Plan Review Details - Permit 07110443
Plan Review Stops For Permit 07110443
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-15 Cont ID  
Sent By jgomez Date 2008-04-15 Time 15:20 Rev Time 0.00
Received By jgomez Date 2008-04-15 Time 15:20 Sent To PC
Notes
2008-04-15 15:23:23BUILDING SUBMITTAL CHECKLIST:
  
 1-NEED TO PROVIDE COMPLETE PRODUCT APPROVAL
 INFORMATION FOR SLIDING GLASS DOORSUNDER A SEPARATE
 PERMIT AS AGREED ONPROVISO DATED 1-11-08. SEE
 ATTACHED COPY.
  
 ***NOTES:
 A) INFORMATION SUBMITTED IS NOT AN APPROVED PRODUCT
 APPROVAL. NEED TO SUBMIT COMPLETE PRODUCT APPROVAL
 INFORMATION FOR TYPE AND SIZE OF DOOR AS SHOWN ON
 PLANS. IF THERE IS NOT AN APPROVED PRODUCT APPROVAL
 AVAILABLE, THENA SITE SPECIFIC PRODUCT APPROVAL CAN
 BE APLIED FOR.COMPLETE ENGINEERING AND TESTING
 PACKAGE CAN BE SUBMITTED TO OBTAIN APPROVAL.COMPLETE
 PACKAGE WILL BE ROUTED TO MR. ROBERT BROWN, LICENSE &
 PERMIT SERVICES MANAGER/ABO (561)805-6652,FOR REVIEW
 AND APPROVAL.
  
 B) REVISED PLANS SUBMITTED ARE APPROVED AND STAMPED BY
 ALL TRADES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-20 Cont ID  
Sent By jgomez Date 2008-02-20 Time 16:55 Rev Time 0.00
Received By jgomez Date 2008-02-20 Time 16:50 Sent To PC
Notes
2008-02-20 16:58:32NEWSINGLE FAMILY RESIDENCE BUILDINGREVISION
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED TO REVISE WIND EXPOSURE CLASSIFICATIONS TO "C"
 FROM "B" AS REQUIRED BY SEC. R301.2.1.4(3)OF 2004
 FLORIDA RESIDENTIAL CODE.SEE ATTACHED COPY OF CODE
 SECTION.NEED TO REVISE INFORMATION ON SHEET T1 AND
 ALSO NEED TO REVISE OPENINGS DESIGN PRESSURES ON
 EXTERIOR ELEVATIONS AS REQUIRED BY TABLE R301.2.(3) OF
 2004 FLORIDA RESIDENTIAL CODE TO VERIFY THAT PRODUCT
 APPROVALS WILL MEET THE REVISED DESIGN PRESSURES.
  
 2- OWES $30.36 FOR REVISION UPDATED VALUATION.
  
 REMAINDER:
 PROVIDE INFORMATION REQUESTED ON PROVISO AS SOON AS
 POSSIBLE TO AVOID DELAYS OR CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANSEXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-11 Cont ID  
Sent By jgomez Date 2008-01-11 Time 13:45 Rev Time 0.00
Received By jgomez Date 2008-01-10 Time 16:36 Sent To PC
Notes
2008-01-11 13:53:29BUILDING REVIEW APPROVED WITH PROVISO:
 1- AS AGREED WITH KIM LIDDELLON 1-11-08 OVER THE
 PHONE, PROVIDE PRODUCT APPROVALFOR SLIDING GLASS
 DOORS SIZE AS SHOWN ON PLANS AND FOR STORM SHUTTERS (IF
 DOORS HAVE NOT IMPACT GLAZING)UNDER A SEPARATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By jgomez Date 2007-12-11 Time 15:55 Rev Time 0.00
Received By jgomez Date 2007-12-11 Time 07:42 Sent To PC
Notes
2007-12-11 16:33:15NEW RESIDENCE BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- SHEET T1:REVISE THE ALLOWABLE STRESS OF MASONRY
 UNITS. SEE SEC. R606.4 OF 2004 FLORIDA RESIDENTIAL CODE
 AND REVISE CONCRETE UNIT MASONRY NOTES D AND I.
  
 3- SHEET A1: REVISE DETAIL 5.DIMENSIONS 6" AND 8"
 DON'T ADD UP TO 10". REVISE AS REQUIRED.
  
 4- PROVIDE COMPLETE SPECIFICATIONS AND LISTING FOR
 EXTERIOR FIREPLACE INSTALLATION AS SHOWN ON PLANS AND
 AS REQUIRED BY SEC. R1002.1 AND SEC. R102.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 5- SHEET A3: REVISE CONNECTOR "C" SPECIFIED FOR GIRDER
 TRUSS ABOVE CLUB ROOM BY THE OPTIONAL DESK AREA.NEED
 TO SPECIFY WOOD TO MASONRY CONNECTOR. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 6- SHEET A6: REVISE ROOF SHEATHING SCHEDULE.MINIMUM
 REQUIREMENT IS TO USE 8D RING SHANK NAILS. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 7- PROVIDE SURVEY WITH ORIGINAL SIGNATURE AS REQUIRED
 BY CHAPTER 472 OF FLORIDA STATUTE.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) 2" MULLIONS AS SHOWN ON PLANS.
  
 B) SLIDING GLASS DOORS.SIZE OF DOORS SHOWN ON
 PRODUCT APPROVAL SUBMITTED IS SMALLER THAN THE ONE
 SPECIFIED ON PLANS.
 ALSO, PROVIDE COMPLETE INSTALLATION SPECIFICATIONS AND
 DRAWINGS.
  
 C) FIXED WINDOWS. NEED TO PROVIDE CURRENT REVISED FL
 243-R5 WITH CORRESPONDING NOA.
  
 D) SINGLE HUNG WINDOWS. NEED TO PROVIDE CURRENT
 REVISED FL 239-R10 WITH CORRESPONDING NOA.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 10- PROVIDE STRUCTURAL BUCK DETAIL USING 2X BUCK AS
 REQUIRED BY PRODUCT APPROVAL SUBMITTED FOR SLIDING
 GLASS DOORS SUBMITTED.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 11- SOIL TEST REPORT IS TOO OLD. IT WAS DONE IN MARCH
 3, 2004. NEED TO PROVIDE CURRENT SOIL TEST REPORT. SEC.
 R401.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 12- OWES $103.08 FOR UPDATED VALUATION AND RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-08-14 Cont ID  
Sent By btrobaug Date 2008-08-14 Time 10:10 Rev Time 0.00
Received By btrobaug Date 2008-08-14 Time 10:10 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-07-28 Cont ID  
Sent By btrobaug Date 2008-07-28 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2008-07-28 Time 11:25 Sent To PC
Notes
2008-07-28 12:22:31 
  
 REVISION DENIED
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PANEL "C" DOES NOT HAVE THE REQUIRED CLEARANCE PER
 110.26.
  
 2} THE #3 CU GROUNDING ELECTRODE IS IN VIOLATION OF
 250.66. A 1/0 IS REQUIRED FOR THE 400 AMP SERVICE AS IS
 ON THE PERMITTED SRT OF PLANS.
  
 3} THE RISER DIAGRAM INDICATES 2-#3 FEEDERS TO PANEL
 "D", THE PANEL SCHEDULE INDICATES #6 FEEDERS, CORRELATE
 SAME.
  
 4}SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, FOR THE A/C COMPRESSERS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-09 Cont ID  
Sent By btrobaug Date 2008-04-09 Time 07:48 Rev Time 0.00
Received By btrobaug Date 2008-04-09 Time 06:47 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-19 Cont ID  
Sent By btrobaug Date 2008-02-19 Time 09:24 Rev Time 0.00
Received By btrobaug Date 2008-02-19 Time 08:59 Sent To P
Notes
2008-02-19 09:24:02 
  
  
 REVISION DENIED
  
 THESE COMMENTS WERE PUT IN AS A PROVISO ON THE PERMIT
 SET AND HAVE NOT BEEN ADDRESSED.
  
 1} THERE ARE TWO SERVICE LOCATIONS INDICATED ON THE
 PLANS, REMOVE ONE.
  
 2} THE KITCHEN ISLAND MUST HAVE A RECEPTACLE TO COMPLY
 WITH 210.52(C)(2).
  
 THESE ITEMS MUST BE CORRECTED ON THE PLAN PRIOR TO
 SUBMITTING THE FIRST REVISION OR CALLING FOR ELECTRICAL
 INSPECTION.
  
 THE ARCHITECT MUST BE MADE AWARE OF THIS PROVISO.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 07:38 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 06:51 Sent To P
Notes
2008-01-08 07:38:09 
  
  
 SAME NOTES AS PREVIOUS REVIEW (PROVISO), SAME SHEET
 RESUBMITTED (A7)./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-11-20 Cont ID  
Sent By btrobaug Date 2007-11-20 Time 10:21 Rev Time 0.00
Received By btrobaug Date 2007-11-20 Time 09:01 Sent To M
Notes
2007-11-20 10:21:37 
  
  
  
  
 PROVISO
  
 THERE ARE TWO SERVICE LOCATIONS INDICATED ON THE PLANS,
 REMOVE ONE.
  
 THE KITCHEN ISLAND MUST HAVE A RECEPTACLE TO COMPLY
 WITH 210.52(C)(2).
  
 BEDROOM #2 MUST HAVE ANOTHER RECEPTACLE ADDED TO COMPLY
 WITH 210.52(A)(1).
  
 THESE ITEMS MUST BE CORRECTED ON THE PLAN PRIOR TO
 SUBMITTING THE FIRST REVISION OR CALLING FOR ELECTRICAL
 INSPECTION.
  
 THE ARCHITECT MUST BE MADE AWARE OF THIS PROVISO.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 10:21 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 10:21 Sent To Z
Notes
2009-02-27 10:22:28TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 14:28 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 14:28 Sent To E
Notes
2008-08-04 14:29:13TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 08:38 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 08:38 Sent To E
Notes
2008-07-22 08:38:57TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 11:10 Sent To M
Notes
2008-07-11 11:11:19TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 14:13 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 14:13 Sent To P
Notes
2008-05-12 14:13:20TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 15:27 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 15:27 Sent To E
Notes
2008-04-02 15:28:02TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 14:45 Sent To E
Notes
2008-02-12 14:46:04TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-03 Cont ID  
Sent By adarroug Date 2008-01-03 Time 15:16 Rev Time 0.00
Received By adarroug Date 2008-01-03 Time 15:16 Sent To Z
Notes
2008-01-03 15:16:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By jgomez Date 2007-12-11 Time 16:33 Rev Time 0.00
Received By jgomez Date 2007-11-16 Time 15:46 Sent To  
Notes
2007-11-16 15:46:32TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-03-02 Cont ID  
Sent By rkussner Date 2009-03-02 Time 11:42 Rev Time 0.00
Received By rkussner Date 2009-03-02 Time 09:28 Sent To Z
Notes
2009-03-02 11:53:44***LANDSCAPE REVIEW PASSED WITH PROVISO:
  
 1. PROVIDE REQUIRED STREET TREES TO BE CONSISTENT WITH
 THE BALANCE OF STREET.
  
 2. GRAVEL SHALL BE CONTAINTED AND UNLESS THERE IS A
 HEDGE ALONG THE NEIGHBORING PROPERTY LINE TO THE WEST,
 SOD SHALL BE USED.
  
 3. HARDSCAPE ELEMENTS (DECKS, POOLS, DRIVES, ETC) SHALL
 BE ACCURATELY SHOWN ON THE PLAN.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-11 Cont ID  
Sent By tgordon Date 2008-07-11 Time 14:03 Rev Time 0.30
Received By tgordon Date 2008-07-11 Time 14:03 Sent To  
Notes
2008-07-11 14:05:22REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-11-28 Cont ID  
Sent By tgordon Date 2007-11-28 Time 14:55 Rev Time 0.30
Received By tgordon Date 2007-11-28 Time 14:55 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-05-15 Cont ID  
Sent By jleech Date 2008-05-15 Time 08:59 Rev Time 0.00
Received By jleech Date 2008-05-15 Time 08:57 Sent To  
Notes
2008-05-15 09:00:05AS-BUILT RISER DIAGRAM

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-04-14 Cont ID  
Sent By jleech Date 2008-04-14 Time 08:36 Rev Time 0.00
Received By jleech Date 2008-04-14 Time 08:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-20 Cont ID  
Sent By jleech Date 2008-02-20 Time 08:53 Rev Time 0.00
Received By jleech Date 2008-02-20 Time 08:40 Sent To B
Notes
2008-02-20 09:01:35DENIED;
 1. BATHROOM TWO IS THE BATHROOM TO BE DELETED NOT
 BATHROOM NUMBER 4. BATHROOM TWO IS STILL SHOWN ON
 SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-08 Cont ID  
Sent By jleech Date 2008-01-08 Time 14:41 Rev Time 0.00
Received By jleech Date 2008-01-08 Time 14:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-04 Cont ID  
Sent By jleech Date 2007-12-04 Time 07:54 Rev Time 0.00
Received By jleech Date 2007-12-04 Time 07:51 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-07 Cont ID  
Sent By choops Date 2008-01-07 Time 09:23 Rev Time 0.00
Received By choops Date 2008-01-07 Time 09:23 Sent To E
Notes
2008-01-07 09:23:52***APPROVED - RESUB #1***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By choops Date 2007-11-19 Time 11:36 Rev Time 0.00
Received By choops Date 2007-11-19 Time 11:36 Sent To E
Notes
2007-11-19 11:43:37***FAILED***
  
  
 1)INDICATE BUILDING HEIGHT FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH (HIGHEST ROOF).I HAVE
 RECHECKED THE PLANS, BETWEEN SHEET A4 OR A5 THE HEIGHT
 IS SHOWN FROM GRADE ON ONLY ONE ELEVATION, IT SHALL BE
 SHOWN ON ALL ELEVATIONS.
  
 2)PROPOSED DRIVEWAY EXCEEDS MAXIMUM SQUARE FOOTAGE
 ALLOWABLE.PURSUANT TO SECTION 94-482(A) OF THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS):LOCATION AND SURFACE.REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS
 ARTICLE.
  
 3)THE DETERMINATION HAS BEEN MADE BY ANGELLA VANN,
 DEPUTY PLANNING DIRECTOR, THAT A TYPICAL LANDSCAPING
 PLANTING LIST IS NOT SUFFICIENT.A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTION 94-442 OF THE ZLDRS
 SHALL BE SUBMITTED WITH EVERY APPLICATION FOR BUILDING
 PERMIT AND SHALL MEET THE MINIMUM REQUIREMENTS FOUND IN
 SECTION 94-442 AND 94-445 OF THE ZLDRS.
  
 4)PROVIDE AN EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR, CITY HALL) APPROVING THE PROPOSED FENCE AND
 COLUMNS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720