Plan Review Details - Permit 07100528
Plan Review Stops For Permit 07100528
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-11 Cont ID  
Sent By mjacobs Date 2007-12-11 Time 11:06 Rev Time 0.00
Received By mjacobs Date 2007-12-11 Time 10:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-03 Cont ID  
Sent By mjacobs Date 2007-11-03 Time 10:42 Rev Time 0.00
Received By mjacobs Date 2007-11-03 Time 09:54 Sent To PC
Notes
2007-11-03 10:42:31 
 BUILDING PLAN REVIEW
 PERMIT: 07100528
 ADD:230 MIRAMAR WAY
 CONT: ALMAR /JACKSON POOLS INC
 TEL: (561)746-4910
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 11-3-07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. THE EQUIPMENT LEGEND
 INDICATES AN ELECTRIC HEAT PUMP HOWEVER, THE POOL
 SPECIFICATIONS SHOWS A GAS HEATER. THE APPLICATION
 INDICATES SWIMMING POOL AND SPA; HOWEVER THE DRAWINGS
 DO NOT SHOW A SPA. CLARIFY. SEE PLUMBING NOTES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-05 Cont ID  
Sent By btrobaug Date 2007-12-05 Time 11:52 Rev Time 0.00
Received By btrobaug Date 2007-12-05 Time 09:32 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-10-23 Time 14:00 Rev Time 0.00
Received By btrobaug Date 2007-10-23 Time 13:51 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-12-07 Cont ID  
Sent By mperson Date 2007-12-07 Time 15:22 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 15:22 Sent To B
Notes
2007-12-07 15:23:21CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-11-01 Cont ID  
Sent By mperson Date 2007-11-01 Time 10:17 Rev Time 0.00
Received By mperson Date 2007-11-01 Time 10:17 Sent To B
Notes
2007-11-01 10:18:49CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 15:30 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 15:30 Sent To Z
Notes
2007-11-30 15:30:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-11-05 Time   Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 10:51 Sent To  
Notes
2007-10-18 10:51:45TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-07 Cont ID  
Sent By mperson Date 2007-12-07 Time 15:21 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 15:21 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-01 Cont ID  
Sent By mperson Date 2007-11-01 Time 09:20 Rev Time 0.00
Received By mperson Date 2007-11-01 Time 09:20 Sent To G
Notes
2007-11-01 10:10:54DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 &
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE EQUIPMENT LAYOUT IS MISLABELED, PLEASE
 CORRELATE THE EQUIPMENT LAYOUT WITH THE LEGEND AND
 CORRECT THE FOLLOWING PER **106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A} THE 2 HP PUMP IS MISLABELED AS "B", IT SHOULD BE
 "A".
  
 B} THE FILTER IS MISLABELED AS "C", IT SHOULD BE "B".
  
 C} THE 1-1/2" WASTE OR DISCHARGE IS MISLABELED AS "D",
 IT SHOULD BE "C".
  
 D} THE HEATER IS MISLABELED AS "E", IT SHOULD BE "D".
  
 E} THE VALVES ARE MISLABELED AS "F", THEY SHOULD BE
 "E".
  
 F} THE 1-1/2" POOL RETURN LINE IS MISLABELED AS "3",
 IT SHOULD BE "4".
  
 2. PLANS INDICATE "PROVIDE AUTO-FILL". PLEASE INDICATE
 ON THE RESUBMITTED PLANS THE FOLLOWING "POTABLE WATER
 SUPPLY TO AUTO-FILL WITH SHUT OFF VALVE AND BACKFLOW
 PROTECTION PER FBC-2004 W/05 & 06 REV. SEC. 608, AND TO
 BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR".
  
 3. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 4. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By choops Date 2007-12-03 Time 15:18 Rev Time 0.00
Received By choops Date 2007-12-03 Time 15:18 Sent To E
Notes
2007-12-03 15:19:31***APPROVED - RESUB #1***
  
  
 FENCE ENCLOSURE UNDER PERMIT #07110400
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By choops Date 2007-10-22 Time 17:29 Rev Time 0.00
Received By choops Date 2007-10-22 Time 17:29 Sent To E
Notes
2007-10-22 17:32:10***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM POOL EQUIPMENT TO
 THE PROPERTY LINES.NOTE:MAY NOT PROJECT MORE THAN
 4' INTO A REQUIRED SETBACK.
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720