Plan Review Details - Permit 07110020
Plan Review Stops For Permit 07110020
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-03 Cont ID  
Sent By shill Date 2008-06-03 Time 08:14 Rev Time 0.00
Received By shill Date 2008-06-03 Time 08:14 Sent To  
Notes
2008-06-03 08:27:16REVISED A1, A2, A3, F1

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-10 Cont ID  
Sent By shill Date 2008-04-10 Time 17:31 Rev Time 0.00
Received By shill Date 2008-04-10 Time 17:31 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-11 Cont ID  
Sent By shill Date 2008-02-11 Time 10:09 Rev Time 0.00
Received By shill Date 2008-02-11 Time 08:44 Sent To  
Notes
2008-02-11 10:14:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 2.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 PLEASE PROVIDE PLANS AS REQUIRED.ARCHITECT PUT A NOTE
 ON THE PLAN; SHOPS AND CALCULATIONS MAY BE SUBMITTED
 LATER BUT, AT A MINIMUM, A SPRINKLER HEAD LAYOUT IS TO
 BE INCLUDED IN THIS PLAN.DCA HAS ISSUED A LETTER
 STATING THAT PLANS MUST BE SUBMITTED PRIOR TO PERMIT
 ISSUANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By shill Date 2007-11-13 Time 11:45 Rev Time 0.00
Received By shill Date 2007-11-13 Time 11:45 Sent To  
Notes
2007-11-13 11:47:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.GOVERNING CODE SHOULD INCLUDE 2007 AMENDMENTS
 EFFECTIVE JULY 1, 2007.
  
 2.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 3.ON THE PLAN, NOTE EXISTING FIRE RATED WALLS.
  
 4.SEE FBC TABLE 1016.1.DECLARE OCCUPANT LOAD FOR
 THE AREAS SERVED BY CORIDORS 100, 102, 112.IF THIS
 CORRIDOR IS TO BE RATED, SHOW COMPLIANCE ON THE PLAN
 AND PLEASE COORDINATE MECHANICAL SHEETS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 13:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-06-12 Cont ID  
Sent By dpalmer Date 2008-06-12 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2008-06-12 Time 13:36 Sent To  
Notes
2008-06-12 13:36:44** DENIED REVISION **
  
 1) NOTE: PLEASE SEE TABLE 13-415.2.C WHICH ALLOWS 1.0
 WATTS PER SQ FT. AS THE ZONE IS SHOWN AS 691 SQ FT, HOW
 CAN THE LIGHTING BE SHOWN AS 752WATTS FOR DESIGN WHEN
 THE CODE GIVES A MAXIMUM OF 1.0 PER SQ FT WHICH
 691WATTS?
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-10 Cont ID  
Sent By rbrown Date 2008-04-10 Time 17:47 Rev Time 0.00
Received By rbrown Date 2008-04-10 Time 17:47 Sent To  
Notes
2008-04-10 17:48:29ENERGY CODE COMPLIANCE FORM WAS SIGNED BY OWNER/OWNER
 AGENT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-24 Cont ID  
Sent By dpalmer Date 2008-01-24 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2008-01-24 Time 14:22 Sent To  
Notes
2008-01-24 14:23:21TEMP FAILED STATUS.
  
 OWNER AGENT NEEDS TO SIGN ENERGY CALCULATIONS
 CERTIFICATION SHEETS IN BOTH COPIEDS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By dpalmer Date 2007-11-28 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2007-11-28 Time 15:37 Sent To  
Notes
2007-11-28 16:39:36** DENIED**
  
  
 1) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE/DENSITIES
 PER 13-415.2.B.1, TABLE 13-415.2.B
  
 2) NOTE: PLEASE CLARIFY IT ROOM SHOWN ON PLANS, IF THIS
 IS A TRUE IT ROOM PER NEC 645, PLEASE PROVIDE
 INFORMATION ON DISCONNECTING MEANS AS REQUIRED PER
 645.10. IF THIS IS NOT AN IT ROOM, PLEASE CHANGE
 DESIGNATION ON PLANS.
 PLEASE SEE NEC 645 SCOPE, AND NFPA-75 CHAPTERS 4 AND
 5.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-06-12 Cont ID  
Sent By mwennerg Date 2008-06-12 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2008-06-12 Time 14:20 Sent To  
Notes
2008-06-12 14:21:21REVISION DATED 3/11/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-03 Cont ID  
Sent By mawillia Date 2008-04-03 Time 14:30 Rev Time 0.00
Received By mawillia Date 2008-04-03 Time 13:49 Sent To  
Notes
2008-04-03 14:20:31*****APPROVED*****
  
  
 PLAN SHEETS A-2, E-2, AND F-1 WERE STAMPED, INITIALED,
 AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-12 Cont ID  
Sent By mawillia Date 2008-02-12 Time 13:08 Rev Time 0.00
Received By mawillia Date 2008-02-12 Time 12:55 Sent To  
Notes
2008-02-12 13:05:41*****PROVISO*****
  
  
 1.WILL THE SCOPE OF WORK HAVE CAUSE FOR ANY FIRE
 SPRINKLERS TO BE RELOCATED, ALTERED, OR REMODELED?
 PROVIDE SPRINKLER HEAD LAYOUT AS PER BUILDING REVIEW
 COMMENT # 2.
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL REVIEWERS HAVE BEEN SATISFIED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-05 Cont ID  
Sent By mawillia Date 2007-12-05 Time 16:43 Rev Time 0.00
Received By mawillia Date 2007-12-05 Time 16:18 Sent To  
Notes
2007-12-05 16:19:51*****PROVISO*****
  
  
 1.WILL THE SCOPE OF WORK HAVE CAUSE FOR ANY FIRE
 SPRINKLERS AND OR FIRE ALARM DEVICES TO BE RELOCATED,
 ALERED,OR REMODELED?IF SO., SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED.
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL REVIEWERS HAVE BEEN SATISFIED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-27 Cont ID  
Sent By adarroug Date 2008-06-27 Time 08:42 Rev Time 0.00
Received By adarroug Date 2008-06-27 Time 08:42 Sent To E
Notes
2008-06-27 08:43:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 11:10 Sent To  
Notes
2008-05-19 11:10:54TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 17:28 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 17:28 Sent To  
Notes
2008-03-10 17:28:18TO "COMM" BD#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-17 Cont ID  
Sent By adarroug Date 2008-01-17 Time 10:17 Rev Time 0.00
Received By adarroug Date 2008-01-17 Time 10:17 Sent To  
Notes
2008-01-17 10:17:15TO "COMM" BD#34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-05 Cont ID  
Sent By mawillia Date 2007-12-05 Time 16:18 Rev Time 0.00
Received By mawillia Date 2007-11-02 Time 10:18 Sent To  
Notes
2007-11-15 14:56:10TO "COMM" BD#27
2007-11-02 10:18:26WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-06-03 Cont ID  
Sent By rregueir Date 2008-06-03 Time 10:36 Rev Time 0.00
Received By rregueir Date 2008-06-03 Time 09:40 Sent To  
Notes
2008-06-03 10:36:45PAGES M-1, M-2, M-3 REVISION #1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-26 Cont ID  
Sent By rregueir Date 2008-03-26 Time 15:45 Rev Time 0.00
Received By rregueir Date 2008-03-26 Time 15:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-11 Cont ID  
Sent By rregueir Date 2008-02-11 Time 16:26 Rev Time 0.00
Received By rregueir Date 2008-02-11 Time 16:04 Sent To  
Notes
2008-02-11 16:26:41REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE THROUGH-PENETRATION FIRESTOP SYSTEMS SHOWN ON
 PLANS DO NOT ALLOW FOR INSULATED PIPE. AS THIS WILL
 INVOLVE INSULATED REFRIGERANT PIPE, THIS SPECIFIED
 SYSTEMS ARE NOT APPROPRIATE. PLEASE PROVIDE A
 THOUGH-PENETRATION FIRESTOP SYSTEM WHICH IS APPROPRIATE
 FOR TH TYPE OF PENETRATIONS BEING POTECTED IN
 ACCORDANCE WITH FBC 712.3.
  
 2 AND 3: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-28 Cont ID  
Sent By rregueir Date 2007-11-28 Time 19:19 Rev Time 0.00
Received By rregueir Date 2007-11-28 Time 19:18 Sent To  
Notes
2007-11-28 19:19:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-2: KEY NOTE #10, ARE REFRIGERANT LINES PENETRATING
 RATED FLOOR/CEILING ASSEMBLIES TO GET TO ROOF? IF SO,
 PROVIDE DETAIL FOR THROUGH-PENETRATION FIRESTOP SYSTEM
 IN COMPLIANCE WITH FBC 712.4.1.2.
  
 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH FBC, M CHAPTER 4 PER THE
 REQUIREMENTS OF FBC, EB 609.1. PROVIDE OUTSIDE AIR
 CALCULATIONS SHOWING VENTILATION REQUIREMENTS INCLUDING
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, CFM REQUIRED
 AND CFM PROVIDED IN ACCORDANCE WITH FBC, M TABLE
 403.3.
  
 3. M-3: PRE-ENGINEERED A/C STANDS ARE DEFINED AS
 STRUCTURAL COMPONENTS UNDER FAC RULE 9B-72 AND AS SUCH
 A PRODUCT APPROVAL IS REQUIRED. PROVIDE A PRODUCT
 APPROVAL FOR THE SPECIFIC STAND TO BE INSTALLED ALONG
 WITH INSTALLATION INSTRUCTIONS. THE STAND IS TO BE
 SECURED TO THE STRUCTURE AND THE CONDENSING UNIT IS TO
 BE ATTACHED TO THE STAND PER THE INSTRUCTIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-20 Cont ID  
Sent By choops Date 2007-11-20 Time 13:07 Rev Time 0.00
Received By choops Date 2007-11-20 Time 13:07 Sent To  
Notes
2007-11-20 13:08:04*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE, AND ONLY
 DOING INTERIOR RENOVATIONS.