Plan Review Details - Permit 07120008
Plan Review Stops For Permit 07120008
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 12:28 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 12:28 Sent To M
Notes
2007-12-28 12:28:57TO TOM GORDONS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-10 Cont ID  
Sent By tgordon Date 2007-12-10 Time 16:12 Rev Time 0.00
Received By tgordon Date 2007-12-10 Time 15:07 Sent To  
Notes
2007-12-10 15:07:53TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-28 Cont ID  
Sent By tgordon Date 2007-12-28 Time 13:59 Rev Time 0.30
Received By tgordon Date 2007-12-28 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-10 Cont ID  
Sent By tgordon Date 2007-12-10 Time 16:01 Rev Time 0.30
Received By tgordon Date 2007-12-10 Time 16:01 Sent To  
Notes
2007-12-10 16:12:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE PERMIT APPLICATION STATES THE 5 TON UNITS ARE
 10.2 SEER. SEE 2004 FBC 13-407.1.ABC.3.2.1 THE MINIMUM
 SEER IS 13, PLEASE CORRECT.
  
 2) MODEL NUMBERS FOR EQUIPMENT COULD NOT BE FOUND ON
 THE ARI WEB SITE, PLEASE SUBMIT THE ARI CERTIFICATE,
 SEE 2004 FBC 13-407.1.ABC.3.1.1.
  
 3) THE ENGINEERING FOR THE WALL STANDS NEED TO BE
 SIGNED AND SEALED BY THE ENGINEER NOT COPIES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]