Plan Review Details - Permit 07110417
Plan Review Stops For Permit 07110417
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-03-24 Cont ID  
Sent By rmcdouga Date 2008-03-24 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2008-03-24 Time 15:57 Sent To  
Notes
2008-03-24 16:37:04REVISED THREE PRODUCT APPROVALS
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS FOR THE SH-4000 PGT WINDOWS
 AND THE MASONITE STEEL DOORS HAVE BEEN REVIEWED FOR
 CODE COMPLIANCE.
  
 2) THE INSTALLATION SCHEDULE FOR THE ALUFAB STORM
 PANELS IS INCORRECT. THE MOUNT TYPE SPECIFIED IS FOR
 VERTICAL INSTALLATION. THE EDGE DISTANCE IS SPECIFIED
 AS 2" WHICH REQUIRES THE ANCHOR SPACING TO BE REDUCED
 BY HALF. PLEASE CORRECT.
  
 3) THE NUMBER OF PRODUCT APPROVALS REVISED IS THREE.
 THEREFORE AND ADDITIONAL $20.00 IN REVISION FEES IS
 DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-01 Cont ID  
Sent By rmcdouga Date 2008-02-01 Time 13:38 Rev Time 0.00
Received By rmcdouga Date 2008-02-01 Time 13:01 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-22 Cont ID  
Sent By rmcdouga Date 2008-01-22 Time 14:39 Rev Time 0.00
Received By rmcdouga Date 2008-01-22 Time 14:39 Sent To  
Notes
2008-01-22 15:49:552004 FBC W/2007 REVISIONS
 RESIDENTIAL REHAB
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE INSTALLATION SCHEDULE FOR THE STORM PANELS IS
 INCORRECT. THE PLANS SHOW THE OPENING WIDTH FOR THE
 THREE FRONT WINDOWS THAT ARE MULLED TOGETHER AS 10'-2"
 (122") AND THE SCHEDULE THE WAS SUBMITTED HAS 101".
 THE SCHEDULE INDICATES THAT THE PANELS WILL ALL BE
 INSTALLED HORIZONTALLY. HOWEVER, TABLE 1 ON PAGE 9 OF
 THE PRODUCT APPROVAL ALLOWS A MAXIMUM SPAN OF 105" FOR
 60 PSF. THE PRODUCT APPROVAL HAS BEEN MARKED TO
 INDICATE THAT A "H" HEADER WILL BE USED. HOWEVER, THIS
 CAN NOT BE USED IF THE PANELS ARE MOUNTED HORIZONTALLY.
 IF THE PANELS ARE MOUNTED VERTICALLY SPECIFY HOW THE
 BOTTOM WILL BE ATTACHED.
  
 3) ONE SET OF PLANS DOES NOT HAVE THE EMBOSSED RAISED
 SEAL OF THE ENGINEER AS REQUIRED BY FS 471 AND FAC
 61G-15-23.002.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By kconrad Date 2007-12-04 Time 19:40 Rev Time 0.00
Received By kconrad Date 2007-12-04 Time 18:32 Sent To I
Notes
2007-12-04 19:42:54PLEASE ADDRESS PREVIOUSLY STATED COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By rmcdouga Date 2007-11-19 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2007-11-19 Time 14:28 Sent To M
Notes
2007-11-19 14:28:072004 FBC W/2007 REVISIONS
 RESIDENTIAL REHAB
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SCOPE OF WORK ON A1 SPECIFIES THAT A 2'-8" STEEL
 DOOR IS TO BE INSTALLED. THE PLANS SHOW A 2'-8" INSWING
 EXTERIOR DOOR AND THE PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR AN OUTSWING DOOR. PLEASE CLARIFY.FBC
 *106.1.1 CITY AMENDMENTS
  
 3)SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR
 THE EXTERIOR DOOR THAT IS BEING REPLACED. SEE FBC TABLE
 R301.2(2).
  
 4) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE MOUNT TYPE, ANCHOR TYPE AND
 SPACING, SPAN, EDGE DISTANCE, ETC. THIS INFORMATION IS
 CONTAINED IN THE PRODUCT APPROVAL. SEE ATTACHED SAMPLE
 INSTALLATION SCHEDULE.
  
 5) SUBMIT ENERGY CALCULATIONS ON FORM 600C-04R AS
 REQUIRED BY FBC 13-101.4.1.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-30 Cont ID  
Sent By btrobaug Date 2008-01-30 Time 12:43 Rev Time 0.00
Received By btrobaug Date 2008-01-30 Time 12:17 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By btrobaug Date 2008-01-22 Time 12:15 Rev Time 0.00
Received By btrobaug Date 2008-01-10 Time 07:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-30 Cont ID  
Sent By btrobaug Date 2007-11-19 Time 10:34 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 10:02 Sent To M
Notes
2007-11-19 10:34:40 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE
 ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER
 DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE.
  
 2} DUE TO THE PANEL LOCATION, A DISCONNECT MAY BE
 REQUIRED PER 230.70, 225.32. INDICATE LOCATION ON PLAN
 PER 230.72(A)(1) .
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 09:01 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 09:01 Sent To B
Notes
2008-03-24 09:01:55TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-09 Cont ID  
Sent By adarroug Date 2008-01-09 Time 11:29 Rev Time 0.00
Received By adarroug Date 2008-01-09 Time 11:29 Sent To E
Notes
2008-01-09 11:29:32TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-04 Cont ID  
Sent By jleech Date 2007-12-04 Time 07:16 Rev Time 0.00
Received By jleech Date 2007-11-16 Time 11:27 Sent To  
Notes
2007-11-16 11:28:13TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-01-30 Cont ID  
Sent By tgordon Date 2008-01-30 Time 13:49 Rev Time 0.20
Received By tgordon Date 2008-01-30 Time 13:49 Sent To P
Notes
2008-01-30 13:50:21REVIEWED AND STAMPED ON 1-17-08.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By btrobaug Date 2008-01-30 Time 12:39 Rev Time 0.30
Received By tgordon Date 2008-01-17 Time 12:00 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By tgordon Date 2007-11-28 Time 11:48 Rev Time 0.40
Received By tgordon Date 2007-11-28 Time 11:48 Sent To P
Notes
2007-11-28 12:26:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL PLAN NEEDS TO SHOW THE SIZE OF THE
 RETURN AIR TRANSFER DUCTS (FLEX) TO THE BEDROOMS, SEE
 2004 FBC/R M1602.4.
  
 2) SHOW ON MECHANICAL PLAN HOW THE AIR IS RETURNING
 BACK TO THE AIR HANDLER, SEE 2004 FBC/R M1602.1.
  
 3) MECHANICAL PLANS SHOWS THE AIR HANDLES SUPPLYING
 1,032 CFM'S TO THE HOUSE, WHEN THE UNIT ONLY SUPPLIES
 800 CFM'S. PLEASE SUBMIT MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND FBC
 13-610.1.ABC.1. DUCT SYSTEMS SERVING HEATING, COOLING
 AND VENTILATION EQUIPMENT SHALL BE FABRICATED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND ACCA
 MANUAL D OR OTHER APPROVED METHODS. (AND)ALL AIR
 DISTRIBUTION SYSTEMS SHALL BE SIZED AND DESIGNED IN
 ACCORDANCE WITH RECOGNIZED ENGINEERING STANDARDS SUCH
 AS ACCA MANUAL D OR OTHER STANDARDS BASED ON THE
 FOLLOWING:
  
 4) ADD THE A/C EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION TO THE MECHANICAL PLAN NOT A SEPARATE
 PAPER, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE
 MECHANICAL PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-01 Cont ID  
Sent By mperson Date 2008-02-01 Time 13:55 Rev Time 0.00
Received By mperson Date 2008-02-01 Time 13:55 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-18 Cont ID  
Sent By jleech Date 2008-01-18 Time 07:39 Rev Time 0.00
Received By jleech Date 2008-01-18 Time 07:30 Sent To B
Notes
2008-01-18 09:14:33DENIED;
 1. ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
 2. AUTOMATIC CLOTHS WASHER FIXTURE DRAIN
 SHALL CONNECT TO A BRANCH DRAIN A MINIMUM
 OF 3" IN DIAMETER. SEE FBC-PLUMBING SECTION 406.3.
 3. W/M NOT VENTED. SEE FBC RESIDENTIAL SECTION
 P3101.2.1
 4. CLEANOUT REQUIRED ON WASHER STACK, SECTION
 P3005.2.6
 5. W/M DISCHARGE CANNOT DRAIN INTO A BATHROOM
 GROUP. MUST BE DOWN STREAM. SECTION
 P3108.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-04 Cont ID  
Sent By jleech Date 2007-12-04 Time 07:12 Rev Time 0.00
Received By jleech Date 2007-12-04 Time 07:12 Sent To  
Notes
2007-12-04 07:15:48SANITARY RISER DIAGRAM REQUIRED SHOWING W/M ADDITION.
 SIZE ALL DRAINAGE AND VENT PIPING. SEE FBC BUILDING
 SECTION 106.3.5.4.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695