Plan Review Details - Permit 07110537
Plan Review Stops For Permit 07110537
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-21 Cont ID  
Sent By shill Date 2007-12-21 Time 08:20 Rev Time 0.00
Received By shill Date 2007-12-21 Time 08:20 Sent To  
Notes
2007-12-21 08:20:51REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-20 Cont ID  
Sent By shill Date 2007-12-20 Time 08:43 Rev Time 0.00
Received By shill Date 2007-12-20 Time 08:43 Sent To  
Notes
2007-12-20 08:47:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE PROVIDE TWO COMPLETE SETS OF DOCUMENTS FOR
 PERMIT ISSUANCE.ONLY ONE SET OF EACH PRODUCT APPROVAL
 WAS SUBMITTED.DUE TO WORK LOAD, I AM UNABLE TO MAKE
 PHOTOCOPIES AT THIS TIME.
  
 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By shill Date 2007-11-28 Time 18:14 Rev Time 0.00
Received By shill Date 2007-11-28 Time 18:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-26 Cont ID  
Sent By shill Date 2007-11-26 Time 15:36 Rev Time 0.00
Received By shill Date 2007-11-26 Time 15:36 Sent To  
Notes
2007-11-26 15:39:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE WINDOW IS NOTED AS AN EGRESS WINDOW, BUT THE
 WINDOW SIZE DOES NOT COMPLY WITH EGRESS REQUIREMENTS.
 SEE FBC CHAPTER 10 AND FBC R 310.HOWEVER, EGRESS
 REQUIREMENTS ARE NOT CLEAR AS THE ENGINEER HAS DECLARED
 THIS AS BUSINESS OCCUPANCY, SO IT IS NOT CLEAR WHY AN
 EGRESS WINDOW IS NOTED.PLEASE CLARIFY CODE
 REQUIREMENTS AND SHOW COMPLIANCE ON THE PLAN.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 13:28 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 13:28 Sent To B
Notes
2007-12-14 13:29:03TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 15:52 Sent To B
Notes
2007-11-27 15:52:46TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-26 Cont ID  
Sent By shill Date 2007-11-26 Time 15:39 Rev Time 0.00
Received By shill Date 2007-11-21 Time 15:25 Sent To  
Notes
2007-11-21 15:25:13TO SMH DESK