Plan Review Details - Permit 07100564
Plan Review Stops For Permit 07100564
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-18 Cont ID  
Sent By rmcdouga Date 2008-03-18 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2008-03-18 Time 14:51 Sent To  
Notes
2008-03-18 14:52:52REVISED SHEET S-1 REVIEWED FOR CODE COMPLIANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-07 Cont ID  
Sent By rmcdouga Date 2008-03-07 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2008-03-07 Time 12:50 Sent To  
Notes
2008-03-07 13:32:41REVISIONS TO SHEET SP-1 AND S-1 CAN NOT BE APPROVED BY
 BUILDING, UNTIL ZONING COMMENTS HAVE BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-07 Cont ID  
Sent By rmcdouga Date 2008-01-07 Time 12:24 Rev Time 0.00
Received By rmcdouga Date 2008-01-07 Time 12:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-14 Cont ID  
Sent By rmcdouga Date 2007-12-14 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2007-12-14 Time 07:25 Sent To  
Notes
2007-12-14 11:38:262004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ON SHEET SP-1 THE OCCUPANCY TYPE IS INCORRECTLY
 SPECIFIED AS R-2. IT SHOULD BE R-3 FOR A SINGLE FAMILY
 DWELLING. FBC CHAPTER 3.
  
 3) ALSO ON SP-1 THE CODE SHOULD BE THE 2004 FBC WITH
 2007 REVISIONS.
  
 4) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS IN THE SCHEDULE ON SHEET S-3. SEE FBC R
 301.2(2).
  
 5) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING
 GLAZED DOORS WITH SIDELITES (OXXO). SEE FAC RULE9B-72.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE SINGLE OUTSWING
 GLAZED DOOR WITH SIDELITES (X) SEE FAC RULE 9B-72.
  
 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 JELD-WEN AWNINGAND CASEMENT WINDOWS DO NOT INDICATE
 IF THEY ARE IMPACT RESISTANT. SUBMIT THIS INFORMATION
 OR PROVIDE IMPACT PROTECTION AS REQUIRED BY FBC R
 301.2.1.2.
  
 8) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 EASTERN METAL SUPPLY STORM PANEL PRODUCT APPROVALS THAT
 WERE SUBMITTED. SPECIFY WHICH OPENINGS WILL BE
 SHUTTERED. SPECIFY THE MOUNT TYPE, ANCHOR TYPE, ANCHOR
 SPACING, ETC. SEE ATTACHED INSTALLATION SCHEDULE. FBC
 106.1.2* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By rmcdouga Date 2007-11-05 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2007-11-05 Time 10:44 Sent To E
Notes
2007-11-05 14:00:362004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON EACH DRAWING.
 FBC * 106.1.2 QUALITY OF PLANS
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1 CITY AMENDMENTS.
  
 4) PROVIDE DIMENSIONS ON THE PLANS FOR THE NEW WALLS,
 OPENINGS, ROOMS, WINDOWS, DOORS, ETC.SPECIFY THE
 WINDOW TYPES AND SIZES ON THE DRAWINGS. FBC 106.1.1
 CITY AMENDMENTS.
  
 5) PROVIDE WALL SECTIONS FOR INTERIOR WALLS. INDICATE
 THE MATERIAL, SIZE AND SPACING OF FRAMING.F.B.C.
 106.1.1 CITY AMENDMENTS.
  
 6) THE EXTERIOR WALL FRAMING DETAIL FOR THE NEW WINDOWS
 AND DOORS DOES NOT CONTAIN ENOUGH INFORMATION. SPECIFY
 THE FRAMING MATERIAL, SPACING, HEADER SIZES, OPENING
 SIZES, NUMBER OF JACKS, INSULATION, INTERIOR AND
 EXTERIOR WALL COVERINGS, SHOW ADEQUATE SUBSTRATE FOR
 ATTACHING STORM PANELS, SPECIFY THE CONNECTORS THAT
 WILL BE USED. BE SPECIFIC. FBC 106.1.1 CITY
 AMENDMENTS.
  
 7)FBC 1606.1.4SHUTTERS.
 INSTALLATION/DESIGN INFORMATION
 REQUIRED.SUBMIT AN INSTALLATION
 SCHEDULE INCLUDING THE FOLLOWING
 DETAILS:
 (A) BUILDING CONSTRUCTION TYPE (EG CBS)
 (B) BUILDING (OR INSTALLATION) HEIGHT
 (C) DESIGN PRESSURE FOR EACH OPENING
 (D) OPENING SIZES
 (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?)
 (F) ANCHOR TYPE, SIZE AND SPACING
 A FORM IS AVAILABLE FROM THIS OFFICE
 GIVING THE RECOMMENDED INSTALLATION
 SCHEDULE FORMAT.SUBMIT THE ABOVE
 INFORMATION WHICH IS REQUIRED FOR
 REVIEW.
  
 8) THE PRODUCT APPROVAL SUBMITTED FOR THE FRENCH DOOR
 IS FOR A SINGLE OUTSWING DOOR WITH SIDELITES (OXO). THE
 DRAWINGS INDICATE A DOUBLE OUTSWING DOOR WITH NO
 SIDELITES INDICATED. PLEASE CLARIFY.
  
 9) THE PRODUCT APPROVAL SUBMITTED FOR THE STORM PANELS
 IS INCOMPLETE. THE INSTALLATION DRAWINGS 05-078 SHEETS
 1-15 ARE MISSING. SEE RULE FAC 9B-72.
  
 10) THE PRODUCT APPROVALS SUBMITTED FOR THE JELD-WEN
 CASEMENT AND AWNING WINDOWS DO NOT SPECIFY THE DESIGN
 PRESSURES. THE DESIGN PRESSURES ARE REQUIRED TO
 DETERMINE IF THE WINDOWS MEET THE COMPONENT AND
 CLADDING PRESSURES FOR THE STRUCTURE. SEE FBC TABLE
 R301.2(2).
  
 11)106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By btrobaug Date 2008-03-03 Time 11:29 Rev Time 0.00
Received By btrobaug Date 2008-03-03 Time 11:06 Sent To B
Notes
2008-03-03 11:27:16 
  
 REFERENCED 680.26(C) FOR NEW PAVERS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-11-07 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 16:09 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 15:24 Sent To P
Notes
2007-11-07 16:56:32 
  
 SEPERATE ELECTRICAL PERMIT PULLED #07100048./WRT.
2007-11-05 16:08:58 

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-03-03 Cont ID  
Sent By ssherman Date 2008-03-03 Time 11:12 Rev Time 0.00
Received By ssherman Date 2008-02-25 Time 14:16 Sent To  
Notes
2008-02-25 14:17:16HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-18 Cont ID  
Sent By adarroug Date 2008-03-18 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-03-18 Time 09:10 Sent To B
Notes
2008-03-18 09:11:07TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 10:17 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 10:17 Sent To Z
Notes
2008-02-26 10:17:36TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 15:33 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 15:33 Sent To B
Notes
2007-12-27 15:33:50TO ROBERT MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 10:57 Sent To B
Notes
2007-12-07 10:57:29TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-06 Cont ID  
Sent By mperson Date 2007-11-06 Time 11:55 Rev Time 0.00
Received By mperson Date 2007-10-18 Time 15:45 Sent To  
Notes
2007-10-18 15:45:29TO "MISC" BOX#1

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-11-06 Cont ID  
Sent By btrobaug Date 2007-11-07 Time 16:55 Rev Time 0.00
Received By mperson Date 2007-11-06 Time 11:47 Sent To PC
Notes
2007-11-06 11:55:29NOTE: THERE IS A SEPERATE PLUMBING PERMIT #07090797,
 THAT HAS BEEN APPLIED FOR ON 9/30/07. PER ROBERT
 BROWN'S INSTRUCTIONS THIS MASTER PERMIT NUMBER WILL BE
 ATTACHED TO THE PLUMBING PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By choops Date 2008-02-27 Time 10:52 Rev Time 0.00
Received By choops Date 2008-02-27 Time 10:52 Sent To B
Notes
2008-02-27 11:02:30***FAILED - REVISION - CHANGING HEADER DETAIL, CHANGES
 TO SITE PLAN, ADDING FRONT PIERS/FENCING, ADDING D/W
 AND PAVER POOL DECK. (ZONING 1ST REVIEW)
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS/GATES.
  
 3)AS THIS IS A DUAL FRONTAGE LOT, PLEASE INDICATE
 SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES LOCATED
 WITHIN BOTH FRONT YARDS (FROM FRONT PROPERTY LINE TO
 THE FRONT BUILDING FACADE).PURSUANT TO SECTION 94-482
 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS):
 REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD;
 HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT
 OF THE FRONT YARD AREA MUST BE LANDSCAPED.
  
 4)SITE PLAN INDICATES NEW GRAVEL DRIVEWAYS, GRAVEL
 IS NOT PERMITTED AS PER SECTION 94-482 OF THE ZLDRS:
 PARKING AREAS SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE.
  
 5)IS BACK PORCH ADDITION EXISTING OR PROPOSED?IF
 EXISTING, WAS IT BUILT WITH HOUSE OR LEGALLY PERMITTED
 AS AN ADDITION?PLEASE CLARIFY.
  
 6)INDICATE HEIGHT OF PROPOSED SLIDING GATE AND POSTS
 LOCATED ALONG SOPHIA DRIVE.MAY NOT EXCEED 4 FEET IN
 HEIGHT AS THIS IS A DUAL FRONTAGE LOT.
  
 7)INDICATE IF APPROACH IS TO BE REDONE OR ADDED.IF
 SO, A FURTHER REVEIW BY THE CITY'S ENGINEERING
 DEPARTMENT WILL BE REQUIRED.
  
  
 NOTE:THE ADDITION OF GATES SHALL NOT CAUSE TRAFFIC
 STACKING WHILE WAITING TO BE OPENED.
  
 NOTE:ANY RELOCATED OR PROPOSED POOL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK AS
 PER SECTION 94-305(B)(4) OF THE ZLDRS.
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT