Plan Review Details - Permit 07110752
Plan Review Stops For Permit 07110752
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By lursu Date 2008-01-17 Time 10:24 Rev Time 0.00
Received By lursu Date 2008-01-17 Time 10:24 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By lursu Date 2007-12-07 Time 11:09 Rev Time 0.00
Received By lursu Date 2007-12-07 Time 11:09 Sent To  
Notes
2007-12-07 11:13:45***FAILED***
  
 SPECIFY THE UNIT NUMBER IN WHICH THE WORK IS BEING
 DONE.
  
 ALSO KNOW THATIT WILL BE THE DEVELOPER RESPONSIBILITY
 TO ASSIGN UNIT (DESIGNATORS) ADDRESSES TO ALL UNITS
 INSIDE THE STRUCTURE .
  
 EXAMPLES TO ASSIGN UNIT NUMBERS ARE:
  
 GROUND/FIRST FLOOR: UNIT NUMBERS FROM 100 TO
 199, (100 MAIN ST. # 101, INDICATES THE UNIT ON THE
 FIRST FLOOR)
 SECOND FLOOR: UNIT NUMBERS FROM 200 TO 299,
 (100 MAIN ST. # 201, INDICATES THE FIRST UNIT ON THE
 SECOND FLOOR)
  
 "N"FLOOR: UNIT NUMBERS FROM N00 TON99,
 (100 MAIN ST. # "N"01, INDICATES THE FIRST UNIT ON THE
 "N" FLOOR,).
  
 QUESTIONS/COMMENTS ,PLEASE CALL:
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-13 Cont ID  
Sent By shill Date 2008-06-13 Time 11:28 Rev Time 0.00
Received By shill Date 2008-06-13 Time 11:28 Sent To  
Notes
2008-06-13 11:29:39A2.1.1, A2.1.2, A7.1.2, A DATED 5/29/8 (REVIEWED BY
 CAPRI, AFFIDAVIT ATTACHED TO REVISION)

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 09:20 Rev Time 0.00
Received By shill Date 2008-06-11 Time 09:20 Sent To  
Notes
2008-06-11 09:20:38REVISION DATED5/17/8, A3.1.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 16:39 Rev Time 0.77
Received By jwitmer Date 2008-05-12 Time 16:39 Sent To PC
Notes
2008-05-12 16:40:10REVISION# 1 SLAB DETAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-21 Cont ID  
Sent By shill Date 2008-04-21 Time 14:26 Rev Time 0.00
Received By shill Date 2008-04-21 Time 14:26 Sent To  
Notes
2008-04-25 11:28:03AFFIDAVITS OK; OK TO RELEASE PLANS/PERMIT
  
2008-04-25 11:26:40ELECTRIC AFFIDAVIT DATED INCORRECTLY; AFFIDAVIT DATED
 3/10/08, PLANS DATED 2/15/08
  
 PERMIT PRINTED, DO NOT RELEASE PENDING RECEIPT OF
 CORRECTED AFFIDAVIT
  
2008-04-21 14:35:54****PRINT HOLD****
 ****PRIVATE PROVIDER PLAN, NEED BUILDING AFFIDAVITS AS
 FOLLOWS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SHEET A0.1.1 IS NOT INCLUDED IN THE PRIVATE
 PROVIDER AFFIDAVIT.PLEASE REVISE.
  
 2.SHEET A2.6.1 IS INCLUDED IN THE PRIVATE PROVIDER
 AFFIDAVIT BUT IS NOT INCLUDED IN THE PLAN OR INDEX
 SHEET.PLEASE REVISE.
  
 3.AT THIS TIME, ONLY THE ARCHITECTURAL AND FIRE
 AFFIDAVITS HAVE BEEN CHECKED.PLEASE CONFIRM OTHER
 TRADES AS THIS MAY DELAY PERMIT ISSUANCE.
  
 4.A PRINT HOLD HAS BEEN PLACED ON THE PERMIT.PLEASE
 SUBMIT THE REVISED AFFIDAVIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 06:36 Rev Time 0.00
Received By shill Date 2008-04-01 Time 06:36 Sent To  
Notes
2008-04-01 06:46:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 COMMENT FROM FIRST AND SECOND AUDITS:
  
 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS
 BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER
 FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS,
 INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH
 IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY
 INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF
 PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR
 COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED."
  
 3RD REVIEW, SPRINKLER PLANS NOT PROVIDED.ARCHITECT'S
 RESPONSE THAT THIS WILL BE UNDER SEPARATE PERMIT IS
 NOTED.AT A MINIMUM, A SPRINKLER HEAD LAYOUT PLAN IS
 TO BE SUBMITTED WITH THIS PERMIT FOR PERMIT ISSUANCE OR
 SUBMITTED SEPARATELY WITH COMPLETE INFORMATION FOR
 SPRINKLER PERMIT ISSUANCE.
  
 PLANS ARE OTHERWISE CODE COMPLIANT; WILL REMAIN IN
 FAILED STATUS UNTIL THE FIRE SPRINKLER PERMIT ISSUE IS
 RESOLVED, EITHER BY SUBMISSION AND REVIEW OF A CODE
 COMPLIANT SPRINKLER PERMIT (WHICH WOULD BE REQUIRED TO
 REMAIN IN F STATUS UNTIL THE TENANT BUILDOUT IS ISSUED)
 OR SUBMISSION AND REVIEW OF A SPRINKLER HEAD LAYOUT
 WITH THE TENANT BUILDOUT PERMIT.
  
 ***PLEASE ADVISE IF THIS ITEM IS ADDRESSED PRIOR TO
 RESUBMITTAL THROUGH SEPARATE PERMIT - STATUS WILL BE
 CHANGED TO "P"***
 ***PLEASE NOTE THAT FIRE SPRINKLER PLANS REQUIRE
 PRIVATE PROVIDER REVIEW AS THIS IS A BUILDING
 REQUIREMENT***
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By shill Date 2008-01-11 Time 14:46 Rev Time 0.00
Received By shill Date 2008-01-11 Time 14:46 Sent To  
Notes
2008-01-11 16:03:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)ADDRESSED.
  
 2.)PLEASE SEE MECHANICAL COMMENT #12.THE RESPONSE
 LETTER STATES THAT THE CONSTRUCTION MANAGER AND BASE
 BUILDING DEVELOPER WILL ISSUE THIS LETTER.I WAS
 UNABLE TO LOCATE THE LETTER IN THE PACKAGE.
  
 3.)ADDRESSED.
  
 4.FROM FIRST REVIEW - ON EITHER THE FLOOR PLAN OR THE
 LIFE SAFETY PLAN, PLEASE NOTE ALL REQUIRED FIRE
 RESISTANCE RATED ELEMENTS AND WALLS.SEE MECHANICAL
 SHEET H2.1.1, AN EXHAUST FAN IS SHOWN THROUGH THE WALL
 TO THE GARAGE AREA.ISN'T THERE AN OCCUPANCY
 SEPARATION AT THIS WALL?SEE FBC712, PENETRATIONS.
  
 2ND REVIEW; 2 HOUR FIRE RATED WALLS SHOWN ON A2.1.5.
 PLEASE SEE SHEET A0.22, GROUND FLOOR PLAN (LIFE SAFETY)
 FOR THE BASE BUILDING, AND NOTE THE FOLLOWING:
  
 A.A 2 HOUR WALL IS SHOWN ON THE TENANT BUILDOUT PLAN
 BETWEEN THE BANK AND THE LOBBY.THIS IS NOT SHOWN ON
 THE BASE BUILDING.PLEASE NOTE THAT IT IS ACCEPTABLE
 TO EXCEED CODE COMPLIANCE, BUT IF NOTED ON THE PLAN AS
 HAVING A REQUIRED FIRE RESISTANCE RATING WILL BE
 TREATED AS SUCH.
  
 B.THE BASE BUILDING SHOWS A REQUIRED 2 HOUR OCCUPANCY
 SEPARATION BETWEEN THE PARKING GARAGE RAMP (NOTED ON
 THE PLAN AS "OPEN AIR RAMP AREA" AND "OUTSIDE WALL &
 CONC. RAMP") AND THE BANK.THE PLAN HAS BEEN REVISED
 TO SHOW OTHER FIRE RATED WALLS.PLEASE NOTE THE 2 HOUR
 REQUIREMENT AS REQUESTED OR CLARIFY HOW AND WHY THIS
 RATING REQUIREMENT HAS BEEN REMOVED.FIRE RESISTANCE
 RATINGS ARE REQUIRED ON PLANS TO EXPEDITE FIELD ISSUES
 WHICH MAY ARISE.
  
 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS
 BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER
 FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS,
 INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH
 IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY
 INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF
 PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR
 COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED."
  
 6.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR A119,
 FBC FIGURE 11-25.
  
 7.BATHROOMS 114, 113, A2.1.4 SHOWS VWC AS WALL
 FINISH.THIS WAS NOT INCLUDED IN THE SCHEDULE OF
 FINISHES; PLEASE SEE FBC1210.2 REGARDING WALL FINISHES
 (BATHROOM, NONABSORBENT SURFACE REQUIRED).ALSO NOTE
 THAT THE DETAIL ROOM NUMBERS DO NOT CORRELATE (SHOWN AS
 113/112), SHEET A3.1.1.
  
 8.THE FLOOR PLAN AND BREAK ROOM 112 PLAN SHOWS A
 SINK, BUT THE DETAILS 111 (NOTE THAT THE ROOM
 DESIGNATION NUMBER DOES NOT CORRELATE WITH FLOOR PLAN)
 DO NOT SHOW A SINK, A3.1.1, AND CABINET DOORS ARE
 SHOWN.SEE FBC11-4.24.3, 11-4.24.5, KNEE CLEARANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By shill Date 2007-12-07 Time 08:41 Rev Time 0.00
Received By shill Date 2007-12-07 Time 08:41 Sent To  
Notes
2007-12-07 08:45:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE ELECTRIC COMMENTS REGARDING ADDRESSING.THIS
 ISSUE SHOULD BE RESOLVED PRIOR TO PERMIT ISSUANCE.
  
 2.SEE MECHANICAL COMMENTS, ITEM 12, REGARDING TENANT
 BUILDOUT.THE DOR ON THIS JOB IS TO PROVIDE SHOP
 DRAWING REVIEW STAMP (MICHAEL O ROSSIN IS ARCHITECT OF
 RECORD, ROBERT J. MCNAMARE, PE IS STRUCTURAL ENGINEER
 OF RECORD).
  
 3.APPLICABLE CODES SHOULD INCLUDE 2007 AMENDMENTS
 EFFECTIVE 7/1/07, SHEET A01.1. WWW.FLORIDABUILDING.ORG
  
 4.ON EITHER THE FLOOR PLAN OR THE LIFE SAFETY PLAN,
 PLEASE NOTE ALL REQUIRED FIRE RESISTANCE RATED ELEMENTS
 AND WALLS.SEE MECHANICAL SHEET H2.1.1, AN EXHAUST FAN
 IS SHOWN THROUGH THE WALL TO THE GARAGE AREA.ISN'T
 THERE AN OCCUPANCY SEPARATION AT THIS WALL?SEE
 FBC712, PENETRATIONS.
  
 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 6.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR A119,
 FBC FIGURE 11-25.
  
 7.BATHROOMS 114, 113, A2.1.4 SHOWS VWC AS WALL
 FINISH.THIS WAS NOT INCLUDED IN THE SCHEDULE OF
 FINISHES; PLEASE SEE FBC1210.2 REGARDING WALL FINISHES
 (BATHROOM, NONABSORBENT SURFACE REQUIRED).ALSO NOTE
 THAT THE DETAIL ROOM NUMBERS DO NOT CORRELATE (SHOWN AS
 113/112), SHEET A3.1.1.
  
 8.THE FLOOR PLAN AND BREAK ROOM 112 PLAN SHOWS A
 SINK, BUT THE DETAILS 111 (NOTE THAT THE ROOM
 DESIGNATION NUMBER DOES NOT CORRELATE WITH FLOOR PLAN)
 DO NOT SHOW A SINK, A3.1.1, AND CABINET DOORS ARE
 SHOWN.SEE FBC11-4.24.3, 11-4.24.5, KNEE CLEARANCE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-08-06 Cont ID  
Sent By dpalmer Date 2008-08-06 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2008-08-06 Time 13:49 Sent To PC
Notes
2008-08-06 13:49:49REV 7.12

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-07-15 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 09:18 Sent To PC
Notes
2008-07-15 09:18:56REV #10, 2.14, 7.12

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-07-14 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 15:06 Sent To PC
Notes
2008-07-14 15:10:59REV #9, SHEET E7.12
  
 1) NOTE: PLEASE KNOW ANY PROJECTS UNDER A PRIVATE
 PROVIDER MUST BE SENT BACK TO THAT FIRM FOR REVIEW,
 STAMPING ALONG WITH NEW SIGNED AFFIDAVITS FOR EACH
 NEW/REVISED SHEET PER FS 553.791

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-05-30 Cont ID  
Sent By dpalmer Date 2008-05-30 Time 13:01 Rev Time 0.00
Received By dpalmer Date 2008-05-30 Time 13:01 Sent To PC
Notes
2008-05-30 13:02:01REV, 2.11,2.12,2.14,7.12

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-22 Cont ID  
Sent By dpalmer Date 2008-04-22 Time 11:18 Rev Time 0.00
Received By dpalmer Date 2008-04-22 Time 11:18 Sent To  
Notes
2008-04-22 11:18:28STAMPED ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-31 Cont ID  
Sent By dpalmer Date 2008-03-31 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2008-03-31 Time 19:30 Sent To  
Notes
2008-03-31 19:30:44** DENIEDAUDIT **
  
  
 1) NOTE: PLEASE SEE REVISED SHEET A2.1.3 DOES NOT
 COORDINATE WITH SHEET E2.1.1. PLEASE SEE ROOM 122 AS
 SHOWN ON ELECTRICAL PLANS WHICH CONTAIN A WALL BETWEEN
 122 AND 121. PLEASE ALSO SEE FIXTURE LAYOUT HAS NOW
 BEEN REVISED.
 PLEASE COORDINATE SHEET E2.1.1 WITH OTHER PLANS AND
 SHEETS AS NO WALL IS SHOWN ON POWER PLANS NOR DOES THIS
 WALL APPEAR ON ARCHITECTURAL PLANS.
 PLEASE ADJUST ANY FIXTURE LAYOUTS.
  
 2) NOTE: PLEASE SEE SHEET E3.1.1 HAS NOW BEEN CHANGED
 FROM PREVIOUS REVIEW. PLEASE SEE THE TITLE BLOCKS
 INDICATES REVISIONS 1, 3 AND 6, HOWEVER PLANS ONLY
 INDICATE A REVISION #4. THIS REVISION #4 ON RISER IS
 NOT ON TITLE BLOCK AND REVISION #6 ON NOT ON PLANS.
 PLEASE COMPLETE PLANS WITH ALL REVISIONS AND COORDINATE
 ALL REVISIONS. IT IS UNCLEAR WHETHER OR NOT PLANS
 CONTAIN REVISIONS OR ARE MISSING REVISIONS NOT YET
 MADE.
  
 3) NOTE: PLEASE SEE NEW CHANGES MADE TO 2PUPS NOW HAS
 PANEL TO A 120/240V SINGLE PHASE PANEL WHICH IS OK,
 HOWEVER PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEET
 FOR THIS PROPOSED UNIT IF THIS WILL BE UNDER THIS
 PERMIT.
 FBC 106.1.2, NE C90.7, 110.3
 ** PLEASE SEE THE LOAD WAS ADJUSTED ON PANEL P21 AND
 LM41, HOWEVER THE LOAD SUMMARY FOR LM41 WAS NOT
 CHANGED. PLEASE EXPLAIN THE KVA OF 16 SHOWN ON PANEL
 P21, WHEN THE LOAD IS NOT THAT OF THE LOAD ON UPS
 PANEL.
 NEC 220.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-12 Cont ID  
Sent By dpalmer Date 2008-01-12 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2008-01-12 Time 16:54 Sent To  
Notes
2008-01-12 16:54:51*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE PLANS HAVE NOW BEEN REVISED WITH ITEMS
 WHICH WERE NOT ON PREVIOUS PLANS FOR REVIEW.
 PLEASE SEE COMMENTS BELOW.
  
 1) NOTE: PLEASE SEE LIGHTING PLANS NOW SHOW NEW
 EXTERIOR FIXTURES XM WHICH ARE NOT LISTED ON FIXTURE
 LEGEND/SCHEDULE. THESE ARE CLOUDED AND APPEAR TO BE
 SEPARATED BY THE OTHER SINGLE XM FIXTURE AS WELL AS THE
 OTHER NEW FIXTURES EN.
 PLEASE SEE NO CIRCUITING, CONTROLS ETC HAVE BEEN
 SUBMITTED OR SHOWN FOR THESE SAME FIXTURES.
 PLEASE SEE NO EXTERIOR LIGHTING PERFORMANCE
 CALCULATIONS ARE SHOWN.
 13-415.2, 13-415.1.ABC.1.4, 13-415.2.ABC.1.3.
 NEC 240.4, 310.16, 408.4, 210, ETC.
  
  
 2) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE STAMPED
 AND SIGNED BY THE RESPONSIBLE ENGINEER ON BASE BUILDING
 AS THIS BUILDING IS STILL UNDER CONSTRUCTION AND HAS
 RECEIVED A CERTIFICATE OF OCCUPANCY.
 PLANS DO CONTAIN A (SHOP DRAWING REVIEW STAMP) HOWEVER
 NOT SIGNED BY THE ELECTRICAL DESIGNER OF RECORD.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By dpalmer Date 2007-12-05 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2007-12-05 Time 11:18 Sent To  
Notes
2007-12-05 17:00:07NOTE ADDED, SPECS AND CUT SHEETS FOR UPS EQUIPMENT IS
 TO BE SUBMITTED FOR REVIEW. PLEASE BE SURE EQUIPMENT
 CONTAINS ALISTING FROM A NRTL.
 90.7, 110.3
2007-12-05 12:57:33** DENIED**
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND
 SUPPORTING DOCUMENTS HAVE BEEN ROUTED TO THE ADDRESSING
 REVIEWER.
 THE PERMIT APPLICATION AS APPLIED INDICATES THE 1ST
 FLOOR HOWEVER THIS TENANT DOES NOT TAKE THE ENTIRE
 FLOOR AND WILL REQUIRE SUITE/UNIT #.
 PLEASE KNOW ONCE THIS HAS BEEN DETERMINED THE TITLE
 BLOCKS ARE TO BE REVISED INDICATING THIS ADJUSTMENT.
 FBC 106.1.2, 106.3.5.1.2, 106.5.3 ETC
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE BE SURE ALL ROOM AND AREA DESIGNATIONS
 ARE LISTED ON PLANS FOR SCOPE OF WORK BEING DONE UNDER
 THIS PERMIT APPLICATION.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR ALL
 ELECTRICAL AS SHOWN AND CORRELATE WITH THE PANELS.
 FOR EXAMPLE:
 PANEL SCHEDULES INDICATE * OFFICE RECEPT* AND NOT THE
 ROOM OR AREA SPECIFIC. FOR EXAMPLE:PLEASE SEE
 2-PUPS-10, PANEL SCHEDULE WORK ROOM AND PLANS WORK ROOM
 IS A CIRCUIT IN BREAK-ROOM 112. PLEASE SEE WORK ROOM
 WHICH IS 121 DOES NOT CALL FOR ROOM OR ARE ON PLANS.
 PLEASE ADJUST
 NEC 408.4, 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE GO OVER ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES FOR
 LOADS.
 PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES WITH THAT
 OF THE LOADS SET FORTH IN THE NEC FOR RECEPTACLES AT
 180VA PER YOKE.
 PLEASE CLARIFY HOW SOME ARE HIGHER OR LOWER PER
 CIRCUIT. WHAT VALUE IS BEING USED.
 PLEASE SEE NEC 220 .14/220.44.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: PLEASE KNOW THAT ELECTRICAL CONDUITS ARE FEEDS
 MAY NOT BE IN A SEPARATE BUILDING ON A SEPARATE
 PROPERTY WHICH IS FED FROM A COMPLETELY DIFFERENT
 ELECTRICAL SERVICE AND SYSTEM.225.30, 230.3, 90.4.
 PLANS NOTE THE DRIVE THRU AND TELLER AREAS WILL BE
 UNDER SEPARATE PERMIT WHICH IS OK, HOWEVER ELECTRICAL
 SYSTEMS MAY NOT BE MIXED AND CROSSED.
 ** PLEASE SEE FLORIDA STATUTES 655.962 FOR MINIMUM
 LIGHTING LEVELS REQUIRED FOR ATM/TELLER LOCATIONS. **
 THIS IS ONLY NOTED FOR INFORMATION.
  
 5) NOTE: PLEASE SEE PLANS FOR AREA/ROOM 105 AS THE
 LIGHTING FIXTURES ON PLANS ARE A HIGHER AMOUNT THAN ON
 THE LIGHTING PERFORMANCE CALCULATIONS.
 EXAMPLE: PLEASE SEE PLANS WITH 18 FIXTURES AND
 CALCULATIONS SHOW 17. APPEARS PLAN CONTAINS AN EXTRA
 MISPRINTED FIXTURE.
  
 6) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL REVIEW
 WITH RESPECT TO LOADS FOR AC AND FOR OTHER TRADES FOR
 ANY ITEMS WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-22 Cont ID  
Sent By mwennerg Date 2008-04-22 Time 14:09 Rev Time 0.00
Received By mwennerg Date 2008-04-22 Time 14:09 Sent To  
Notes
2008-04-22 14:10:50LIFE SAFETY AND SPRINKLER LAYOUT SHEETS STAMPED, SIGNED
 AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-04 Cont ID  
Sent By mawillia Date 2008-04-04 Time 13:09 Rev Time 0.00
Received By mawillia Date 2008-04-04 Time 12:47 Sent To  
Notes
2008-04-04 13:04:14*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED, AND A LAYOUT OF THE FIRE SPRINKLER HEADS
 HAVE BEEN PROVIDED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-17 Cont ID  
Sent By mwennerg Date 2008-01-17 Time 10:51 Rev Time 0.00
Received By mwennerg Date 2008-01-17 Time 10:51 Sent To  
Notes
2008-01-17 11:01:52***DENIED***
  
 1) NO RESPONSE INCLUDED. PLEASE NOTE THAT THE SUITE
 NUMBER HAS BEEN INCLUDED IN THE TITLE BLOCK OF MOST
 SHEETS. THE REQUIREMENTS FOR THE SUITE CHARACTERS HAVE
 NOT BEEN ADDRESSED.
  
 2) OK
  
 3) OK
  
 4) NO RESPONSE INCLUDED.
  
 5) OK
  
 6) THE FIRE EXTINGUISHERS ARE SHOWN ON THE PLANS.
 PLEASE INCLUDE ACKNOWLEDGMENT REGARDING THE MINIMUM
 RATING REQUIREMENTS, OR WHERE THAT INFORMATION CAN BE
 FOUND.
  
 NEW COMMENTS:
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING ENGINEER
 RESPONSIBILITIES.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By mwennerg Date 2007-12-14 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2007-12-14 Time 10:17 Sent To  
Notes
2007-12-14 10:30:11***DENIED***
  
 1) SUITE IDENTIFICATION TO BE ADDED TO TITLE BLOCK. THE
 SUITE CHARACTERS SHALL BE MINIMUM (3") IN WIDTH AND
 CONTRASTING TO THE BACKGROUND PER CITY OF WEST PALM
 BEACH REQUIREMENTS.
  
 2) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B ORC. PLEASE BE SPECIFIC REGARDING THIS PROJECT.
  
 3) FIRE RATED DOORS SHALL BE REFERERED TO IN TERMS OF
 HOURS. PLEASE CORRECT ON SHT A7.1.1
  
 4) DUCT SMOKE DETECTORS WHERE PROVIDED ARE TO INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 5) PLEASE CLARIFY THE OCCUPANT LOAD FOR THIS SPACE
 USING THE APPROPRIATE FACTOR PER NFPA 101, SEC.7.3.1.2.
 SEE BUILDING COMMENT #8
  
 6) MINIMUM RATING FOR FIRE EXTINGUISHERS SHALL BE
 2A-10B,C.
  
 7) HOW WILL EMERGENCY ACCESS INTO TENANT SPACE AFTER
 BUSINESS HOURS BE ACCOMPLISHED?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 13:49 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 13:49 Sent To E
Notes
2008-07-23 13:50:30TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 10:59 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 10:59 Sent To E
Notes
2008-06-19 11:00:37TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:32 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:32 Sent To E
Notes
2008-06-17 16:32:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 10:48 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 10:48 Sent To B
Notes
2008-06-06 10:50:06TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 11:44 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 11:44 Sent To  
Notes
2008-06-05 09:45:166/5/08--ELEC SHEETS WERE PULLED FROM REVIEW TODAY BY
 STEPHANIE FROM PASS INTERNATION.PLANS ROUTED TO
 "SHILL" FOR "BLDG" REVIEW.
2008-06-03 11:44:28TO "COMM" BD#7--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:19 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:19 Sent To  
Notes
2008-05-08 16:20:01TO "COMM" BD#2--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:06 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:05 Sent To B
Notes
2008-05-08 16:05:33TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 11:51 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 11:51 Sent To  
Notes
2008-04-21 11:51:54TO "COMM" BD#55--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 10:13 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 10:13 Sent To  
Notes
2008-03-27 10:13:48TO "COMM" BD#53--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-09 Cont ID  
Sent By adarroug Date 2008-01-09 Time 10:35 Rev Time 0.00
Received By adarroug Date 2008-01-09 Time 10:35 Sent To  
Notes
2008-01-09 10:40:45TO "COMM" BD#60--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-14 Cont ID  
Sent By mwennerg Date 2007-12-14 Time 10:40 Rev Time 0.00
Received By mwennerg Date 2007-12-03 Time 11:16 Sent To  
Notes
2007-12-03 11:16:51TO "COMM" BD#53--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-23 Cont ID  
Sent By rregueir Date 2008-05-23 Time 16:28 Rev Time 0.00
Received By rregueir Date 2008-05-23 Time 16:14 Sent To  
Notes
2008-05-23 16:28:34PAGES: H2.1.1 REV.5, H2.1.2 REV. 6, H6.1.2 REV.4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-29 Cont ID  
Sent By rregueir Date 2008-03-29 Time 11:02 Rev Time 0.00
Received By rregueir Date 2008-03-29 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-16 Cont ID  
Sent By rregueir Date 2008-01-16 Time 16:54 Rev Time 0.00
Received By rregueir Date 2008-01-16 Time 12:44 Sent To  
Notes
2008-01-16 16:55:47REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ALL TECHNICAL CODE COMMENTS HAVE BEEN SATISFIED.
 HOWEVER, THE PLANS CANNOT BE STAMPED AT THIS TIME FOR
 THE FOLLOWING REASON: THE BUILDING OFFICIAL HAS
 ESTABLISHED A POLICY BY WHICH TENANT IMPROVEMENT
 PERMITS COULD BE ISSUED FOR SHELL BUILDINGS PRIOR TO
 COMPLETION OF THE SHELL. THAT POLICY REQUIRES A LETTER
 OF UNDERSTANDING (SEE PREVIOUS MECHANICAL REVIEW
 COMMENT #12). THIS LETTER WAS NOT INCLUDED WITH THIS
 SUBMITTAL. ALSO, A SHOP DRAWING REVIEW STAMP AND
 ORIGINAL SIGNATURE OF THE BASE BUILDING DESIGNER OF
 RECORD ON THE TENANT PLANS IS REQUIRED PRIOR TO PERMIT
 ISSUANCE. THESE PLANS HAVE BEEN INITIALED BY SOMEONE
 OTHER THAN DANIEL A. CAMPIA, THE MECHANICAL ENGINEER OF
 RECORD.
  
 AS THESE PLANS HAVE BEEN REVIEWED AND STAMPED BY A
 PRIVATE PROVIDER, IT IS RECOMMENDED THAT THE SAME PLANS
 WHICH HAVE BEEN SUBMITTED BE RETURNED TO THE BASE
 BUILDING DESIGNER OF RECORD FOR SIGNATURE. ONCE PLANS
 ARE RESUBMITTED WITH REQUIRED SIGNATURE AND LETTER OF
 UNDERSTANDING, PLANS WILL BE STAMPED FOR PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By rregueir Date 2007-12-04 Time 13:23 Rev Time 0.00
Received By rregueir Date 2007-12-03 Time 11:44 Sent To  
Notes
2007-12-04 13:23:18REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. H2.1.1: ROOM 108 IS SHOWN TO HAVE TYPE P25 WALLS,
 WHICH GO FROM FLOOR TO DECK (SEE A2.1.1). THERE IS NO
 MEANS SHOWN ON PLANS FOR RETURN AIR FROM THIS SPACE.
 SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA
 IN ACCORDANCE WITH FBC, M 601.4.
  
 2. H2.1.1: EF 1-3 AND EF 1-5 ARE BOTH LOCATED IN A
 RETURN AIR PLENUM CEILING. THE DISCHARGE DUCT FROM
 THESE FANS WILL BE UNDER POSITIVE PRESSURE. EXHAUST
 DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE LOCATED IN A
 PLENUM IN ACCORDANCE WITH FBC, M 601.3. SHOW HOW THESE
 AREAS ARE TO BE EXHAUSTED IN ACCORDANCE WITH THIS
 SECTION.
 NOTE: EF 1-1 AND EF 1-2 ARE ISOLATED FROM PLENUM AS
 BATHROOM WALLS ARE TYPE P25, WHICH GO FROM FLOOR TO
 DECK. THEREFORE THEY ARE NOT SUBJECT TO THIS COMMENT.
  
 3. H2.1.1: HP 1-7, UNIT IS LOCATED TO PROVIDE SERVICE
 CLEARANCE FROM WALL AT TELLER STORAGE 120. HOWEVER,
 THIS PLACES THE UNIT ABOVE THE P25 FLOOR TO DECK TYPE
 WALL AT STORAGE ROOM 117. HOW WILL THIS UNIT BE
 SERVICEABLE OR ABLE TO BE REMOVED IF IT IS EMBEDDED IN
 A FRAMED WALL? PLEASE SHOW ACCESS FOR SERVICE AND
 REPLACEMENT WHICH IS IN ACCORDANCE WITH FBC, M 306.1.
 THIS CONDITION WOULD ALSO BE IN CONFLICT WITH HVAC NOTE
 #1.
  
 4. H2.1.1: EF 1-1, 1-2, 1-3, 1-5 ARE SHOWN DISCHARGING
 THROUGH A NORTH WALL TO AN AREA MARKED AS "EXISTING."
 ACCORDING TO BASE BUILDING PLANS, THIS AREA IS PART OF
 THE ENCLOSED PARKING GARAGE. FIRE RESISTANCE RATED
 SEPARATION IS REQUIRED IN ACCORDANCE WITH FBC TABLE
 302.3.2. SHOW HOW THESE OPENINGS ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBC, M 607.5. ALSO, FANS ARE
 DISCHARGING INTO AN ENCLOSED PARKING GARAGE. THIS DOES
 NOT QUALIFY AS OUTDOORS. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 IN ACCORDANCE WITH FBC, M 501.2.
  
 5. H2.1.1 AND H6.1.3:HP 1-1 THROUGH HP 1-6 SHARE A
 COMMON RETURN AIR PLENUM. AS SUCH, THEY ARE REQUIRED TO
 HAVE FAN SHUT-DOWN BY SMOKE DETECTOR IN ACCORDANCE WITH
 FBC, M 606.2.2 AND 606.4. IF DUCT SMOKE DETECTORS ARE
 USED, THEY SHALL BE TIED INTO THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH FBC, M 606.4.1.
  
 6. H6.1.3: CONTROL SEQUENCES, THE OUTSIDE AIR DAMPERS
 (MOTORIZED) ARE SHOWN TO BE OPEN WHENEVER THE HEAT PUMP
 FANS ARE RUNNING. THESE DAMPERS ARE TO BE SHUT WHENEVER
 THE SPACES SERVED ARE NOT IN USE AND SHALL BE
 CONTROLLED IN ACCORDANCE WITH THE SHUTOFF DAMPER
 CONTROL REQUIREMENTS OF FBC 13-409.1.ABC.3.3.
  
 7. H6.1.3: EACH WATER LOOP HEAT PUMP SHALL HAVE A
 TWO-POSITION AUTOMATIC VALVE INTERLOCKED TO SHUT OFF
 WATER FLOW WHEN THE COMPRESSOR IS OFF IN ACCORDANCE
 WITH FBC 13-411.1.ABC.1.4. SHOW COMPLIANCE WITH THIS
 SECTION.
  
 8. H7.1.1: VENTILATION AIR CALCULATIONS, BASED ON THE
 SQUARE FOOTAGE OF DIFFERENT AREAS AS SHOWN ON PG
 A2.1.5, THE OCCUPANT LOADS USED FOR CALCULATIONS DO NOT
 CORRESPOND WITH THE OCCUPANT LOADS AS SHOWN ON TABLE
 403.3. EXAMPLE: THE LOBBY AREA ON PLANS IS SHOWN TO BE
 759SQ.FT. AT AN ESTIMATED OCCUPANT LOAD OF 60/1000,
 THIS SPACE WOULD HAVE AN OCCUPANT LOAD OF 46 PEOPLE.
 THERE ARE ALSO NO CALCULATIONS FOR TELLER AREAS OR
 WORKROOMS. INCLUDE THESE SPACES IN THE OFFICE AREA
 TOTALS BASED ON THE SQUARE FOOTAGE SHOWN ON A2.1.5. THE
 OCCUPANT LOAD UTILIZED FOR DESIGN OF THE VENTILATION
 SYSTEM SHALL NOT BE LESS THAN THE NUMBER DETERMINED
 FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED
 IN TABLE 403.3.
  
 9. H7.1.1: PROVIDE AN AIR BALANCE SCHEDULE SHOWING THE
 SPACE TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS IN
 ACCORDANCE WITH FBC 13-409.1.ABC.2. THE CURRENT BALANCE
 OF EXHAUST AIR, RELIEF AIR AND OUTSIDE AIR WOULD PUT
 THE SPACE IN NEGATIVE PRESSURE.
  
 10. H7.1.2: PROVIDE COOLING LOAD CALCULATIONS OR A
 SYSTEM SIZING SUMMARY IN ACCORDANCE WITH FBC
 13-407.1.ABC.1. HVAC SYSTEMS AND EQUIPMENT SHALL BE
 SIZED TO PROVIDE NO MORE THAN THE SPACE AND SYSTEM
 LOADS CALCULATED IN ACCORDANCE WITH THIS SECTION PER
 FBC 13-407.1.ABC.1.1.
  
 11. A1.1.1: THIS PLAN SHOWS A VACUUM TUBE SYSTEM
 RUNNING THROUGH THIS TENANT SPACE AS WELL AS CROSSING
 OVER INTO A SEPARATE PARCEL. A SEPARATE PERMIT WITH
 FULL ENGINEERED DOCUMENTATION IS REQUIRED FOR THIS
 SYSTEM IN ACCORDANCE WITH FBC 105.3.1(5). SUBMIT A
 SEPARATE APPLICATION, ASSOCIATED WITH THE PARCEL WHERE
 THE EQUIPMENT IS LOCATED, WITH ALL REQUIRED
 DOCUMENTATION AND MANUFACTURER'S SPECS FOR REVIEW IN
 ACCORDANCE WITH THIS SECTION.
  
 12. AS THIS TENANT BUILD OUT IS TO TAKE PLACE IN A
 BUILDING WHICH HAS NOT BEEN COMPLETED, AS A CONDITION
 OF PERMIT, THE CONSTRUCTION SERVICES DEPARTMENT IS
 REQUIRING A LETTER OF UNDERSTANDING BETWEEN THE BASE
 BUILDING CONTRACTOR, THE TENANT CONTRACTOR, AND THE
 BASE BUILDING DEVELOPER. THIS LETTER SHALL STATE THAT
 ALL INTERESTED PARTIES SHALL TAKE RESPONSIBILITY FOR
 THEIR WORK AND ACKNOWLEDGE THAT THE WORK OF ONE
 CONTRACTOR HAS THE POTENTIAL TO IMPACT THE OTHER?S
 ABILITY TO OBTAIN FINAL INSPECTIONS. CODE DEFICIENCIES
 WILL NOT BE OVERLOOKED REGARDLESS OF WHO IS RESPONSIBLE
 FOR THE RELATED WORK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-04-21 Cont ID  
Sent By kstevens Date 2008-04-21 Time 14:40 Rev Time 0.00
Received By kstevens Date 2008-04-21 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-03-28 Cont ID  
Sent By kstevens Date 2008-03-28 Time 13:57 Rev Time 0.00
Received By kstevens Date 2008-03-28 Time 13:57 Sent To  
Notes
2008-03-28 15:13:05AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS AIDIT:
  
 ******FROM PREVIOUS AUDITS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
  
 **********NEW COMMENT**********
  
 1B. OK
 2B. OK
  
 3B. SINCE THE SHELL BUILDING DOES NOT HAVE A
 CERTIFICATE OF OCCUPANCY, THE ENGINEER OF RECORD,
 DANIEL A CAMPIA IS REQUIRED TO REVIEW AND APPROVE THE
 PLANS FOR THE BUILDOUT. PLANS HAVE A SHOP DRAWING
 REVIEW STAMP, BUT IS NOT SIGNED BY THE PLUMBING
 ENGINEER OF RECORD.
 ******RESPONSE FROM ENGINEER, "PLEASE REFER TO
 ARCHITECT PLANS/COMMENTS FOR RESPONSES. ARCHITECTS
 RESPONSE, "SEE ENGINEERS RESPONSE LETTER". COMMENT NOT
 ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-14 Cont ID  
Sent By kstevens Date 2008-01-14 Time 08:49 Rev Time 0.00
Received By kstevens Date 2008-01-11 Time 16:53 Sent To  
Notes
2008-01-14 09:55:44DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLANS TO BE ROUTED TO ADDRESSING TO DETERMINE SUITE
 NUMBER. ONCE ESTABLISHED THE SUITE NUMBER SHALL BE
 INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SHTA1.1.2 HAS BEEN ADDED.
 THIS SHEET IS NOT INDICATED ON THE PLANS INDEX ON SHT
 A0.0.1, NOR DOES IT HAVE A SUITE NUMBER IN THE TITLE
 BLOCK.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
  
 **********NEW COMMENT**********
  
 1B. SHTS A3.1.1, (DETAIL 10),& A4.1.2, (DETAIL 1),
 SHOW THE CABINET DOORS. THE CABINET DOORS ARE NOT
 APPROVED AND SHALL BE REMOVED. SECTION 11-4.24.5 CLEAR
 FLOOR SPACE.
  
 2B. SHT A6.1.1 DETAIL 4 INDICATES 2'10" TO THE FLOOD
 RIM LEVEL AT THE BACK OF THE CABINET DETAIL, BUT SHOWS
 2'10" PLUS 1-5/8" AT THE FRONT OF THE CABINET. PLEASE
 INDICATE THE CLEARANCE AT THE FRONT OF THE CABINET AS
 REQUIRED IN SECTION 11-4.24.3. (27" MIN).
  
 3B. SINCE THE SHELL BUILDING DOES NOT HAVE A
 CERTIFICATE OF OCCUPANCY, THE ENGINEER OF RECORD,
 DANIEL A CAMPIA IS REQUIRED TO REVIEW AND APPROVE THE
 PLANS FOR THE BUILDOUT. PLANS HAVE A SHOP DRAWING
 REVIEW STAMP, BUT IS NOT SIGNED BY THE PLUMBING
 ENGINEER OF RECORD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By kstevens Date 2007-12-06 Time 08:28 Rev Time 0.00
Received By kstevens Date 2007-12-06 Time 08:28 Sent To  
Notes
2007-12-06 09:08:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS TO BE ROUTED TO ADDRESSING TO DETERMINE SUITE
 NUMBER. ONCE ESTABLISHED THE SUITE NUMBER SHALL BE
 INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
  
 2. A2.1.4 WALL FINISH LEGEND FOR THE MEN'S, (113), AND
 THE WOMEN'S, (114) TOILET ROOMS INDICATE P-1/CWT. CWT
 IS NOT SHOWN ON THE WALL FINISH LEGEND. PLEASE CLARIFY.
 ALSO P-1 PAINT DOES NOT COMPLY WITH SECTION 1210.2 OF
 THE BLDG CODE REQUIRING THE WALL TO HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. PAINT IS NOT A HARD
 SURFACE. PLEASE INDICATE WHAT MATERIAL WILL BE
 PAINTED.
  
 3. SHT A3.1.1 ADA REQUIREMENTS. PLEASE SHOW COMPLIANCE
 WITH SECTION 11-4.19.4 EXPOSED PIPES & SURFACES, AND
 SHOW THE TURNING AREA REQUIRED IN THE TOILET ROOMS AS
 REQUIRED IN SECTION 11-4.22.3.
  
 4. SHOW THE CLEAR FLOOR SPACE FOR THE BREAK ROOM SINK
 AS REQUIRED IN SECTION 11-4.24.5.
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 6.SHT P2.1.1 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN THE TOILET ROOMS. THE RISER
 SHOWS LAV, W/C, W/C & LAV, BUT THE FLOOR PLAN SHOWS
 W/C, LAV, LAV & W/C. PLEASE SUBMIT A RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-14 Cont ID  
Sent By eschneid Date 2008-01-14 Time 19:31 Rev Time 0.00
Received By eschneid Date 2008-01-14 Time 19:31 Sent To  
Notes
2008-01-14 19:35:47PASSED
  
 SHEET A1.1.2 SHALL BE REMOVED AS IT SHOWS EXTERIOR
 CONDITIONS THAT ARE NOT PART OF THIS PERMIT SUBMITTAL.
 THIS PLAN SEEMS TO BE ONE THAT SHOULD HAVE BEEN REMOVED
 PRIOR TO THE RESUBMITTAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-05 Cont ID  
Sent By eschneid Date 2007-12-06 Time 18:57 Rev Time 0.00
Received By eschneid Date 2007-12-05 Time 12:01 Sent To  
Notes
2007-12-05 12:10:28FAILED
  
 RESPOND TO COMMENTS IN WRITING.
  
 1) SHEET A1.1.0 SHOWS THAT THE EXTERIOR WORK NORTH OF
 THE BUILDING IS EXCLUDED FROM THIS PERMIT (0711052).
 ADDITIONALLY, THE PERMIT SCOPE OF WORK IS FOR INTERIOR
 WORK ONLY.
  
 2) SHEETS A1.1.1 AND A1.1.2 SHOW TUBES AND OTHER ITEMS
 OUTSIDE OF THE BUILDING, INCLUDING IN THE AREA THAT HAS
 BEEN STATED IS EXCLUDED FROM THE PERMIT.NO SUCH
 NOTATION IS ON THESE SHEETS.THESE SHEETS DO NOT
 INCLUDE THE PROPERTY LINE BETWEEN THE OFFICE PARCEL AND
 THE B-DECK GARAGE PARCEL.NOTE: ALL WORK DONE TO THE
 B-DECK GARAGE PARCEL SHALL BE ON A SEPARATE PERMIT AND
 SHALL BE CLEARLY SHOWN EXCLUDED FROM THIS PERMIT.
  
 3) A MINOR AMENDMENT IS REQUIRED TO BE APPROVED BY THE
 PLANNING AND ZONING DEPARTMENT FOR THE RECONFIGURATION
 OF THE OFFICE PARCEL ACCESS DRIVE AND THE B-DECK GARAGE
 PARCEL FOR THE REMOTE TELLERS AND ACCESS DRIVES PRIOR
 TO ANY BUILDING PERMIT APPROVAL FOR THIS WORK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.