Plan Review Details - Permit 07110714
Plan Review Stops For Permit 07110714
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-12 Cont ID  
Sent By shill Date 2008-12-12 Time 09:32 Rev Time 0.00
Received By shill Date 2008-12-12 Time 09:32 Sent To  
Notes
2008-12-12 09:34:10SHEETS M2, E2,E3, E4, E5; NO APPARENT BUILDING CHANGES.
  
 PROVISO - SUBMIT BUILDING CHANGES, IF ANY, AS A
 REVISION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-12 Cont ID  
Sent By shill Date 2008-02-12 Time 13:54 Rev Time 0.00
Received By shill Date 2008-02-12 Time 13:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By shill Date 2007-12-07 Time 17:40 Rev Time 0.00
Received By shill Date 2007-12-07 Time 17:40 Sent To  
Notes
2007-12-07 17:42:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE INCLUDE 2007 AMENDMENTS IN GOVERNING CODE,
 SP1, LS1, EFFECTIVE JULY 1, 2007,
 WWW.FLORIDABUILDING.ORG.
  
 2.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-12-12 Cont ID  
Sent By btrobaug Date 2008-12-12 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2008-12-12 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-08 Cont ID  
Sent By btrobaug Date 2008-05-08 Time 12:43 Rev Time 0.00
Received By btrobaug Date 2008-05-08 Time 07:47 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-20 Cont ID  
Sent By btrobaug Date 2008-02-20 Time 08:05 Rev Time 0.00
Received By btrobaug Date 2008-02-19 Time 16:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-06 Cont ID  
Sent By btrobaug Date 2007-12-06 Time 07:12 Rev Time 0.00
Received By btrobaug Date 2007-12-05 Time 12:05 Sent To  
Notes
2007-12-06 07:12:30 
  
 APPLICATION # 07110714
 ELECTRICAL PLAN REVIEW
 401 N. DIXIE HIGHWAY
 12/6/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} PROVIDE LIGHTING DENSITY FOR COMPLIANCE WITH
 13-415.
  
 2} THE COMPUTER ROOM MUST HAVE SPACE CONTROL PER
 13-415.1.ABC.1.2. INDICATE LOCATION ON THE PLAN.
  
 3} THE SPACE CONTROL DEVICES MUST TURN LIGHTING OFF
 WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE
 PER 13-415.1.ABC.1.2.(A). PLEASE NOTE SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-06-05 Cont ID  
Sent By mwennerg Date 2009-06-05 Time 14:40 Rev Time 0.00
Received By mwennerg Date 2009-06-05 Time 14:40 Sent To  
Notes
2009-06-05 14:40:32REVISION DATED 5/18/09

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-12 Cont ID  
Sent By mwennerg Date 2008-12-12 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2008-12-12 Time 14:01 Sent To  
Notes
2008-12-12 14:01:51REVISION DATED 11/4/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date 2008-02-14 Cont ID  
Sent By mawillia Date 2008-02-14 Time 17:15 Rev Time 0.00
Received By mawillia Date 2008-02-14 Time 16:49 Sent To  
Notes
2008-02-14 17:08:28*****APPROVED*****
  
  
 PLAN SHEETS LS1, A2, F1, F2, E2, AND E3 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 11:35 Rev Time 0.00
Received By mawillia Date 2007-12-12 Time 10:51 Sent To  
Notes
2007-12-12 11:35:29*****PROVISO*****
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE PROJECT
 SITE LOCATION IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 ABOVE COMMENT AS WELL AS THE OTHER PLAN REVIEWERS'
 COMMENTS HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-05 Cont ID  
Sent By adarroug Date 2008-12-05 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-12-05 Time 10:18 Sent To  
Notes
2008-12-05 10:21:29TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 14:57 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 14:57 Sent To E
Notes
2008-05-07 14:57:36TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-11 Cont ID  
Sent By adarroug Date 2008-02-11 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 08:53 Sent To  
Notes
2008-02-11 08:56:45TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 11:35 Rev Time 0.00
Received By mawillia Date 2007-11-29 Time 10:46 Sent To  
Notes
2007-12-03 14:27:10TO "BOB"#17
2007-11-29 10:46:51WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-06-01 Cont ID  
Sent By rregueir Date 2009-06-01 Time 11:21 Rev Time 0.00
Received By rregueir Date 2009-06-01 Time 10:30 Sent To FIRE
Notes
2009-06-01 11:21:38PAGE M2 REVISION 3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 12:56 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 12:56 Sent To PC
Notes
2008-12-14 12:56:54REVISED M2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-11 Cont ID  
Sent By tgordon Date 2008-02-11 Time 11:27 Rev Time 0.25
Received By tgordon Date 2008-02-11 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-05 Cont ID  
Sent By tgordon Date 2007-12-05 Time 11:28 Rev Time 0.45
Received By tgordon Date 2007-12-05 Time 11:28 Sent To  
Notes
2007-12-05 11:39:02*** PROVISO ***
 1) AIR HANDLER SMOKE DETECTORS SHALL BE TIED INTO THE
 BUILDINGS FIRE ALARM SYSTEM, PER 2004 FBC/M 606.4.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-04 Cont ID  
Sent By choops Date 2007-12-04 Time 09:26 Rev Time 0.00
Received By choops Date 2007-12-04 Time 09:26 Sent To  
Notes
2007-12-04 09:26:48*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.