Plan Review Details - Permit 07100587
Plan Review Stops For Permit 07100587
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-02-21 Cont ID  
Sent By mjacobs Date 2008-02-21 Time 12:54 Rev Time 0.00
Received By mjacobs Date 2008-02-21 Time 12:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-10 Cont ID  
Sent By mjacobs Date 2008-01-10 Time 15:37 Rev Time 0.00
Received By mjacobs Date 2008-01-10 Time 15:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-03 Cont ID  
Sent By mjacobs Date 2008-01-03 Time 15:42 Rev Time 0.00
Received By mjacobs Date 2008-01-03 Time 15:39 Sent To PC
Notes
2008-01-03 15:40:22PERMIT: 07100587
 ADD: 222 LAKEVIEW AVE #1130
 CONT: MACO CONSTRUCTION SERVICES LLC
 TEL: (561)844-2225
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 1-3-08
 ACTION: DENIED
  
 1A)OK
  
 **NO RESPONSE NOT ADDRESSED**
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. THIS APPEARS TO
 BE A LEVEL 2 ALTERATION.
  
 3)OK
 6) OK
 5)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-13 Cont ID  
Sent By mjacobs Date 2007-12-13 Time 14:14 Rev Time 0.00
Received By mjacobs Date 2007-12-13 Time 11:08 Sent To  
Notes
2007-12-13 14:14:28BUILDING PLAN REVIEW
 PERMIT: 07100587
 ADD: 222 LAKEVIEW AVE #1130
 CONT: MACO CONSTRUCTION SERVICES LLC
 TEL: (561)844-2225
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 12/13/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)A FLOOR PLAN IS REQUIRED WITH ALL THE DIMENSIONS
 AND LAY-OUT OF THE SPACE. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL IT WILL CONFORM TO THE PROVISIONS OF THIS CODE
 AND. FBC 1061.1.
  
 4) SUBMIT TWO COMPLETE SIGNED AND SEALED SETS OF PLANS.
 IF THE DESIGN PROFESSIONAL IS AND ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE AS PROVIDED FOR
 IN CHAPTER 481, FLORIDA STATUTES, PART 1 OR ENGINEERING
 AS PROVIDED FOR IN CHAPTER 471 FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS. FBC 106.1
  
 5)NOTE: THREE PAGE OF THE REFLECTED CEILING PLAN WAS
 SUBMITTED. THERE IS NO FLOOR PLAN IN THE SETS
 THEREFORE; A THOROUGH REVIEW CANNOT BE ACHIEVED AT THIS
 TIME. ALSO ONE SET OF DRAWINGS IS NOT SIGNED AND
 SEALED. SUBMIT THE CORRECT INFORMATION FOR REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By mjacobs Date 2007-10-31 Time 18:34 Rev Time 0.00
Received By mjacobs Date 2007-10-31 Time 16:01 Sent To  
Notes
2007-10-31 18:33:58 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07100587
 ADD: 222 LAKEVIEW AVE #1130
 CONT: MACO CONSTRUCTION SERVICES LLC
 TEL: (561)844-2225
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 10/31/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 NOTE: FORM 400 A-2004 IS FOR THE PERFORMANCE OF THE
 WHOLE BUILDING. FBC 13-101.1.3 RENOVATED COMMERCIAL
 BUILDINGS SHALL COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400C OR WITH METHOD B OF
 SUBCHAPTER 13-4.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-02-16 Cont ID  
Sent By dpalmer Date 2008-02-16 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2008-02-16 Time 18:41 Sent To  
Notes
2008-02-16 18:42:17REV OK AND STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By dpalmer Date 2008-01-08 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2008-01-08 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 15:58 Sent To  
Notes
2007-12-22 15:58:34** DENIED 3RD REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE THE NOTE ON PREVIOUS REVIEW (NOTE
 #1) THE FORM(S) *C* SUBMITTED ARE THE EXACT SAME AS
 BEFORE. NO CHANGES WERE MADE.NO INFORMATION IS SHOWN
 ON HOW LIGHTING DENSITIES EXCEED THAT ON TABLES.
 PLEASE SEE THE SHEETS AS SUBMITTED SEEM TO FALL INTO A
 SPACE BY SPACE AS EACH SHEET (FORM 400C) SHOWS OFFICE,
 SERVER AND OFFICE. WHERE DOES THE 2.0 WATTS PER SQ FT
 COME FROM?
 TABLE *C* DOES NOT SHOW ANY ALLOWANCE OF 2.0 FOR ANY
 SERVER ROOM. PLEASE SEE TABLE *C* AS SERVER ROOM IS NOT
 A BUILDING AREA AS A WHOLE. PLEASE SEE THE CLOSEST ROOM
 DESIGNATION WOULD BE * ELECTRICAL/ MECHANICAL* ON TABLE
 *B*.
 PLEASE SEE 13-415.2, 13-415.2.B?
 PLEASE ALSO SEE AS THE SAME EXACT SHEET WERE SUBMITTED
 BACK, THEY ARE STILL NOT SIGNED, DATED AND SEALED AS
 REQUIRED PER FAC 61G15-23.002, FS 471.025 AND FBC
 13.101.1.1.1
  
 2) NOTE: NOTICE TO CONTRACTOR:
 PLEASE SEE THAT THE PLANS WERE SUBMITTED BACK AND A
 *SUBMITTAL* WHEN IN FACT THIS IS A RE-SUBMITTAL OF
 PLANS. THE RE-SUBMITTAL FEE WILL BE DUE FOR THIS RE-SUB
 AND THE FOLLOWING RE-SUB AS FULL REVIEWS FOR CODE
 COMPLIANCE ARE STILL BEING PERFORMED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-06 Cont ID  
Sent By dpalmer Date 2007-12-06 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2007-12-06 Time 11:47 Sent To  
Notes
2007-12-06 11:47:53** DENIED 2ND REVIEW **
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AS THERE IS
 NEED FOR SOME CORRECTIONS/ADJUSTMENTS.
  
  
 1) NOTE: PLEASE SEE THE PARTIALLY COMPLETED METHOD *C*
 SHEETS SUBMITTED. ONLY ONE OF THE SHEETS WERE SIGNED
 DATED AND SEAL.
 AS THE SPACE IS HAS EXISTING AIR CONDITIONING, THE
 ELECTRICAL REVIEW ONLY NEEDS LIGHTING PERFORMANCE
 CALCULATIONS. PLEASE SEE PART OF A CALCULATIONS SHEET
 MENTIONS A SERVER ROOM WITH A ALLOWANCE/DESIGN OF 2.0.
 PLEASE PROVIDE WHERE AN ALLOWANCE OF 2.0 COMES FROM.
 PLEASE ALSO SEE BASED ON THE FIXTURES ON PLANS AND SQ
 FT, THIS DOES NOT SEEM TO BE POSSIBLE?
 PLEASE KNOW IF USING SPACE BY SPACE, 13-415.2.B, OR
 13-415.2.C.1, THIS CAN BE DONE ON A TABLE OF SOME SORT.
 PLEASE CALL TO GO OVER.
  
 2) NOTE: PLEASE SHOW THE LOCATIONS OF NEW PANELS AND
 SERVICE EQUIPMENT WHICH IS BEING NOTED TO BE INSTALLED
 IN SPACE.
 110.26, 408.17, 240.24 ETC FOR REVIEW.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE SEE BOTH SETS OF PLANS ARE NOT
 COMPLETE. ONLY ONE SET CONTAINS ELECTRICAL SHEET. A E-2
 AND A E-3.
 PLEASE SUBMIT TWO COMPLETE SETS FOR REVIEW.
 106.1
  
 ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO
 GO OVER EXISTING WORK AND PROPOSED NEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By dpalmer Date 2007-10-29 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 12:24 Sent To  
Notes
2007-10-29 09:45:11 
  
 *** DENIED ***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 THIS IS REQUIRED FOR BOTH THE ARCHITECTURAL TITLE
 SHEETS AND ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE METHOD *A* ENERGY CALCULATIONS
 SUBMITTED MAY NOT BE USED. METHOD *A* IS FOR WHOLE
 BUILDING METHOD.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE COMPLETE THE FIXTURE LEGEND AND CORRELATE WITH
 THE LPC WHICH ARE TO BE SUBMITTED.
  
 3) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FIRE
 ALARMS DEVICES PER FBC 11-4.28.1,.2 AND .3(4).
  
 4) NOTE: PLEASE SEE 408.4, FBC 106.1, 106.3.5.1.2,
 106.3. PLEASE SEE THE CIRCUITS NEED TO BE SPECIFIC TO
 THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE USE OF RECEPTACLES NEEDS TO BE MORE
 SPECIFIC TO ROOM DESIGNATIONS. THIS CAN BE DONE BY
 ALPHA OR NUMERIC DESIGNATIONS.
  
 5) NOTE: PLEASE DO NOT ATTACH ANY SUPPORTING DOCUMENTS
 DOWN THE LEFT HAND SIDE OF PLANS. ** THIS IS NOTED AS
 THE DOCUMENTS WHICH WERE ATTACHED HAVE BEEN REMOVED.
  
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 11:12 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 11:05 Sent To  
Notes
2008-02-21 11:12:06*****REVISION APPROVED*****
  
 REVISED PLAN SHEETA1.1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By mawillia Date 2008-01-10 Time 14:37 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 14:17 Sent To  
Notes
2008-01-10 14:36:51*****APPROVED*****
  
 PREVIOUSLY APPROVED AND FIRE-STAMPED ON 01/03/2008;
 PLAN SHEETS A1.1, E2, AND FP1 WERE RE-STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-03 Cont ID  
Sent By mawillia Date 2008-01-03 Time 15:25 Rev Time 0.00
Received By mawillia Date 2008-01-03 Time 15:11 Sent To  
Notes
2008-01-03 15:25:43*****APPROVED*****
  
 PLAN SHEETS A1.1, E2, AND FP1 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-01-02 Cont ID  
Sent By mwennerg Date 2008-01-02 Time 10:29 Rev Time 0.00
Received By mwennerg Date 2008-01-02 Time 10:29 Sent To  
Notes
2008-01-02 10:40:56***DENIED***
  
 1) PLEASE NOTE THAT PLANS WERE PASSED DURING FIRST
 REVIEW BUT DENIED DURING SECOND REVIEW. SINCE THAT
 TIME, IT APPEARS THAT COMPLETE SETS OF DRAWINGS HAVE
 NOT BEEN SUBMITTED FOR REVIEW. IN ADDITION, ONLY ONE
 SET OF PLANS ARE SIGNED, SEALED AND DATED BY DESIGN
 PROFESSIONAL. A MINIMUM OF (2) COMPLETE SETS OF PLANS
 NEED TO BE SUBMITTED BEFORE APPROVAL AND STAMPING CAN
 BE COMPLETED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-12 Cont ID  
Sent By mwennerg Date 2007-12-12 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2007-12-12 Time 11:16 Sent To  
Notes
2007-12-12 11:18:16***DENIED***
  
  
 1) PLANS WERE APPROVED BY FIRE DURING FIRST REVIEW.
 PLEASE NOTE AS INDICATED BY OTHER REVIEW COMMENTS THAT
 SUBMITTAL IS NOT COMPLETE. PLEASE SUBMIT ALL
 APPROPRIATE SHEETS FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-11-01 Cont ID  
Sent By mwennerg Date 2007-11-01 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2007-11-01 Time 14:48 Sent To  
Notes
2007-11-01 14:52:37APPROVED/PROVISO
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL PRIOR TO WORK ON
 SYSTEM.
  
 2) INCORRECT NFPA 101 CODE EDITIONS INDICATED ON SHEET
 A4.1. PLEASE MAKE CORRECTION USING 2003 EDITION FOR
 REFERENCE.
  
 PLANS WILL BE STAMPED WHEN RETURNED FOR OTHER REVIEW
 CORRECTIONS IN ADDITION TO FIRE REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-15 Cont ID  
Sent By adarroug Date 2008-02-15 Time 10:16 Rev Time 0.00
Received By adarroug Date 2008-02-15 Time 10:16 Sent To  
Notes
2008-02-15 10:19:44TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-07 Cont ID  
Sent By shill Date 2008-01-07 Time 16:41 Rev Time 0.00
Received By shill Date 2008-01-07 Time 16:41 Sent To  
Notes
2008-01-07 16:49:37TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 11:01 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 11:01 Sent To  
Notes
2007-12-21 17:06:19TO "BOB" # 912/21/07 SPALMER
2007-12-19 11:02:17WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 09:06 Sent To  
Notes
2007-12-06 09:06:22TO "BOB"#9
2007-12-03 09:06:59WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-08 Cont ID  
Sent By jleech Date 2007-11-08 Time 08:53 Rev Time 0.00
Received By jleech Date 2007-10-22 Time 09:30 Sent To  
Notes
2007-10-27 12:24:512007-10-27 12:24:51
 TO BOB BOARD SPACE #12
2007-10-22 09:30:38WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By tgordon Date 2008-01-08 Time 11:52 Rev Time 0.30
Received By tgordon Date 2008-01-08 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 13:59 Rev Time 0.30
Received By tgordon Date 2007-12-26 Time 13:59 Sent To  
Notes
2007-12-26 14:08:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 ** SAME MECHANICAL PLANS SIGNED AND SEALED 10-16-07
 WITH NO CORRECTIONS ON THEM WERE RE-SUBMITTED 12-18-07.
 **
  
 1) AS NOTED IN LAST TWO REVIEWS 12-7-07 AND 10-31-07.
 COOLING LOAD CALCULATIONS FOR HP-1 ARE CALLING FOR
 34,625 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 2) AS NOTED IN LAST TWO REVIEWS 12-7-07 AND 10-31-07.
 COOLING LOAD CALCULATIONS FOR HP-2 ARE CALLING FOR
 33,016 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-12-07 Cont ID  
Sent By tgordon Date 2007-12-07 Time 09:41 Rev Time 0.40
Received By tgordon Date 2007-12-07 Time 09:41 Sent To  
Notes
2007-12-07 10:04:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-31-07. COOLING LOAD
 CALCULATIONS FOR HP-1 ARE CALLING FOR 34,625 TOTAL
 BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS SHOWING 42,000
 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR MORE THAN THE
 COOLING LOAD CAL'S., SEE 2004 FBC 13-407.1.ABC.1.1.
 PLEASE CORRECT. ( RESPONSE RECEIVED WAS ADDRESSING THE
 SENSIBLE COOLING BTU'S. AT 37,800). THE BUILDING CODE
 REQUIREMENT ADDRESS TOTAL BTU'S. NOT SENSIBLE BTU'S.
 PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 10-31-07. COOLING LOAD
 CALCULATIONS FOR HP-2 ARE CALLING FOR 33,016 TOTAL
 BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS SHOWING 42,000
 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR MORE THAN THE
 COOLING LOAD CAL'S., SEE 2004 FBC 13-407.1.ABC.1.1.
 PLEASE CORRECT. (SEE NOTE 1 RESPONSE).
  
 *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 3) ONLY ONE SET OF SUBMITTED PLANS HAD MECHANICAL PLANS
 PAGE M1 AND M2 IN THEM, AND THEY WERE NOT SIGNED AND
 SEALED BY THE ENGINEER, SEE 61G15-23.002. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By tgordon Date 2007-10-31 Time 10:54 Rev Time 0.45
Received By tgordon Date 2007-10-31 Time 10:53 Sent To  
Notes
2007-10-31 11:04:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS FOR HP-1 ARE CALLING FOR
 34,625 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS FOR HP-2 ARE CALLING FOR
 33,016 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-10 Cont ID  
Sent By jleech Date 2008-01-10 Time 07:59 Rev Time 0.00
Received By jleech Date 2008-01-10 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 10:24 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 10:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 05:53 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 05:53 Sent To  
Notes
2007-12-15 05:54:49DENIED;
 "P" PAGES ARE MISSING FROM PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-11-08 Cont ID  
Sent By jleech Date 2007-11-08 Time 08:53 Rev Time 0.00
Received By jleech Date 2007-11-08 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-11-02 Cont ID  
Sent By choops Date 2007-11-02 Time 10:43 Rev Time 0.00
Received By choops Date 2007-11-02 Time 10:43 Sent To  
Notes
2007-11-02 10:44:11*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.