Plan Review Details - Permit 07110326
Plan Review Stops For Permit 07110326
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-26 Cont ID  
Sent By shill Date 2007-11-26 Time 17:53 Rev Time 0.00
Received By shill Date 2007-11-26 Time 17:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By shill Date 2007-11-19 Time 14:01 Rev Time 0.00
Received By shill Date 2007-11-19 Time 14:01 Sent To  
Notes
2007-11-19 14:10:41****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 PLEASE CLARIFY SECONDARY WATER BARRIER:
  
 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER
 REQUIRED FS553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT.INFORMATION MAY BE
 AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION.
  
 PER CONVERSATION WITH CONTRACTOR, 4" TAPE AT THE SEAMS
 WILL BE USED FOR THE SHINGLE PITCHED ROOF.PLEASE
 ADVISE THE OWNER THAT FOR SOME INSURANCE COMPANIES, 6"
 TAPE IS REQUIRED FOR AN INSURANCE CREDIT.A PERMIT
 WILL BE ISSUED SPECIFYING 4" AS THIS IS THE MINIMUM
 CODE REQUIREMENT, BUT CONTRACTOR IS REQUIRED TO INFORM
 THE HOMEOWNER.
  
 PER CONVERSATION WITH CONTRACTOR, ONE ADDITIONAL PLY
 SHEET WILL BE INSTALLED (TWO PLY SHEETS) TO COMPLY WITH
 THE SECONDARY WATER BARRIER REQUIREMENT FOR THE LOW
 SLOPE ROOF.TO SHOW CODE COMPLIANCE AND TO AVOID
 MISUNDERSTANDING/DELAYS IN INSPECTIONS IN THE FIELD,
 PLEASE SUMMARIZE EACH SYSTEM WITH A DETAILED
 DESCRIPTION (DESCRIPTION OF LAYERS, NOT FASTENING).WE
 DISCUSSED USE OF ONE PLY OF GLASPLY 4, AN ADDITIONAL
 PLY OF RUBEROID MOP SMOOTH, AND A CAP SHEET.THE
 LETTER AND NOA SPECIFIES TWO PLIES OF GLASPLY4.THIS
 IS NOT COMPLIANT AS THE SECONDARY WATER BARRIER.
  
 2.)TW MOISTURE WRAP SPEC SHEET WAS PROVIDED.THE
 MANUFACTURER DOES NOT ALLOW THIS INSTALLED ON ROOF
 SHEATHING; TAMKLO MOISTURE GUARD PLUS IS THE CORRECT
 PRODUCT FOR ROOF SHEATHING.SEE THE TAMKO WEBSITE.
 HTTP://WWW.TAMKO.COM/ARTICLEDISPLAYPAGE/TABID/56/CONTRO
 LTYPE/ARTICLEDISPLAY/ITEMID/3366/DEFAULT.ASPX
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-14 Cont ID  
Sent By shill Date 2007-11-14 Time 17:13 Rev Time 0.00
Received By shill Date 2007-11-14 Time 17:13 Sent To  
Notes
2007-11-14 17:13:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER
 REQUIRED FS553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT.INFORMATION MAY BE
 AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION.
  
 PER CONVERSATION WITH CONTRACTOR, 4" TAPE AT THE SEAMS
 WILL BE USED FOR THE SHINGLE PITCHED ROOF.PROVIDE
 SPEC SHEET OR PRODUCT APPROVAL.
  
 PER CONVERSATION WITH CONTRACTOR, ONE ADDITIONAL PLY
 SHEET WILL BE INSTALLED (TWO PLY SHEETS) TO COMPLY WITH
 THE SECONDARY WATER BARRIER REQUIREMENT FOR THE LOW
 SLOPE ROOF.TO SHOW CODE COMPLIANCE AND TO AVOID
 MISUNDERSTANDING/DELAYS IN INSPECTIONS IN THE FIELD,
 PLEASE SUMMARIZE EACH SYSTEM WITH A DETAILED
 DESCRIPTION (DESCRIPTION OF LAYERS, NOT FASTENING).
  
 THE TILE ROOF FALLS UNDER THE EXCEPTION FS553.844; NO
 ADDITIONAL WATER BARRIER REQUIRED.
  
 2.)AS YOU HAVE THREE DIFFERENT ROOF SYSTEMS, PLEASE
 PROVIDE A ROOF PLAN.
  
 3.)PROVIDE INFORMATION IN REGARDS TO THE ROOF TILE
 INSTALLATION AREA.IF A TILE ROOF IS NOT CURRENTLY
 INSTALLED, ENGINEERING ADDRESSING THE ADDITIONAL DEAD
 LOAD WILL BE REQUIRED.
  
 4.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-11-14 Cont ID  
Sent By ssherman Date 2007-11-14 Time 09:59 Rev Time 0.00
Received By ssherman Date 2007-11-14 Time 09:59 Sent To  
Notes
2007-11-14 09:59:36HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 09:23 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 09:23 Sent To B
Notes
2007-11-19 09:24:03TO "SHILL" DESK/RESUB