rev Time 0.00
Received By shill Date 2007-12-11 Time 07:53 Sent To  
Notes
2007-12-11 08:57:11****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE FBC*106.3.5, MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.NO PLANS WERE SUBMITTED.PROVIDE A FLOOR
 PLAN SHOWING LOCATION AND SCOPE OF WORK FOR ALL WORK
 REQUIRING A PERMIT (INSULATION, DRYWALL, STRUCTURAL
 REPAIR, DOORS, WINDOWS, SHUTTERS, CEILINGS, DEMOLITION
 OF PATIO, PATIO TRUSS REPAIR, ETC.), SITE PLAN.WORK
 WHICH IS NOT REQUIRED TO BE PERMITTED DOES NOT NEED TO
 BE INCLUDED IN THE PLANS (SUCH AS PAINT OF EXISTING
 ELEMENTS, BASEBOARD, ETC.).
  
 2.PROVIDE A STRUCTURAL DETAIL FOR THE FRONT DOOR
 SHELTER.THIS SHOULD INCLUDE ELEVATIONS, A SECTION,
 AND BE SHOWN ON THE FLOOR PLAN AND SITE PLAN.ZONING
 APPROVAL REQUIRED.
  
 3.PROVIDE A WALL SECTION SHOWING STRAPPING
 INFORMATION.THE FLOOR PLAN IS TO SHOW LOCATION OF
 STRAPPING.PROVIDE PRODUCT APPROVAL FOR THE
 CONNECTORS.
  
 4.FOR THE SHUTTERS, COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE.PROVIDE A KEY PLAN SHOWING
 SHUTTER LOCATIONS WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE.
  
 5.DECLARE GOVERNING CODE INCLUDING 2007 AMENDMENTS
 AND WIND DESIGN CRITERIA FBC1603.1.4.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 09:23 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 09:23 Sent To B
Notes
2008-01-04 09:23:53TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By shill Date 2007-12-11 Time 09:00 Rev Time 0.00
Received By shill Date 2007-12-04 Time 15:31 Sent To  
Notes
2007-12-04 15:32:13TO "MISC" BOX#1