2007-11-06 09:35:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) SHOW COMPLYANCE WITH 2004 FBC/M 502.3 |
| BATTERY-CHARGING AREAS. VENTILATION SHALL BE PROVIDED |
| IN AN APPROVED MANNER IN BATTERY-CHARGING AREAS TO |
| PREVENT A DANGEROUS ACCUMULATION OF FLAMMABLE GASES. |
| 502.4 STATIONARY LEAD-ACID BATTERY SYSTEMS. VENTILATION |
| SHALL BE PROVIDED FOR STATIONARY LEAD-ACID BATTERY |
| SYSTEMS IN ACCORDANCE WITH THIS CHAPTER AND SECTION |
| 502.4.1 OR 502.4.2. |
| 502.4.1 HYDROGEN LIMIT. THE VENTILATION SYSTEM |
| SHALL BE DESIGNED TO LIMIT THE MAXIMUM CONCENTRATION OF |
| HYDROGEN TO 1.0 PERCENT OF THE TOTAL VOLUME OF THE |
| ROOM. |
| 502.4.2 VENTILATION RATE. CONTINUOUS VENTILATION |
| SHALL BE PROVIDED AT A RATE OF NOT LESS THAN 1 CUBIC |
| FOOT PER MINUTE PER SQUARE FOOT (CFM/FT 2 ) [0.00508 M |
| 3 /(S.M 2)] OF FLOOR AREA OF THE ROOM. |
| 502.5 VALVE-REGULATED LEAD-ACID BATTERIES. |
| VALVE-REGULATED LEAD-ACID BATTERY SYSTEMS AS REGULATED |
| BY THE FLORIDA FIRE PREVENTION CODE , SHALL BE PROVIDED |
| WITH VENTILATION IN ACCORDANCE WITH SECTION 502.5.1 OR |
| 502.5.2 FOR ROOMS AND IN ACCORDANCE WITH SECTION |
| 502.5.3 OR 502.5.4 FOR CABINETS. |
| |