Plan Review Details - Permit 07110754
Plan Review Stops For Permit 07110754
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-14 Cont ID  
Sent By lursu Date 2008-01-14 Time 14:44 Rev Time 0.00
Received By lursu Date 2008-01-14 Time 12:06 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By lursu Date 2007-12-07 Time 11:14 Rev Time 0.00
Received By lursu Date 2007-12-07 Time 11:14 Sent To  
Notes
2007-12-07 11:14:46***FAILED***
  
 SPECIFY THE UNIT NUMBER IN WHICH THE WORK IS BEING
 DONE.
  
 ALSO KNOW THATIT WILL BE THE DEVELOPER RESPONSIBILITY
 TO ASSIGN UNIT (DESIGNATORS) ADDRESSES TO ALL UNITS
 INSIDE THE STRUCTURE .
  
 EXAMPLES TO ASSIGN UNIT NUMBERS ARE:
  
 GROUND/FIRST FLOOR: UNIT NUMBERS FROM 100 TO
 199, (100 MAIN ST. # 101, INDICATES THE UNIT ON THE
 FIRST FLOOR)
 SECOND FLOOR: UNIT NUMBERS FROM 200 TO 299,
 (100 MAIN ST. # 201, INDICATES THE FIRST UNIT ON THE
 SECOND FLOOR)
 ?
 ?N? FLOOR: UNIT NUMBERS FROM ?N?00 TO ?
 N?99, (100 MAIN ST. # ?N?01, INDICATES THE FIRST UNIT
 ON THE ?N? FLOOR,).
  
 QUESTIONS/COMMENTS ,PLEASE CALL:
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 16:44 Rev Time 0.55
Received By jwitmer Date 2008-05-12 Time 16:44 Sent To PC
Notes
2008-05-12 16:44:56REVISION# 1 PARTITION SCHEDULE REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-10 Cont ID  
Sent By shill Date 2008-04-10 Time 15:37 Rev Time 0.00
Received By shill Date 2008-04-10 Time 15:37 Sent To  
Notes
2008-04-11 11:46:21RECEIVED UPDATED AFFIDAVITS, REMOVED PRINTING HOLD
2008-04-10 16:34:37****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE PRIVATE PROVIDER ELECTRICAL PLANS COMPLIANCE
 AFFIDAVIT REFERS TO SHEETS DATED 12/15/07; PLAN SHEETS
 ARE DATED 2/15/08.PLEASE SUBMIT AN AFFIDAVIT WITH THE
 CORRECT PLAN REVISION DATE.
  
 2.SHEET A2.6.1 DATED 3/10/08 WAS NOT INCLUDED IN THE
 MOST RECENT PRIVATE PROVIDER BUILDING PLANS COMPLIANCE
 AFFIDAVIT.PLEASE SUBMIT.
  
 PLEASE NOTE THAT THE PLANS WILL BE PROCESSED FOR
 PERMITTING BUT THE TWO AFFIDAVITS ARE REQUIRED BEFORE
 THE PERMIT WILL BE ISSUED AND PLANS RELEASED.AS
 DISCUSSED WITH ARCHITECT, IT IS POSSIBLE THAT, IF THE
 PLANS HAVE BEEN PROCESSED, THIS CAN BE DONE
 SIMULTANEOUSLY.
  
 3.PLEASE PROVIDE A NOTICE OF COMMENCEMENT, FS713.13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 07:12 Rev Time 0.00
Received By shill Date 2008-04-01 Time 07:12 Sent To  
Notes
2008-04-01 07:17:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 COMMENT FROM PREVIOUS AUDIT:
  
 4.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).HOW DOES THIS RENOVATION AFFECT THE FIRE
 SPRINKLER LAYOUT?
  
 2ND AUDIT, NOT ADDRESSED.PROVIDE, AT A MINIMUM, A
 SPRINKLER HEAD LAYOUT AND SPECIFICATION.CALCULATIONS
 AND SHOP DRAWINGS MAY BE SUBMITTED AT THE TIME OF FIRE
 SPRINKLER PERMIT.
  
 3RD AUDIT, ARCHITECT'S RESPONSE THAT THIS HAS BEEN
 REQUESTED IS NOTED, THANK YOU.PLEASE NOTE THAT THIS
 IS A STATUTORY REQUIREMENT AND CANNOT BE PROVISO'D.
 THEREFORE, THIS PERMIT WILL REMAIN IN FAILED STATUS
 UNTIL THE FIRE SPRINKLER PERMIT HAS BEEN REVIEWED AND
 IS READY TO BE ISSUED.PLEASE ADVISE WHEN THIS IS
 ISSUED AND THE STATUS WILL BE CHANGED TO "P".
  
 ***PLEASE NOTE THAT FIRE SPRINKLER PLANS REQUIRE
 PRIVATE PROVIDER REVIEW AS IT IS A PART OF THE BUILDING
 REVIEW***
  
 NEW COMMENTS:
  
 6.SHEET A7.1.2 HAS BEEN VOIDED PRIOR TO BUILDING
 REVIEW AS IT IS LACKING THE COMPLETE ADDRESS AND IS NOT
 INCLUDED IN THE INDEX SHEET.THIS SHEET IS REQUIRED AS
 IT INCLUDES BUILDING DETAILS.
  
 7.PLEASE CLARIFY; LEVEL 6 IS REFERENCED ON SHEET
 A0.0.1 AND OTHER PLACES; SUITE NUMBER IS 700.ARE YOU
 USING A BRITISH STORY NUMBERING CONVENTION?
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 10:33 Rev Time 0.00
Received By shill Date 2008-01-17 Time 10:33 Sent To  
Notes
2008-01-17 10:34:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.ADDRESSED.
  
 2.SEE MECHANICAL COMMENTS, ITEM 12, REGARDING TENANT
 BUILDOUT (COMMENT ALSO MADE BY OTHER REVIEWERS).THE
 RESPONSE LETTER STATES THAT THE LETTER WILL BE
 DEVELOPED BY CONTRACTOR AND DEVELOPER.THIS MUST BE
 DONE PRIOR TO PERMIT ISSUANCE; PLEASE PROVIDE.
  
 3.ADDRESSED.
  
 4.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).HOW DOES THIS RENOVATION AFFECT THE FIRE
 SPRINKLER LAYOUT?
  
 2ND REVIEW, NOT ADDRESSED.PROVIDE, AT A MINIMUM, A
 SPRINKLER HEAD LAYOUT AND SPECIFICATION.CALCULATIONS
 AND SHOP DRAWINGS MAY BE SUBMITTED AT THE TIME OF FIRE
 SPRINKLER PERMIT.
  
 5.ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By shill Date 2007-12-07 Time 10:59 Rev Time 0.00
Received By shill Date 2007-12-07 Time 10:59 Sent To  
Notes
2007-12-07 11:03:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE ELECTRIC COMMENTS REGARDING ADDRESSING.THIS
 ISSUE SHOULD BE RESOLVED PRIOR TO PERMIT ISSUANCE.
  
 2.SEE MECHANICAL COMMENTS, ITEM 12, REGARDING TENANT
 BUILDOUT.THE DOR ON THIS JOB IS TO PROVIDE SHOP
 DRAWING REVIEW STAMP (MICHAEL O ROSSIN IS ARCHITECT OF
 RECORD, ROBERT J. MCNAMARE, PE IS STRUCTURAL ENGINEER
 OF RECORD).
  
 3.APPLICABLE CODES SHOULD INCLUDE 2007 AMENDMENTS
 EFFECTIVE 7/1/07, SHEET A01.1. WWW.FLORIDABUILDING.ORG
  
 4.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).HOW DOES THIS RENOVATION AFFECT THE FIRE
 SPRINKLER LAYOUT?
  
 5.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR B619 AT
 RECEPTION, FBC FIGURE 11-25.
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-08-11 Cont ID  
Sent By dpalmer Date 2008-08-11 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2008-08-11 Time 13:56 Sent To PC
Notes
2008-08-11 13:57:04E7.62

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-08-06 Cont ID  
Sent By dpalmer Date 2008-08-06 Time 13:37 Rev Time 0.00
Received By dpalmer Date 2008-08-06 Time 13:37 Sent To PC
Notes
2008-08-06 13:38:10 
 **TEMP DENIED**
  
  
 1) NOTE:PLANS NEEDS STAMPS AND SIGNATURE FROM BASE
 BUILDING DESIGNER OF RECORD. PLANS WILL NOT COUNT AS A
 FEE FOR REVISION AS LONG AS THE SAME PLANS ARE BROUGHT
 BACK.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-07-14 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 12:07 Sent To PC
Notes
2008-07-14 12:08:50REV #9 FOR 7.62 FAILED.
  
 1) NOTE: ALL PRIVATE PROVIDER PROJECTS MUST BE
 SUBMITTED TO THE PROVIDER, REVIEWED, STAMPED AND
 PROVIDE AFFIDAVIT PER FS 553.791
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-14 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 12:06 Sent To PC
Notes
2008-07-14 12:06:58REV #9 OK, FOR 2.64ONLY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-05-30 Cont ID  
Sent By dpalmer Date 2008-05-30 Time 13:37 Rev Time 0.00
Received By dpalmer Date 2008-05-30 Time 13:37 Sent To PC
Notes
2008-05-30 13:38:38REV E- 2.64, 6.61, 7.62

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-31 Cont ID  
Sent By dpalmer Date 2008-03-31 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2008-03-31 Time 20:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By dpalmer Date 2008-01-11 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2008-01-11 Time 16:39 Sent To  
Notes
2008-01-11 16:39:18*** DENIED REVIEW ***
  
 1) NOTE: PLEASE SEE THE ADDRESSING IS STILL IN NEED OF
 ADDRESSING. PLEASE SEE THE COMMENTS FROM ADDRESSING
 REVIEWER.
 PLANS SHOWS SUITE #700, YET PERMIT APPLICATION AND
 COMPUTER SHOWS 6TH FLR.
 PLEASE SEE SOME SHEETS INDICATE SUITE #100?
  
 2) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE STAMPED
 AND SIGNED BY THE RESPONSIBLE ENGINEER ON BASE BUILDING
 AS THIS BUILDING IS STILL UNDER CONSTRUCTION AND HAS
 RECEIVED A CERTIFICATE OF OCCUPANCY.
 PLANS DO CONTAIN A (SHOP DRAWING REVIEW STAMP) HOWEVER
 NOT SIGNED BY THE ELECTRICAL DESIGNER OF RECORD.
  
 **
 ONCE THE ADDRESS IS DETERMINED AND PLANS ARE SIGNED,
 ELECTRICAL PLANS ARE OK FOR STAMPING.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By dpalmer Date 2007-12-05 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2007-12-04 Time 16:23 Sent To  
Notes
2007-12-05 11:05:40** DENIED**
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND
 SUPPORTING DOCUMENTS HAVE BEEN ROUTED TO THE ADDRESSING
 REVIEWER.
 THE PERMIT APPLICATION AS APPLIED INDICATES THE 6TH
 FLOOR HOWEVER THIS TENANT DOES NOT TAKE THE ENTIRE
 FLOOR AND WILL REQUIRE A SUITE/UNIT #.
 PLEASE KNOW ONCE THIS HAS BEEN DETERMINED THE TITLE
 BLOCKS ARE TO BE REVISED INDICATING THIS ADJUSTMENT.
 FBC 106.1.2, 106.3.5.1.2, 106.5.3 ETC
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE BE SURE ALL ROOM AND AREA DESIGNATIONS
 ARE LISTED ON PLANS FOR SCOPE OF WORK BEING DONE UNDER
 THIS PERMIT APPLICATION.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR ALL
 ELECTRICAL AS SHOWN.
 FOR EXAMPLE:
 PLEASE SEE E2.6.4 WHICH SHOWS NO CIRCUITING ETC. THIS
 ROOM BY THE LABEL ON THE ARCHITECTURAL PLANS SHEET
 A2.6.1 SHOWS THIS AS THE CATERING ROOM, YET THESE PLANS
 INDICATE NEW RECEPTACLES AND OUTLETS WITH NO
 CIRCUITING.?
 PLEASE COMPLETE.
 NEC 408.4, 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE GO OVER ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE FOR EXAMPLE:
 PLEASE SEE ROOM 622 AND 623 WHICH INDICATES CIRCUITS
 *P26-34,36 AND 38* YET THE PLANS FOR ROOM 623 DO NOT
 CONTAIN ANY 38?
 PLEASE SEE THIS SAME ROOM #623 WHICH SHOWS CIRCUIT 37,
 YET CIRCUIT 37 ON PANEL SCHEDULE SHOWS ROOM 673. COULD
 NOT LOCATE ANY ROOM 673.
 PLEASE SEE FOR EXAMPLE SAME AREA WHICH SHOWS CIRCUITS
 *P-26, 35, 37, AND 39* YET THE PANEL SCHEDULE SHOWS A
 *SPARE* FOR #39.
 ** THESE ARE A FEW EXAMPLES FOR COORDINATION.
 NEC 408.4
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION
  
 4) NOTE: PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES
 WITH THAT OF THE LOADS SET FORTH IN THE NEC FOR
 RECEPTACLES AT 180VA PER YOKE.
 PLEASE SEE NEC 220 .14/220.44.
 PLEASE SEE FOR EXAMPLE CIRCUIT #6 ON PLANS WHICH SHOW 7
 RECEPTACLES/YOKES YET THE VA SHOWN ON PANEL SCHEDULE IS
 LOWER.
 PLEASE SEE FOR EXAMPLE CIRCUIT #14 AND #29 ETC. PLEASE
 CORRELATE ALL LOADS WHICH ARE NOT KNOWN DEDICATED LOADS
 FOR EQUIPMENT ETC ON PANEL SCHEDULES.
  
 5) NOTE: PLEASE SEE THE ZONE DESIGNATIONS ON E6.6.2 AND
 2.6.2 ARE NOT LABELED THE SAME. PLEASE CLARIFY AND
 COORDINATE.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE TOTALS SHOWN ON LCP6 AND LMC DO
 NOT APPEAR TO CORRELATE WITH THE LIGHTING WATTAGE LOADS
 ON LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE ADJUST AND CORRELATE.
 13-415.2
 FBC 106.1.2
  
 7) NOTE: PLEASE CLARIFY OPEN OFFICE AREAS NOTED AS
 CLOSED OFFICE ON LP CALCULATIONS. THE ALLOWANCES ARE
 THE SAME AND THIS COULD BE REDLINED.
 SEE ROOM/AREA 619 FOR EXAMPLE.
  
 8) NOTE: PLEASE SEE THE OCTAGONAL NOTE #2 ON PLANS NEXT
 TO THE J-BOX SYMBOL AT DOORS WHICH BY THE NOTE MENTIONS
 THESEARE TABLE TOP MONUMENTS FOR PHONE ETC.
 THIS NOTE DOES NOT SEEM TO BE PART OF THE DOOR AREA
 J-BOX.
 PLEASE COORDINATE AND ADJUST. WHAT ARE THESE J-BOXES
 FOR? IF PART OF ACCESS CONTROL PLEASE BE SURE TO SEE
 NFPA-101 CHAPTER 7 FOR ACCESS/EGRESS CONTROLS. THIS IS
 NOT PART OF THIS PERMIT AT THIS TIME.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-10 Cont ID  
Sent By mawillia Date 2008-04-10 Time 14:12 Rev Time 0.00
Received By mawillia Date 2008-04-10 Time 13:17 Sent To B1
Notes
2008-04-10 13:46:55*****APPROVED*****
  
  
 PLAN SHEETS A2.6.3, A2.6.4, A.2.6.5, A7.6.1, E2.6.1,
 E2.6.2, E2.6.4, AND FP1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-01 Cont ID  
Sent By mawillia Date 2008-04-01 Time 17:07 Rev Time 0.00
Received By mawillia Date 2008-04-01 Time 16:50 Sent To  
Notes
2008-04-01 17:06:36*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN
 BUILDING PLANS EXAMINER COMMENT #4 (IN REFERENCE TO
 FIRE SPRINKLER LAYOUT) HAS BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By mwennerg Date 2008-01-22 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2008-01-22 Time 14:06 Sent To  
Notes
2008-01-22 14:08:30IT APPEARS THAT PLANS ARE IN COMPLIANCE. PLEASE RESPOND
 TO OTHER REVIEW COMMENTS AND PLANS WILL BE STAMPED WHEN
 RETURNED WITH CORRECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By mwennerg Date 2007-12-14 Time 11:22 Rev Time 0.00
Received By mwennerg Date 2007-12-14 Time 11:22 Sent To  
Notes
2007-12-14 11:28:06***DENIED***
  
 1) THE SUITE IDENTIFICATION TO BE ADDED TO TITLE BLOCK.
 THE CHARACTERS LOCATED NEAR THE FRONT ENTRANCE OF THE
 BUSINESS TO BE MINIMUM OF (3") AND CONTRASTING TO
 BACKGROUND PER CITY OF WEST PAKM BEACH REQUIREMENTS.
  
 2) FIRE EXTINGUISHERS ARE REQUIRED TO BE MINIMUM
 2A-10B,C RATED.
  
 3) FIRE RATED DOORS TO BE ILLUSTRATED IN TERMS OF
 HOURS.
  
 4) PLEASE CLARIFY OCCUPANT LOAD FOR SPACE PER NFPA 101,
 SEC. 7.3.1.2.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PALN REVIEW
 FIRE PREVENTIO (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-08-13 Cont ID  
Sent By adarroug Date 2008-08-13 Time 15:44 Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 15:44 Sent To M
Notes
2008-08-13 15:44:36TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 13:45 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 13:45 Sent To E
Notes
2008-07-23 13:45:38TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 10:47 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 10:47 Sent To E
Notes
2008-06-19 10:48:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:37 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:37 Sent To E
Notes
2008-06-17 16:37:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 11:56 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 11:56 Sent To E
Notes
2008-06-03 11:56:42TO "DPALMER" DESK/ 2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:14 Sent To  
Notes
2008-05-08 16:16:21TO "COMM" BD#1--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:07 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:07 Sent To B
Notes
2008-05-08 16:07:27TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 10:22 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 10:22 Sent To B
Notes
2008-04-08 10:22:40TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-09 Cont ID  
Sent By adarroug Date 2008-01-09 Time 10:24 Rev Time 0.00
Received By adarroug Date 2008-01-09 Time 10:24 Sent To  
Notes
2008-01-09 10:28:55TO "COMM" BD#26--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-14 Cont ID  
Sent By mwennerg Date 2007-12-14 Time 11:29 Rev Time 0.00
Received By mwennerg Date 2007-12-03 Time 11:01 Sent To  
Notes
2007-12-03 11:01:14TO "COMM" BD#53--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-08-28 Cont ID  
Sent By rregueir Date 2008-08-28 Time 08:38 Rev Time 0.00
Received By rregueir Date 2008-08-28 Time 08:28 Sent To PC
Notes
2008-08-28 08:37:58REVISED H2.6.1 REV 8

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-23 Cont ID  
Sent By rregueir Date 2008-05-23 Time 16:54 Rev Time 0.00
Received By rregueir Date 2008-05-23 Time 16:43 Sent To  
Notes
2008-05-23 16:54:22REVISED H2.6.1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-02 Cont ID  
Sent By rregueir Date 2008-03-29 Time 10:25 Rev Time 0.00
Received By rregueir Date 2008-03-27 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-16 Cont ID  
Sent By rregueir Date 2008-01-16 Time 18:14 Rev Time 0.00
Received By rregueir Date 2008-01-16 Time 17:09 Sent To  
Notes
2008-01-16 18:14:32REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. BALANCED RETURN PROVISIONS HAVE BEEN PROVIDED FOR
 ALL ROOMS LISTED IN THE PREVIOUS COMMENT EXCEPT FOR
 ROOM 610. NO CHANGES OR TRANSFER DUCT COULD BE FOUND ON
 PLANS. PLEASE CORRECT AND RESUBMIT. FBC, M 601.4.
  
 2. IT IS UNCLEAR HOW THREE TRANSFER DUCTS IN ROOM 621
 COMMUNICATING WITH ROOM 624 IS TO PROVIDE BALANCED
 RETURN FOR THE QUANTITIES OF AIR BEING SUPPLIED TO THAT
 HALF OF THE FLOOR SPACE. PLEASE CLARIFY. BALANCED
 RETURN IS REQUIRED IN ACCORDANCE WITH FBC, M 601.4.
  
 3. OK
  
 4. OK
  
 5. THIS ITEM HAS NOT BEEN ADDRESSED. THE BUILDING
 OFFICIAL HAS ESTABLISHED A POLICY BY WHICH TENANT
 IMPROVEMENT PERMITS COULD BE ISSUED FOR SHELL BUILDINGS
 PRIOR TO COMPLETION OF THE SHELL. THAT POLICY REQUIRES
 A LETTER OF UNDERSTANDING (SEE PREVIOUS MECHANICAL
 REVIEW COMMENT #5). THIS LETTER WAS NOT INCLUDED WITH
 THIS SUBMITTAL. ALSO, A SHOP DRAWING REVIEW STAMP AND
 ORIGINAL SIGNATURE OF THE BASE BUILDING DESIGNER OF
 RECORD ON THE TENANT PLANS IS REQUIRED PRIOR TO PERMIT
 ISSUANCE. THESE PLANS HAVE BEEN INITIALED BY SOMEONE
 OTHER THAN DANIEL A. CAMPIA, THE MECHANICAL ENGINEER OF
 RECORD. PLEASE INCLUDE THESE REQUIREMENTS WITH
 RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By rregueir Date 2007-12-03 Time 16:59 Rev Time 0.00
Received By rregueir Date 2007-12-03 Time 11:44 Sent To  
Notes
2007-12-03 16:59:29REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. H2.6.1: ROOM 601, 606, 607, 610, 620, 638
 ARCHITECTURAL FLOOR PLAN SHOWS WALLS FOR THESE ROOMS
 FROM FLOOR TO DECK. THERE ARE NO PROVISIONS FOR RETURN
 AIR FROM THESE ROOMS. BALANCED RETURN AIR IS REQUIRED
 PER FBC, M 601.4. SHOW HOW BALANCED RETURN IS TO BE
 ACHIEVED IN THIS AREA.
  
 2. H2.6.1: ROOM 620 HAS AN R/A TRANSFER SHOWN FROM ROOM
 621. HOWEVER, THERE IS NO MEANS SHOWN FRO RETURN AIR
 FROM ROOM 620 BACK TO CENTRALIZED RETURN. ALSO,
 CENTRALIZED RETURN INTAKE IS LOCATED ABOVE CLERICAL
 ROOM 619. THIS INTAKE IS SEPARATED FROM THE EAST SIDE
 OF THE SPACE BY TWO CONTINUOUS P25 WALLS, ONE ON EACH
 SIDE OF RECEPTION 620 AND CONFERENCE 621. PLEASE SHOW
 HOW BALANCED RETURN IN THESE AREAS IS TO BE ACHIEVED.
  
 3. H7.6.1: VENTILATION AIR CALCULATIONS STATE THAT
 THERE IS AN EXPECTED OCCUPANCY OF 35 AND THIS NUMBER IS
 USED PER THE PROVISIONS OF FBC, M 403.3.1. THIS SECTION
 ALLOWS FOR VENTILATION TO BE BASED ON ACTUAL OCCUPANTS,
 NOT EXPECTED OCCUPANTS. THIS WOULD REQUIRE SOME MEANS
 OF COUNTING THE NUMBER OF OCCUPANTS IN THE SPACE AT ANY
 GIVEN TIME AND VARYING THE VENTILATION RATE BASED ON
 THAT NUMBER. ABSENT THAT TYPE OF SYSTEM OR APPROVED
 STATISTICAL DATA SHOWING AN OCCUPANT LOAD DIFFERENT
 THAN THAT IN TABLE 403.3, AS ALLOWED BY THE EXCEPTION
 TO THAT SECTION, THE VENTILATION RATE SHALL BE
 DETERMINED IN ACCORDANCE WITH TABLE 403.3.
  
 -BASED ON THE SQUARE FOOTAGE SHOWN ON THE LIFE SAFETY
 PLAN THERE IS APPROX. 6800S.F. OF OFFICE SPACE,
 EXCLUDING CONFERENCE ROOMS, CORRIDORS, CLOSETS, ETC.
 THE OCCUPANT LOAD AT 7/1000 IS 48. THE RATE FOR OFFICE
 SPACE IS 20 CFM PER PERSON FOR A TOTAL OF 960CFM.
  
 - BASED ON THE SQUARE FOOTAGE SHOWN ON THE LIFE SAFETY
 PLAN THERE IS APPROX. 1179S.F. IN CONFERENCE ROOMS 621,
 639 AND RNET ROOM 623. THE OCCUPANT LOAD AT 50/1000 IS
 59. THE RATE FOR CONFERENCE ROOMS IS 20 CFM PER PERSON
 FOR A TOTAL OF 1180 CFM.
  
 - BASED ON THE SQUARE FOOTAGE SHOWN ON THE LIFE SAFETY
 PLAN THERE IS APPROX. 685S.F. IN THE RECEPTION AREA
 ROOM 620. THE OCCUPANT LOAD AT 60/1000 IS 41. THE RATE
 FOR THE RECEPTION AREA IS 15 CFM PER PERSON FOR A TOTAL
 OF 615 CFM.
  
 BASED ON THESE CALCULATIONS, THE OUTSIDE AIR
 REQUIREMENTS FOR THIS SPACE EXCEEDS THE TOTAL SUPPLIED
 BY BASE BUILDING SYSTEMS FOR THIS FLOOR. THE AMOUNT OF
 OUTSIDE AIR FOR THIS SPACE CANNOT EXCEED THE PERCENTAGE
 OF THE FLOOR SPACE USED BY THIS TENANT BUILD-OUT IN
 ORDER TO ALLOW FOR ENOUGH FRESH AIR TO REMAIN FOR THE
 REST OF THE FLOOR WHEN OCCUPIED. THE BASE BUILDING
 VENTILATION SYSTEM WAS DESIGNED UNDER ASHRAE 62.1-2004
 AS ALLOWED BY FBC, M 403.4. DESIGNER SHOULD DETERMINE
 IF THAT METHOD OF DESIGN WOULD BRING THE VENTILATION
 REQUIREMENTS TO WITHIN THE QUANTITIES PROVIDED BY BASE
 BUILDING SYSTEMS OR IF ADDITIONAL OUTSIDE AIR IS
 REQUIRED BASED ON THE QUANTITIES REQUIRED BY TABLE
 403.3.
  
 4. CEILING RETURN PLENUM CAVITIES DESIGNED FOR AIR
 TRANSPORT SHALL BE LINED WITH AN AIR BARRIER AND SEALED
 IN ACCORDANCE WITH SECTION 603.9 AND SHALL BE INSULATED
 IN ACCORDANCE WITH TABLE 13-410.1.ABC.2.2. APPROVED AIR
 BARRIERS SHALL BE AS DEFINED IN FBC, M 603.9.1 AND THE
 R-VALUE OF INSULATION SHALL BE MIN. R-8 IN ACCORDANCE
 WITH THE ABOVE TABLE. SHOW THESE COMPONENTS AS A
 MINIMUM AS PART OF DETAIL 1 ON PG A7.6.3
  
 5. AS THIS TENANT BUILD OUT IS TO TAKE PLACE IN A
 BUILDING WHICH HAS NOT BEEN COMPLETED, AS A CONDITION
 OF PERMIT, THE CONSTRUCTION SERVICES DEPARTMENT IS
 REQUIRING A LETTER OF UNDERSTANDING BETWEEN THE BASE
 BUILDING CONTRACTOR, THE TENANT CONTRACTOR, AND THE
 BASE BUILDING DEVELOPER. THIS LETTER SHALL STATE THAT
 ALL INTERESTED PARTIES SHALL TAKE RESPONSIBILITY FOR
 THEIR WORK AND ACKNOWLEDGE THAT THE WORK OF ONE
 CONTRACTOR HAS THE POTENTIAL TO IMPACT THE OTHER?S
 ABILITY TO OBTAIN FINAL INSPECTIONS. CODE DEFICIENCIES
 WILL NOT BE OVERLOOKED REGARDLESS OF WHO IS RESPONSIBLE
 FOR THE RELATED WORK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-29 Cont ID  
Sent By kstevens Date 2008-03-29 Time 10:26 Rev Time 0.00
Received By kstevens Date 2008-03-29 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By kstevens Date 2008-01-11 Time 13:15 Rev Time 0.00
Received By kstevens Date 2008-01-10 Time 14:27 Sent To  
Notes
2008-01-11 13:24:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLANS TO BE ROUTED TO ADDRESSING TO DETERMINE SUITE
 NUMBER. ONCE ESTABLISHED THE SUITE NUMBER SHALL BE
 INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SHEET A7.1.2 HAS NO SUITE
 NUMBER IN THE TITLE BLOCK. ALSO SHT A7.1.2 IS NOT SHOWN
 IN THE SHEET INDEX ON SHT A0.0.1. PLEASE CORRELATE
 INDEX AND SHEETS SUBMITTED.
  
 2. SHT 2.6.1 BREAK ROOM SINK SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 CLEARANCE
 ****RESPONSE NOTED, BUT THE CLEARANCE REQUIRED BY
 SECTION 11-4.24.3 IS NOT INDICATED ON SHT A6.6.1 AS
 STATED. DETAIL 4 SHOWS 2'10" TO FLOOD RIM LEVEL IN THE
 BACK OF THE CABINET, THEN SHOWS 2'10" PLUS 1-5/8" TO
 THE SAME FLOOD RIM LEVEL IN THE FRONT OF THE CABINET.
 THE REQUIREMENT FOR THE CLEARANCE SHALL BE INDICATED AS
 27" MINIMUM HIGH, 30" WIDE AND 19" DEEP UNDERNEATH THE
 SINK. THIS IS BEST INDICATED WITH AN ELEVATION OF THE
 BREAKROOM SINK CABINET. CABINET DOORS ARE NOT ALLOWED
 IN THE CLEAR FLOOR SPACE OF THE SINK.
 B. 1OK
  
 3. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By kstevens Date 2007-12-06 Time 12:26 Rev Time 0.00
Received By kstevens Date 2007-12-06 Time 12:26 Sent To  
Notes
2007-12-06 12:36:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS TO BE ROUTED TO ADDRESSING TO DETERMINE SUITE
 NUMBER. ONCE ESTABLISHED THE SUITE NUMBER SHALL BE
 INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
  
 2. SHT 2.6.1 BREAK ROOM SINK SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 CLEARANCE
 B. 11-4.24.5 CLEAR FLOOR SPACE
  
 3. SHT P7.6.1 ELECTRIC WATER HEATER DETAIL SHOWS A HUB
 DRAIN FOR THE INDIRECT WASTE OF THE EMERGENCY PAN DRAIN
 AND THE P & T VALVE OF THE WATER HEATER. ALSO SHOWN ON
 THE DETAIL IS A TRAP PRIMER. THESE ARE NOT SHOWN ON THE
 SANITARY RISER ISOMETRIC, NOR ON THE WATER RISER
 ISOMETRIC SHT P2.6.1.. PLEASE HAVE THE RISER DIAGRAMS
 REFLECT THE PIPING SHOWN ON THE WATER HEATER DETAIL.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]