2007-11-27 13:06:44 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER |
| REQUIRED FS553.844(5)(A). |
| |
| THE APPLICATION STATES THAT YOU ARE USING GLASPLY 4 AS |
| THE SECONDARY WATER BARRIER.THIS IS NOT COMPLIANT |
| WITH THE REQUIREMENTS; SEE THE FS553.844 AND |
| WWW.BOAF.NET.YOU MAY USE AN APPROVED CAP SHEET SUCH |
| AS RUBBEROID MOP SMOOTH OR RUBBEROID 20 AS THE |
| SECONDARY WATER BARRIER OR COMPLY IN ANOTHER WAY SUCH |
| AS TAPING THE PLYWOOD JOINTS OR FULL DECK COVERAGE. |
| |
| SECONDARY WATER BARRIER IS REQUIRED FOR THE SHINGLED |
| AREA ALSO.PLEASE PROVIDE SPEC SHEET OR PRODUCT |
| APPROVAL. |
| |
| IF YOU ELECT TO TAPE THE PLYWOOD JOINTS, PLEASE BE |
| ADVISED THAT 4" IS REQUIRED BY CODE, BUT 6" IS REQUIRED |
| BY SOME INSURANCE COMPANIES.A PERMIT WILL BE ISSUED |
| FOR 4" TAPE BUT CONTRACTOR IS ASKED TO ADVISE THE |
| HOMEOWNER OF THIS INFORMATION PRIOR TO MAKING A |
| DECISION. |
| |
| 2.)PLEASE REVISE THE ENHANCED FASTENING LETTER TO |
| INCLUDE ZONE II (PERIMETER).THE LETTER STATES ZONE |
| III, PERIMETER AND CORNER.THIS SHOULD READ ZONES II |
| AND III, PERIMETER AND CORNER. |