2008-01-25 09:58:17 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.PROVIDE TWO SETS OF THE INSTALLATION INSTRUCTIONS |
| AND EVALUATION REPORT FOR THE CLEAR PANELS.A TEST |
| REPORT WAS PROVIDED, BUT THIS IS NOT REQUIRED.PLEASE |
| GO TO THE WEBSITE AND PRINT THE REQUIRED DOCUMENT. |
| PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| |
| 2.THE SHUTTER CONNECTION MOUNTING TYPE ON THE |
| INSTALLATION SCHEDULE IS TO CORRELATE WITH THE ANCHOR |
| CHART ON THE PRODUCT APPROVAL. YOU'VE WRITTEN A1, BUT |
| SEE THE PANEL PRODUCT APPROVAL.THEY ARE C1 THROUGH |
| C5. |
| |
| 3.DESIGN PRESSURES WERE CALCULATED AT 130MPH.CITY |
| OF WEST PALM BEACH LIES ENTIRELY WITHIN THE 140MPH |
| ZONE, PLEASE REVISE. |
| |
| 4.PROVIDE A FLOOR PLAN SHOWING SHUTTER LOCATION AND |
| TYPE OF SHUTTER.ANCHOR SPACING COMPLIANCE CANNOT BE |
| DETERMINED.SEE THE ANCHOR SPACING CHART ON SHEET 3 OF |
| THE INSTALLATION INSTRUCTIONS.THE 9" SPACING DOES NOT |
| APPEAR TO BE COMPLIANT FOR A HOLLOW BLOCK SUBSTRATE. |
| |
| 5.A HOLD WAS PLACED ON ANOTHER PERMIT, 07060349, |
| ISSUED TO YOUR COMPANY.A REVISION IS REQUIRED; THIS |
| ISSUE HAS BEEN DISCUSSED WITH YOUR COMPANY AND THE |
| HOMEOWNER.PLEASE SUBMIT THIS REVISION AT THIS TIME. |
| NOTE THAT THIS PERMIT WILL EXPIRE SOON (2/1/08).THIS |
| PERMIT WAS NOT REVOKED DUE TO AN AGREEMENT BETWEEN ME |
| AND YOUR COMPANY THAT A REVISION WOULD BE SUBMITTED. |
| THIS HAS NOT BEEN DONE.ALLOWING THIS PERMIT TO BE |
| REVOKED OR TO EXPIRE WILL PUT THIS PERMIT IN THE STATUS |
| OF WORK BEING DONE WITHOUT A PERMIT AND YOU MAY BE |
| SUBJECT TO DISCIPLINARY ACTION.PLEASE ADDRESS THIS |
| ISSUE AT THIS TIME. |