Plan Review Details - Permit 07100754
Plan Review Stops For Permit 07100754
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-03 Cont ID  
Sent By shill Date 2008-01-03 Time 11:32 Rev Time 0.00
Received By shill Date 2008-01-03 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 16:18 Rev Time 0.00
Received By shill Date 2007-11-08 Time 16:18 Sent To  
Notes
2007-11-08 16:19:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE SAFETY REQUIREMENTS ARE NOT COMPLIANT WITH FBC
 R4101.17.IT STATES "ONE OF THE FOLLOWING" BUT ITEMS 3
 AND 4 ARE TO BE USED IN COMBINATION WITH A PERIMETER
 FENCE; THIS APPLIES WHEN THE HOUSE IS A BARRIER.
 REVISE SAFETY NOTES.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-30 Cont ID  
Sent By btrobaug Date 2007-10-30 Time 14:20 Rev Time 0.00
Received By btrobaug Date 2007-10-30 Time 14:14 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-12-21 Cont ID  
Sent By mperson Date 2007-12-21 Time 16:05 Rev Time 0.00
Received By mperson Date 2007-12-21 Time 16:05 Sent To B
Notes
2007-12-21 16:06:49CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-11-07 Cont ID  
Sent By mperson Date 2007-11-07 Time 09:05 Rev Time 0.00
Received By mperson Date 2007-11-07 Time 09:05 Sent To Z
Notes
2007-11-07 09:06:24NOTE: REFERENCE PLUMBING PLAN REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 16:38 Sent To Z
Notes
2007-12-19 16:38:29TO "Z" BOX/RESUB

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-21 Cont ID  
Sent By mperson Date 2007-12-21 Time 15:46 Rev Time 0.00
Received By mperson Date 2007-12-21 Time 15:46 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-07 Cont ID  
Sent By mperson Date 2007-11-07 Time 08:56 Rev Time 0.00
Received By mperson Date 2007-11-07 Time 08:56 Sent To G
Notes
2007-11-07 09:04:50DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 &
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) PERMIT APPLICATION IS INDICATING AN ELECTRIC POOL
 HEATER, SHEET 1, POOL EQUIPMENT IS INDICATING A 400,000
 BTU GAS POOL HEATER. PLEASE CLARIFY AND CORRELATE WHICH
 TYPE OF POOL HEATER IS BEING USED ON THE RESUBMITTAL.
 PER * 106.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 14:00 Rev Time 0.00
Received By choops Date 2007-12-21 Time 14:00 Sent To P
Notes
2007-12-21 14:00:54***APPROVED - RESUB #1***
  
 FENCE ENCLOSURE ON PERMIT #07120340
  
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-07 Cont ID  
Sent By choops Date 2007-11-07 Time 13:45 Rev Time 0.00
Received By choops Date 2007-11-07 Time 13:45 Sent To B
Notes
2007-11-07 13:47:20***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM POOL EQUIPMENT TO
 ALL PROPERTY LINES.NOTE:MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4' INTO ANY REQUIRED SETBACK.
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
  