Plan Review Details - Permit 07110235
Plan Review Stops For Permit 07110235
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By mjacobs Date 2007-12-12 Time 18:41 Rev Time 0.00
Received By mjacobs Date 2007-12-12 Time 18:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By mjacobs Date 2007-11-21 Time 06:48 Rev Time 0.00
Received By mjacobs Date 2007-11-21 Time 05:59 Sent To PC
Notes
2007-11-21 06:48:43BUILDING PLAN REVIEW
 PERMIT: 07110235
 ADD: 1000 OKEECHOBEE RD
 CONT: SOUTH PALM CONST. INC.
 TEL: (561)659-5828
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST11/21/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS. THIS INFORMATION IS
 REQUIRED ON THE PLANS.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)SUBMIT AN EXISTING AND A PROPOSED FLOOR SHOWING THE
 PROPOSED WORK. THE EXISTING DRAWINGS SHALL INDICATE THE
 AREAS OF THE DAMAGE DRYWALL IN THE ELECTRIC ROOM AND
 THE KITCHEN AREA. SUBMIT AN ELEVATION DRAWING OF THE
 SERVICE COUNTER WHICH MEETS THE REQUIREMENTS OF FBC
 11-7, WHERE A PORTION OF THE COUNTER IS A MINIMUM OF 36
 INCHES IN LENGTH AND A MAXIMUM HEIGHT OF 36 INCHES. IF
 THE NEW WALL WILL BE USED AS A SERVICE COUNTER, IT
 SHALL MEET THESE REQUIREMENTS ALSO.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 15:24 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 15:24 Sent To B
Notes
2007-12-07 15:25:01TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-11-21 Time   Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 12:55 Sent To  
Notes
2007-11-09 12:55:20TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-14 Cont ID  
Sent By choops Date 2007-11-14 Time 13:57 Rev Time 0.00
Received By choops Date 2007-11-14 Time 13:57 Sent To B
Notes
2007-11-14 13:59:02ZONING REVIEW NOT REQUIRED - INTERIOR RENOVATION ONLY
  
  
 SENT TO "B" - MISC. 2