Plan Review Details - Permit 07110335
Plan Review Stops For Permit 07110335
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-27 Cont ID  
Sent By shill Date 2007-11-27 Time 17:22 Rev Time 0.00
Received By shill Date 2007-11-27 Time 17:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-16 Cont ID  
Sent By shill Date 2007-11-16 Time 16:03 Rev Time 0.00
Received By shill Date 2007-11-16 Time 16:03 Sent To  
Notes
2007-11-16 16:11:10****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.PROVIDE INFORMATION FROM THE MANUFACTURER SHOWING
 THAT THE "QUICK ROOF" CAN BE USED IN THIS APPLICATION
 (UNDER 30# AND SHINGLES).FROM THE DOCUMENTATION
 PROVIDED, IT APPEARS THAT IT IS TO BE USED AS A ROOF
 SURFACING.
  
 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR ROOF COMPONENTS, FAC9B72.WWW.FLORIDABUILDING.ORG.
 PLEASE PRINT THE PRODUCT APPROVAL AND ASSOCIATED
 DOCUMENTS (EVALUATION REPORT AND INSTALLATION
 INSTRUCTIONS, FOUND AS LINKS ON THE PRODUCT APPROVAL AT
 WWW.FLORIDABUILDING.ORG).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-15 Cont ID  
Sent By shill Date 2007-11-15 Time 13:44 Rev Time 0.00
Received By shill Date 2007-11-15 Time 13:44 Sent To  
Notes
2007-11-15 13:46:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
 _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
  
 CONTRACTOR SUBMITTED HURRICANE MITIGATION GUIDELINES.
 A PRODUCT APPROVAL OR SPEC SHEET IS REQUIRED.ALSO
 PLEASE REVISE THE APPLICATION TO INCLUDE SECONDARY
 WATER BARRIER INTO SCOPE OF WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By shill Date 2007-11-13 Time 17:52 Rev Time 0.00
Received By shill Date 2007-11-13 Time 17:52 Sent To  
Notes
2007-11-13 17:52:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 ____4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  