Plan Review Details - Permit 07100863
Plan Review Stops For Permit 07100863
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-11-06 Cont ID  
Sent By rmcdouga Date 2007-11-06 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2007-11-06 Time 08:09 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-11-05 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 11:46 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 10:39 Sent To B
Notes
2007-11-05 11:46:44 
  
  
 MISC. BOX #2./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-06 Time 15:36 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 10:17 Sent To M
Notes
2007-11-14 15:38:08TO "M" BOX/RESUB
2007-10-31 10:17:49TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-15 Cont ID  
Sent By tgordon Date 2007-11-15 Time 16:25 Rev Time 0.30
Received By tgordon Date 2007-11-15 Time 16:25 Sent To  
Notes
2007-11-15 16:28:45*** PROVISO ***
 1) PROVIDE FOR VENTILATION PER 2004 FBC/M 502.5.1 AND
 ENGINEER'S LETTER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-06 Cont ID  
Sent By tgordon Date 2007-11-06 Time 09:28 Rev Time 0.30
Received By tgordon Date 2007-11-06 Time 09:28 Sent To  
Notes
2007-11-06 09:35:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW COMPLYANCE WITH 2004 FBC/M 502.3
 BATTERY-CHARGING AREAS. VENTILATION SHALL BE PROVIDED
 IN AN APPROVED MANNER IN BATTERY-CHARGING AREAS TO
 PREVENT A DANGEROUS ACCUMULATION OF FLAMMABLE GASES.
 502.4 STATIONARY LEAD-ACID BATTERY SYSTEMS. VENTILATION
 SHALL BE PROVIDED FOR STATIONARY LEAD-ACID BATTERY
 SYSTEMS IN ACCORDANCE WITH THIS CHAPTER AND SECTION
 502.4.1 OR 502.4.2.
 502.4.1 HYDROGEN LIMIT. THE VENTILATION SYSTEM
 SHALL BE DESIGNED TO LIMIT THE MAXIMUM CONCENTRATION OF
 HYDROGEN TO 1.0 PERCENT OF THE TOTAL VOLUME OF THE
 ROOM.
 502.4.2 VENTILATION RATE. CONTINUOUS VENTILATION
 SHALL BE PROVIDED AT A RATE OF NOT LESS THAN 1 CUBIC
 FOOT PER MINUTE PER SQUARE FOOT (CFM/FT 2 ) [0.00508 M
 3 /(S.M 2)] OF FLOOR AREA OF THE ROOM.
 502.5 VALVE-REGULATED LEAD-ACID BATTERIES.
 VALVE-REGULATED LEAD-ACID BATTERY SYSTEMS AS REGULATED
 BY THE FLORIDA FIRE PREVENTION CODE , SHALL BE PROVIDED
 WITH VENTILATION IN ACCORDANCE WITH SECTION 502.5.1 OR
 502.5.2 FOR ROOMS AND IN ACCORDANCE WITH SECTION
 502.5.3 OR 502.5.4 FOR CABINETS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-11-02 Cont ID  
Sent By choops Date 2007-11-02 Time 15:28 Rev Time 0.00
Received By choops Date 2007-11-02 Time 15:28 Sent To E
Notes
2007-11-02 15:31:07***APPROVED***
  
  
 SENT TO "E"