2007-12-06 14:58:29 | |
| |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| COMMENTS NOT ADDRESSED FROM THE PREVIOUS REVIEW. ALL |
| COMMENTS RELATE TO SHEET E1.0, UNLESS OTHERWISE NOTED. |
| |
| |
| 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS, |
| CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION |
| FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT.* THIS |
| COMMENT REFERS TO THE EQUIPMENT UNDER THE SCOPE OF WORK |
| ON THE APPLICATION. SEE COFFEE BREWER AND NOTE THERE IS |
| NO CIRCUIT NUMBER LISTED AT THE EQUIPMENT FOR THAT |
| ITEM. |
| |
| 2} ALL PLANS SUBMITTED FOR REVIEW MUST HAVE A CITY |
| PLACE STAMP. 106.1.3.* CORRECTED. |
| |
| 3} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE |
| LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED |
| UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC. THERE |
| ARE SEVERAL SHEETS SUBMITTED WITH THE APPLICATION, NONE |
| OF WHICH SEEM TO BE RELEVANT TO THE DESCRIPTION ON THE |
| APPLICATION.* NOW MISSING ONLY THE COFFEE BREWER ON |
| SHEET E1.0 |
| |
| 4} THE PERSON SEALING THE DOCUMENT MUST ALSO PRINT HIS |
| NAME IN THE TITLE BLOCK PER 61G1-16.004 FAC.* NO TITLE |
| BLOCK FOR THE ENGINEER WHO SEALED THE PLAN. SEE FS |
| 553.80(2)(B) MANDATORY FOUR TIMES THE FEE TO BE LEVIED |
| ON THE DESIGN PROFESSIONAL AFTER THE NEXT REVIEW WITH |
| THE SAME VIOLATIONS. ALSO ATTACHED TO THE PACKAGE. |
| |
| 5} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE |
| OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).* |
| NOT DONE AND NO RESPONSE GIVEN. |
| |
| PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| FBC AS AMENDED.* THIS COMMENT NOT ONLY WAS NOT |
| ADDRESSED, BUT ARTICLES 220.20, 220.20(A), 220.13 |
| REFERENCED ON SHEET E1.0 ARE NOT LISTED IN THE 2005 |
| CODE BUT IN THE 2002 CODE. CORRECT THE ARTICLES. |
| |
| PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO THE |
| COMMENTS MADE IN THIS REVIEW. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |