Plan Review Details - Permit 07120041
Plan Review Stops For Permit 07120041
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-21 Cont ID  
Sent By mwennerg Date 2008-02-21 Time 12:59 Rev Time 0.00
Received By mwennerg Date 2008-02-21 Time 12:59 Sent To  
Notes
2008-02-21 13:00:26INSTALLATION OF (2) TAMPER SWITCHES ON PIV ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By mwennerg Date 2007-12-11 Time 13:29 Rev Time 0.00
Received By mwennerg Date 2007-12-11 Time 13:29 Sent To  
Notes
2007-12-11 13:45:05***DENIED***
  
 1) PERMIT APPLICATION INDICATES INSTALLATION OF (1)
 FLOW SWITCH AND (1) TAMPER SWITCH. THE DRAWINGS
 ILLUSTRATE (2) TAMPER SWITCHES. PLEASE CORRELATE
 INFORMATION.
  
 2) PLEASE CLARIFY IF THE CONTROL PANEL IS EXISTING.
 MANUFACTURER SPEC SHEETS SHOULD INCLUDE THE EQUIPMENT
 THAT WILL BE INSTALLED.
  
 3) PLEASE INDICATE THE TOTAL OCCUPANCY LOAD FOR THE
 BUILDING.
  
 4) NEW SYSTEMS THAT SUPERVISE AN AUTOMATIC FIRE
 SPRINKLER SYSTEM ARE REQUIRED TO BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 09:43 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 09:43 Sent To FIRE
Notes
2008-02-06 09:43:31TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By mwennerg Date 2007-12-11 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2007-12-04 Time 11:09 Sent To  
Notes
2007-12-04 11:09:54TO "F" BOX