Sent To |
|
|
Notes |
2007-10-28 10:39:22 | A NOTICE OF COMMENCEMENT WILL BE REQUIRED IF INSTALLED | | ON PRIVATE PROPERTY, PLEASE EXPLAIN CAMERA LOCATION AT | | GOOD SAMARITAN HOSPITAL. | | | | PROVIDE COMPLETE FASTENING DETAILS. | | | | | | | | | | | | L.MARTINEZ | | 561-805-6710 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-06 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-06 |
Time |
08:20 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-10-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-10-26 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-10-26 |
Time |
11:16 |
Sent To |
B |
|
Notes |
2007-10-26 11:21:18 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS, | | CONDUIT AND CONDUCTOR SIZE AND TYPE, AND OCP FOR THE | | EQUIPMENT BEING WIRED UNDER THIS PERMIT. 106.3.5.1.2 | | FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-28 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2007-10-28 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2007-10-18 |
Time |
10:14 |
Sent To |
|
|
Notes |
2007-10-18 10:14:44 | TO "E" BOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-11-06 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-11-06 |
Time |
10:56 |
Sent To |
B |
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |