Plan Review Details - Permit 07100501
Plan Review Stops For Permit 07100501
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-27 Cont ID  
Sent By shill Date 2008-02-27 Time 17:44 Rev Time 0.00
Received By shill Date 2008-02-27 Time 17:44 Sent To  
Notes
2008-02-27 17:45:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE PROVIDE THE AMOUNT OF ADDITIONAL VALUE FOR
 THIS REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 08:03 Rev Time 0.00
Received By shill Date 2007-11-08 Time 08:03 Sent To  
Notes
2007-11-08 08:04:19***PROVISO***
  
 SAMANTHA M HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
  
 REPAIR PERMIT; REPLACEMENT OF DAMAGED DRYWALL AND
 INSULATION IN CAFE & DINING ROOM ONLY PER INSPECTOR BOB
 TILLEY, OWNER IS REQUIRED TO SUBMIT PLANS FOR REPAIRS
 AND ALTERATIONS IN THE KITCHEN, DISHWASHER/ELECT PANEL
 ROOMS
  
  
 NOTE - CONTRACTOR REMOVED ALTERATION FROM SCOPE OF WORK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By shill Date 2007-10-23 Time 18:37 Rev Time 0.00
Received By shill Date 2007-10-23 Time 18:37 Sent To E
Notes
2007-10-23 18:53:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.COMMERCIAL PROJECTS DO NOT FALL UNDER THE
 EXCEPTIONS TO ARCHITECTURE, FS481.229.PROVIDE PLANS
 PREPARED BY A DESIGN PROFESSIONAL (ARCHITECT OR
 ENGINEER).
  
 2.PLANS ARE TO INCLUDE ALL INFORMATION REQUIRED TO
 SHOW CODE COMPLIANCE.PLANS DID NOT PROVIDE ANY
 INFORMATION.
  
 3.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 4.SHOW HOW EGRESS WILL BE AFFECTED.PROVIDE ALL
 DIMENSIONS.FBC CHAPTER 10.
  
 5.PROVIDE A CODE SUMMARY REGARDING THE EXISTING
 BUILDING; BUILDING TYPE FBC6, BUILDING HEIGHT AND AREA
 FBC5, SPRINKLER INFORMATION, OCCUPANCY CLASSIFICATION
 FBC 3 AND AREA PER OCCUPANCY.
  
 6.PROVIDE AN ARCHITECTURAL QUALITY DETAIL FOR THE
 KNEE WALL, DRAWN TO SCALE, FBC*106.NO DIMENSIONS FOR
 FRAMING MATERIAL OR FASTENERS WAS PROVIDED.
  
 7.PROVIDE A LEGEND.CIRCLES ARE SHOWN ON THE NEW
 WALL, BUT IT IS NOT CLEAR WHAT THEY REPRESENT.ARE
 THEY OUTLETS?TWO DIFFERENT CIRCLE GRAPHICS ARE SHOWN.
  
  
 8.A PORTION OF THE WALL WAS HIGHLIGHTED.HIGHLIGHTER
 CANNOT BE USED TO SHOW CODE COMPLIANCE AS IT DOES NOT
 APPEAR WHEN SCANNED.USE STANDARD ARCHITECTURAL
 GRAPHICS AND MARKERS.
  
 9.SHOW HOW ACCESSIBILITY WILL BE AFFECTED.A
 SWINGING DOOR IS SHOWN WITH NO DIMENSIONS OR OTHER
 INFORMATION, FBC11-4.13.
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-11-14 Cont ID  
Sent By btrobaug Date 2007-10-29 Time 09:42 Rev Time 0.00
Received By btrobaug Date 2007-10-29 Time 09:22 Sent To FIRE
Notes
2007-10-29 09:42:12 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES. 106.3.5 FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 3} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.NOTE SAME ON THE PLAN.
  
 4} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 5} INDICATE COMPLIANCE WITH 210.8(B)(2), GFCI ON THE
 PLAN.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-03-04 Cont ID  
Sent By mawillia Date 2008-03-04 Time 10:23 Rev Time 0.00
Received By mawillia Date 2008-03-04 Time 10:12 Sent To  
Notes
2008-03-04 10:16:30*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET SHOWING THE INSTALLATION OF THE HC
 RAILING WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2007-11-14 Cont ID  
Sent By shill Date 2007-11-14 Time 16:57 Rev Time 0.00
Received By shill Date 2007-11-14 Time 16:57 Sent To  
Notes
2007-11-14 16:59:05****PROVISO****
  
 PLANS/PERMIT REQUIRED FOR REPAIRS AND ALTERATIONS IN
 KITCHEN, DISHWASHER/ELECTRIC PANEL ROOMS
  
 OK PER MIKE CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By btrobaug Date 2007-11-14 Time 16:51 Rev Time 0.00
Received By mawillia Date 2007-10-29 Time 12:51 Sent To  
Notes
2007-10-29 13:16:42*****DENIED*****
  
  
  
 1.THE PROJECT SITE LOCATION SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALL IN TERMS OF CLASS A, CLAAS B, OR CLASS C.
  
 5.PLEASE SHOW PATH OF TRAVEL AISLE CLEARANCE ONCE THE
 WALL IS ERECTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-22 Cont ID  
Sent By adarroug Date 2008-02-22 Time 12:03 Rev Time 0.00
Received By adarroug Date 2008-02-22 Time 12:03 Sent To B
Notes
2008-02-25 12:47:322/25/08--PLANS SUBMITTED BACK IN AS REV, ROUTED TO
 "COMM" BD#61(SEE FRONT SCREEN NOTES)
2008-02-22 12:04:06TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 08:56 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 08:56 Sent To E
Notes
2007-10-24 08:56:44TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-23 Cont ID  
Sent By shill Date 2007-10-23 Time 18:53 Rev Time 0.00
Received By shill Date 2007-10-17 Time 14:35 Sent To  
Notes
2007-10-17 14:42:29TO "MISC" BOX#1--OK TO ROUTE TO "MISC" BOX PER ROBERT
 BROWN.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-02-26 Cont ID  
Sent By choops Date 2008-02-26 Time 11:17 Rev Time 0.00
Received By choops Date 2008-02-26 Time 11:17 Sent To  
Notes
2008-02-26 11:19:52***APPROVED - REVISION - ADDING 3 FOOT HANDICAP RAILING
 AT WEST ENTRY AND SOUTH BATHROOM ENTRY***