Plan Review Details - Permit 07110478
Plan Review Stops For Permit 07110478
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-28 Cont ID  
Sent By rmcdouga Date 2008-08-28 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2008-08-28 Time 10:03 Sent To  
Notes
2008-08-28 10:03:27BUILDING REVISION TO ADD IMPACT RATED EXTERIOR DOOR AND
 NON-IMPACT SH WINDOWS. REVISED SHEETS A1 AND A2 ARE OK
 FOR BUILDING.
 REVISED PRODUCT APPROVALS FOR WINDOWS DOOR AND STORM
 PANELS ARE OK.
  
 PROVISO
  
 SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE. SPECIFY
 CONNECTION TYPE (A,B,C,D OR E), ANCHOR TYPES, ANCHOR
 SPACING, PANEL SPAN, EDGE DISTANCE, ETC. A COPY OF AN
 INSTALLATION SCHEDULE IS ATTACHED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-25 Cont ID  
Sent By rmcdouga Date 2008-06-25 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2008-06-25 Time 10:44 Sent To E
Notes
2008-06-25 10:44:452004 FBC W/2007 REVISIONS
 REVISION TO ADD EXTERIOR DOOR TO ADDITION
  
 DENIED BY BUILDING
  
 1) THE DRAWINGS ARE REQUIRED TO HAVE A TITLE BLOCK
 CONTAINING ALL OF THE INFORMATION REQUIRED BY FLORIDA
 STATUTES AND FAC 61G15-23.002.
  
 2) SUBMIT TWO SIGNED, SEALED AND DATED COPIES OF
 REVISED DRAWINGS. FBC 106.1
  
 3) IN ADDITION TO THE FLOOR PLANS, SUBMIT TWO SIGNED
 AND SEALED COPIES OF A REVISED ELEVATION SHOWING
 LOCATION OF THE NEW DOOR. FBC R301.2.1 AND DCA RULE
 9B-72.
  
 4) IN ADDITION TO THE FLOOR PLANS, SUBMIT TWO SIGNED
 AND SEALED COPIES OF A REVISED ROOF FRAMING PLAN
 SPECIFYING THE LINTEL THAT WILL BE USED ABOVE THE DOOR
 OPENING. FBC R606.8
  
 5) THE PRESSURES SPECIFIED ON THE REVISION ARE TOO LOW
 AS THE DOOR APPEARS TO BE LOCATED IN WALL ZONE 5.
 PLEASE CORRECT. FBC R301.2.1 AND FIGURE R301.2(8).
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 THE PRODUCT APPROVALS FOR THE DOOR HAS NOT BEEN
 APPROVED IN WRITING BY THE ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-18 Cont ID  
Sent By rmcdouga Date 2008-03-10 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2008-03-10 Time 12:46 Sent To  
Notes
2008-03-10 14:59:10BUILDING PROVISO
  
 SUBMIT A LETTER FROM THE DESIGNER OF RECORD APPROVING
 THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9B-72.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By rmcdouga Date 2007-11-21 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2007-11-21 Time 16:14 Sent To E
Notes
2007-11-21 17:03:242004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.IF NEW SHEETS ARE SUBMITTED FOR THE ONES
 WITH THE IMPACT FEE STAMP, THEY WILL HAVE TO BE
 RESTAMPED OR THE OLD SHEETS WITH THE STAMPS CAN BE
 RESUBMITTED ALONG WITH THE NEW ONES.
  
 2) THE VALUE OF THE WORK ON THE PERMIT APPLICATION WAS
 TOO LOW. IT HAS BEEN ADJUSTED BASED ON THE ICC BUILDING
 VALUATION DATA. FEES IN THE AMOUNT OF $265.35 WHICH
 INCLUDES RADON FEES ARE DUE.
  
 3) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 4) SPECIFY THE SPACING OF THE VERTICAL WALL
 REINFORCEMENT ON THE PLANS. SEE FBC R609.3.
  
 5) THE CONCRETE NOTES ON D1 SPECIFY THE WRONG EDITION
 ON ACI 318. CHAPTER 43 OF THE 2004 FBC RESIDENTIAL
 SPECIFIES AC1 318-02. PLEASE CORRECT.
  
 6) THE CLADDING PRESSURES SPECIFIED UNDER WIND
 INFORMATION ON A1 ARE INCORRECT. SEE FBC TABLE
 R301.2(2) AND USE THE 10 SQFT EFFECTIVE WIND AREA FOR
 WORST CASE.
  
 7) SOME OF THE ROOF OVERHANG COMPONENT AND CLADDING
 PRESSURES ON A1 ARE NOT CORRECT. PLEASE CORRECT. SEE
 FBC TABLE 1609.6.2.1(3).
  
 8) PROVIDE A ROOF ZONE DIAGRAM FOR A GABLE ROOF ON A1.
 SEE FBC FIGURE R301.2(8).
  
 9) THE ENERGY CALCULATION FORM IS INCORRECT. WHEN USING
 THE PRESCRIPTIVE METHOD C, THE INSULATION IS REQUIRED
 TO BE THE MINIMUM SPECIFIED ON THE FORM. THEREFORE, THE
 CONCRETE BLOCK IS REQUIRED TO HAVE R-5 INSULATION. SEE
 FBC 13-600.
  
 10) FBC 106.3* CITY AMENDMENTSPRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 11) THE NOA FOR THE TRACO WINDOWS HAS BEEN REVISED BY
 NOA NO. 05-0930.03.
  
 NOTE: IN ORDER TO EXPEDITE PLAN REVIEW PLEASE SUBMIT
 ONE SET OF THE OLD DRAWINGS ALONG WITH THE NEW ONES.
 ALSO SUBMIT BOTH OF THE DRAWINGS THAT HAVE THE COUNTY
 IMPACT FEE STAMP OR THE NEW PLANS WILL HAVE TO BE
 STAMPED BY THE COUNTY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-26 Cont ID  
Sent By btrobaug Date 2008-08-26 Time 11:56 Rev Time 0.00
Received By btrobaug Date 2008-08-26 Time 11:25 Sent To B
Notes
2008-08-26 11:39:38NONCOMPLIANT
 REVISION DENIED
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A2, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THE PERMIT SET HAD AN EXISTING 200 AMP SERVICE WITH
 A DISCONNECT IN COMPLIANCE WITH 230.70(A)(1), THE NEW
 SERVICE ON THE REVISED PLANS DO NOT COMPLY WITH THAT
 ARTICLE AND INITIATES THE FOLLOWING COMMENTS.
  
 2} DUE TO THE PANEL LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1)
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230
 CAN BE REVIEWED.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES IN THE MASTER BEDROOM. THESE WERE REDLINED
 ON THE PERMIT SET AND NOT CORRECTTED ON THE REVISION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-23 Cont ID  
Sent By btrobaug Date 2008-06-23 Time 14:49 Rev Time 0.00
Received By btrobaug Date 2008-06-18 Time 06:36 Sent To B
Notes
2008-06-18 09:21:07 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN ONE TWO OR MORE
 SETS WITH EACH APPLICATION FOR A PERMIT.ONLY ONE RISER
 WAS SUBMITTED. CALLED ALFONSE AND LEFT A MESSAGE ON
 6/18/08 AND HELD THE REVISION WAITING ON THE SECOND
 COPY FOR THREE DAYS.
  
 2} 210.70(2)(B) REQUIRES AN EGRESS LIGHT FOR THE NEW
 BEDROOM DOOR. INDICATE COMPLIANCE WITH SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-11-27 Cont ID  
Sent By btrobaug Date 2007-11-27 Time 08:01 Rev Time 0.00
Received By btrobaug Date 2007-11-27 Time 07:33 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 11:59 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 11:59 Sent To E
Notes
2008-08-20 12:00:18TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 13:59 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 13:59 Sent To E
Notes
2008-06-16 13:59:23TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 16:15 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 16:15 Sent To M
Notes
2008-05-14 16:15:38TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 10:35 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 10:35 Sent To Z
Notes
2008-02-29 10:36:04TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-04 Cont ID  
Sent By jleech Date 2007-12-04 Time 08:12 Rev Time 0.00
Received By jleech Date 2007-11-19 Time 15:54 Sent To  
Notes
2007-11-19 15:54:14TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-20 Cont ID  
Sent By tgordon Date 2008-05-20 Time 14:58 Rev Time 0.30
Received By tgordon Date 2008-05-20 Time 14:58 Sent To  
Notes
2008-05-20 14:59:08REVISION TO MECH. PLAN AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-05-15 Cont ID  
Sent By tgordon Date 2008-05-15 Time 09:04 Rev Time 0.45
Received By tgordon Date 2008-05-15 Time 09:04 Sent To  
Notes
2008-05-15 09:21:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
  
 1) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN WITH
 CONTACT INFORMATION, AND CONTRACTOR INFORMATION IF
 APPLICABLE ON THEM, SEE W.P.B. AMEND. 106.1.3.
  
 2)THE AIR HANDLER MODEL NUMBERS (FSM3000) LISTED ON
 THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE
 ARI DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 3) SHOW THE A/C SYSTEM SEER ON THE PLAN, PER 2004 FBC
 13-607.1.ABC.3.1.1.
  
 4) AS THE A/C SYSTEM HAS BEEN INCREASED TO A 2.5 TON
 SYSTEM PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER
 2004 FBC 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 11:46 Rev Time 0.30
Received By tgordon Date 2008-03-03 Time 11:46 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By tgordon Date 2007-11-28 Time 15:51 Rev Time 0.40
Received By tgordon Date 2007-11-28 Time 15:51 Sent To P
Notes
2007-11-28 15:55:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 9A-1 IS CALLING FOR R4.2,
 SEE TABLE 6C-1 ON THE SECOND PAGE OF THE ENERGY CAL'S,
 THE MINIMUM INSULATION IS R-5, SEE 2004 FBC
 13-604.1.C.1. PLEASE CORRECT.
  
 2)ENERGY CALCULATIONS LINE 10A IS CALLING FOR R19,
 SEE TABLE 6C-1 ON THE SECOND PAGE OF THE ENERGY CAL'S,
 THE MINIMUM INSULATION IS R-30 FOR UNDER ATTIC, SEE
 2004 FBC 13-604.1.C.1. PLEASE CORRECT.
  
 3) THE MODEL NUMBER 113RNA035 ON THE MECHANICAL PLAN
 FOR THE A/C CONDENSER UNIT IS A INCORRECT NUMBER, SEE
 2004 FBC 13-607.ABC.3.1.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-04 Cont ID  
Sent By jleech Date 2008-03-04 Time 07:37 Rev Time 0.00
Received By jleech Date 2008-03-04 Time 07:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-04 Cont ID  
Sent By jleech Date 2007-12-04 Time 08:11 Rev Time 0.00
Received By jleech Date 2007-12-04 Time 08:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By choops Date 2008-03-03 Time 08:52 Rev Time 0.00
Received By choops Date 2008-03-03 Time 08:52 Sent To M
Notes
2008-03-03 08:52:56***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-20 Cont ID  
Sent By choops Date 2007-11-20 Time 09:27 Rev Time 0.00
Received By choops Date 2007-11-20 Time 09:27 Sent To E
Notes
2007-11-20 09:31:07***FAILED***
  
  
 1)THE VALUE OF PROPOSED WORK EXCEEDS 50% OF THE
 VALUE OF THE HOME.PURSUANT TO ARTICLE XIV OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS(ZLDRS), A
 LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION 94-442
 OF THE ZLDR'S SHALL BE SUBMITTED.
  
 2)PROVIDE OVERHANG DIMENSIONS.NOTE:PURSUANT TO
 SECTION 94-305 OF THE ZLDRS: STRUCTURAL INTRUSIONS MAY
 NOT PROJECT MORE THAN 3' INTO A REQUIRED SETBACK.
  
 3)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED, IF
 ANY, MECHANICAL EQUIPMENT TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720