Plan Review Details - Permit 07110500
Plan Review Stops For Permit 07110500
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-06 Cont ID  
Sent By lmartine Date 2007-12-06 Time 16:03 Rev Time 0.00
Received By lmartine Date 2007-12-06 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-30 Cont ID  
Sent By lmartine Date 2007-11-30 Time 11:13 Rev Time 0.00
Received By lmartine Date 2007-11-30 Time 11:13 Sent To  
Notes
2007-11-30 11:15:38PROVIDE SIGNED AND SEALED CALCULATIONS
  
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-11-29 Cont ID  
Sent By kconrad Date 2007-11-29 Time 09:17 Rev Time 0.00
Received By kconrad Date 2007-11-29 Time 09:17 Sent To B
Notes
2007-11-29 09:20:25THE PROPOSED ROOF RECOVER HAS BEEN APPROVED AS STATED.
 THE EXISTING BUR ROOF LAYERS WERE VERIFIED AND
 CONSISTED OF1-1/2" ISO BOARD MECHANICALLY ATTACHED TO
 THE EXISTING STEEL DECKING. THE ROOF MEMBRANE APPEARED
 TO BE A MODIFIED CAP SHEET. THEREFORE, A RECOVER IS
 WARRANTED AND COMPLIES WITH SECTION 511.3 OF THE
 FLORIDA EXISTING BUILDING CODE. REQUIRE PLAN REVIEW FOR
 DOCUMENTS SUBMITTED.