Plan Review Details - Permit 07100482
Plan Review Stops For Permit 07100482
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-10-19 Cont ID  
Sent By lursu Date 2007-10-19 Time 08:59 Rev Time 0.00
Received By lursu Date 2007-10-19 Time 08:59 Sent To  
Notes
2007-10-19 08:59:23IF THE STRUCTURE IS DIVIDED IN MULTIPLE UNITS ,THEN
 EACH UNIT MUST HAVE A UNIQUE NUMBER ASSIGNED TO IT.THE
 UNIT NUMBER WILL BE THE SITE ADDRESS FOR THAT UNIT.THE
 NUMBERING OF THE UNITS MUST START AT THE EAST PORTION
 OF THE STRUCTURE GOING HIGHER TO THE WEST.
 PLEASE CLARIFY IN WHICH UNIT THE JOB IS LOCATED?
 IF YOU HAVE ANY QUESTION PLEASE CONTACT ME.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By kconrad Date 2007-11-05 Time 19:21 Rev Time 0.00
Received By kconrad Date 2007-11-05 Time 15:48 Sent To I
Notes
2007-11-05 16:50:20PROJECT: 2223 PALM BEACH LAKES BLVD.
  
 PROJECT DETAIL: INTERIOR ALTERATION FOR NEW OUTPATIENT
 CLINIC
  
  
 CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE
 W/2006 REVISIONS.
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS.
 CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE
 ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION.
  
 STATUS: FAILED
  
  
 COMMENTS:
  
 1) PLEASE CONTACT MR. ALEX ORTEGA WITH THE PALM BEACH
 COUNTY HEALTH DEPARTMENT PRIOR TO ANY DEMOLITION AT
 355.3023,EXT.1148. AN ASBESTOS SURVEY MAY BE REQUIRED
 AS PER THE FOLLOWING:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION
 301.5:
  
 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 4) PLEASE SATISFY PREVIOUS ADDRESSING REQUIREMENTS.
  
 5) PROVIDE FIRE EXTINGUISHERS AS REQUIRED:
  
 SECTION 1309
 FIRE EXTINGUISHERS
 1309.1WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND
 SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATE
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 6) PLEASE PROVIDE PRODUCT APPROVALS/ENGINEERING FOR THE
 FOLLOWING:
  
 A) SPECIFICATIONS FOR 1 HOUR RATED GLASS DOOR AND
 STOREFRONT FRAMING SYSTEM.(MARK A).
 B) 1 HOUR RATED DOOR.( MARK B).
 C) DOOR INDICATED AT MARK E.
 D) EXIT DOOR AT WEST BUILDING ELEVATION.
 E) PRE-CAST CONCRETE LINTELS.
  
 7) PROVIDE CLARIFICATION FOR THE FOLLOWING STATEMENT:
  
 *TENANT EXITS UNDER SEPARATE PERMIT, SHEET A-3.
  
 8) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE
  
 SECTION 611
 ENERGY CONSERVATION
 611.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 9) SIZE OF RATED GLAZING SHALL MEET THE NFPA80
 STANDARDS AS PER THE FBC, PLEASE INDICATE THE TOTAL
 SQUARE AREA OF GLAZING PER UNIT:
  
 715.4.4 NONWIRED GLASS.
 GLAZING OTHER THAN WIRED GLASS IN FIRE WINDOW
 ASSEMBLIES SHALL BE FIRE-PROTECTION-RATED GLAZING
 INSTALLED IN ACCORDANCE WITH AND COMPLYING WITH THE
 SIZE LIMITATIONS SET FORTH IN NFPA 80.
  
 10) PLEASE SUBMIT EPOXY AND CONCRETE SPECIFICATIONS.
  
 11) PLEASE PROVIDE DETAIL SECTION NUMBER AT 14' ROUGH
 OPENING.
  
 12) WHERE IS DETAIL 2A/A-2??
  
 13) MARK E MEANS EXISTING ON SHEET A-3? PLEASE CLARIFY
 DOOR SCHEDULE.
  
 14) PLEASE PROVIDE LISTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAILS FOR THROUGH PENETRATIONS:
  
 FLORIDA BUILDING CODE
  
 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 15) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION
 605.4.1.1, AN ADDITIONAL EXIT IS REQUIRED FOR SUITE
 "B":
  
 605.4.1.1OCCUPANT LOAD AND TRAVEL DISTANCE.
  
 IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN
 OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL
 DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL
 HAVE A MINIMUM OF TWOEGRESS DOORWAYS.
 EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES
 HAVING A MAXIMUM OCCUPANT LOAD OF 10.
  
 16) PLEASE PROVIDE DETAILS FOR THE EXISTING BATHROOMS.
 A BUILDING THAT IS ALTERED SHALL COMPLY WITH FBC,
 CHAPTER 11:
  
 606.1GENERAL.
 A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 17) THE VALUATION FOR THE PROPOSED SCOPE OF WORK
 APPEARS TO BE LOW AND SHOULD BE ADJUSTED TO REFLECT THE
 SAME.
  
 *********END OF REVIEW********
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 09:10 Sent To  
Notes
2007-11-07 10:12:25** DENIED **
  
 1) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR SCOPE OF
 WORK.
 PLEASE SEE THAT ALL RELEVANT CODES AS FOLLOWS ARE TO BE
 STATED ON DRAWINGS.
 2004 FBC W2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SUBMIT AN ELECTRICAL RISER COMPLYING
 WITH THE NEC.
 PLEASE SEE 230.2 AS THE SERVICE(S) AS SHOWN ARE NOT
 PERMITTED.
 PLEASE SEE MORE THAN SIX MAINS ARE SHOWN WHICH IS NOT
 PERMITTED. 230.70,230.71,230.72 ETC
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR ALL LOADS.
 220.
 PLEASE SEE 110.9 FOR COMPLETE AIC RATINGS FOR ALL.
 PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AS
 REQUIRED PER 250.50,250.66 ETC
 PLEASE INDICATE ALL CONDUCTORS AND OVER CURRENT
 PROTECTION WHICH COMPLIES WITH THE NEC 310.16, 240.4.
 EXAMPLE: 5/0 CONDUCTORS ARE SHOWN. THERE IS NOT SUCH
 WIRE SIZE BASED ON THE AWG AMERICAN WIRE GAUGE.
  
 ** PLEASE KNOW AS THERE ARE TOO NUMEROUS CHANGES
 REQUIRED A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT
 BE DONE AT THIS TIME.
 PLEASE KNOW THE PLANS FOR POSSIBLE BUILD OUT WILL BE
 AFFECTED AS WELL.
  
 3) NOTE: PLEASE SEE 700.12F AS THE CIRCUITING FOR
 EMERGENCY LIGHT FIXTURES SHALL BE CIRCUITED TO THE
 BRANCH CIRCUIT OF THE LOCAL LIGHTING.
  
 4) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING AND
 INTENDED SCOPE OF WORK,
 FBC 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE SEE NEC 517.1 AS WIRING METHOD FOR THIS
 SPACE IS REQUIRED TO MEET CODE. PLEASE ADJUST PLANS AND
 DESIGN FOR THIS.
  
 6) NOTE: PLEASE SUBMIT COMPLETE INFORMATION FOR FBC
 CHAPTER 13 REQUIREMENTS.
 PLEASE SEE 13-413.1.ABC.1.1, AND .1.2
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS.
 ETC
  
 7) NOTE: PLEASE SEE ADDRESSING AS ALL UNIT/SUITE
 NUMBERS WILL BE REQUIRED ON PLANS.
  
 8) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS SHOWN SHALL INCLUDE ALL LABOR, MATERIALS,
 DESIGN COST, EQUIPMENT ETC EVEN IF ANY OF THIS IS OWNER
 SUPPLIED. THE VALUE FOR SCOPE SHOWN IS LOW.
 FBC 108.3
  
  
 *** PLEASE KNOW AS BASED ON THE MANY CHANGES WHICH WILL
 BE REQUIRED, THERE MAY VERY WELL BE NEW COMMENTS ON THE
 FOLLOWING REVIEW AS THERE ARE MANY ITEMS MISSING FROM
 PLANS. THESE ITEMS AND CHANGES CAN NOT BE REVIEWED AT
 THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-14 Cont ID  
Sent By mcarsill Date 2007-11-14 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2007-11-14 Time 09:29 Sent To  
Notes
2007-11-14 09:47:151. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 3. THE NEW TENANT PARTITIONS SHOULD BE CALLED OUT ON
 THE PLANS AS ONE HOUR FIRE RATED TENANT DEMISING WALLS
 AS INDICATED IN THE WALL DETAIL.
  
 4. PORTABLE FIRE EXTINGUISHERS ILLUSTRATED ON PLANS
 SHALL BE CURRENTLY SERVICE TAGGED.
  
 5. ALL FUTURE TENANT BUILD-OUT SPACES SHALL BE EQUIPPED
 WITH EMERGENCY LIGHTING EQUIPMENT.
  
 6. ADDITIONAL PORTABLE FIRE EXTINGUISHERS WILL BE
 NEEDED IN FUTURE TENANT SPACES DUE TO TRAVEL
 DISTANCES.
  
 7. AN ADDITIONAL EXIT SIGN IS NEEDED NEAR SUITE C TO
 DIRECT PERSONS AROUND CORNER TO THE EXIT.
  
 8. WHAT IS THE AJACENT TENANT SPACE USED FOR. HOW MANY
 TOTAL PERSONS ARE EXPECTED AT THE BUILDING.
  
 9. IS THERE ANY FIRE ALARM EQUIPMENT PRESENT AT THE
 BUILDING.
  
 10. MORE DETAILS NEEDED ON GLASS FIRE RATED DOORS
 ILLUSTRATED ON THE PLANS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 08:48 Rev Time 0.00
Received By jleech Date 2007-10-17 Time 10:18 Sent To  
Notes
2007-11-05 10:11:52TO "COMM" BD#13
2007-10-17 10:22:32WAITING FOR "COMM" BD--MEDICAL CLINIC

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-19 Cont ID  
Sent By rregueir Date 2007-11-19 Time 11:11 Rev Time 0.00
Received By rregueir Date 2007-11-19 Time 10:52 Sent To  
Notes
2007-11-19 11:11:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGN PROFESSIONAL OR THE OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE IN ACCORDANCE
 WITH FBC, EB 301.5. PLEASE DECLARE LEVEL OF ALTERATION
 UNDER THE ?GENERAL BUILDING CODE ANALYSIS? SECTION ON
 PLANS.
  
 2. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS DESCRIBED
 IN FBC, EB 304.1. AS SUCH THE SPACE BEING RECONFIGURED
 SHALL BE SHOWN TO MEET THE MINIMUM VENTILATION
 REQUIREMENTS OF FBC,M TABLE 403.3 IN ACCORDANCE WITH
 FBC,M 609.1. SHOW OUTSIDE AIR CALCULATIONS FOR ALL
 SPACES AS WELL AS MEANS OF PROVIDING THE REQUIRED RATES
 OF VENTILATION, INCLUDING BATHROOMS IN ACCORDANCE WITH
 THESE SECTIONS.
  
 3. MECHANICAL EQUIPMENT AND SUPPORTS THAT ARE EXPOSED
 TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBC, M 301.13. PROVIDE WIND LOAD
 CALCULATIONS SHOWING THE ATTACHMENT DETAILS ON PLAN TO
 BE SUFFICIENT FOR THE REQUIRED WIND LOADS PER FBC SEC.
 1609. ALSO, PROVIDE MANUFACTURER?S DATA SHOWING THE
 EQUIPMENT TO BE DESIGNED FOR WIND LOADS AS REQUIRED BY
 THESE SECTIONS.
  
 4. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC, EB
 611.1. SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS
 OF THE FLORIDA ENERGY EFFICIENCY CODE:
  
 A) NEWLY INSTALLED EQUIPMENT SHALL MEET THE MINIMUM
 EFFICIENCY STANDARDS AS LISTED IN FBC TABLE
 13-407.1.ABC.3.2A. THE EQUIPMENT LISTED AND THE
 EFFICIENCY STATED ON PLANS DOES NOT APPEAR TO MEET THIS
 REQUIREMENT.
  
 B) IF ALL WORK ON THIS BUILDING WITHIN A ONE YEAR
 PERIOD SHOULD MEET THE THRESHOLD FOR A RENOVATION AS
 DEFINED IN FBC 13-202, COOLING LOAD CALCULATIONS SHALL
 BE REQUIRED IN ACCORDANCE WITH FBC 13-407.1.ABC.1.
  
 C) PROVIDE SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBC 13-409.1.ABC.3.3.
  
 5. CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS
 SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN
 APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE. ALSO, CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL. SHOW MEANS AND
 LOCATION OF CONDENSATE DISPOSAL IN COMPLIANCE WITH FBC,
 M 307.2.1 AND FBC 1503.6.
  
 6. AUXILIARY DRAIN PROTECTION IS REQUIRED IN ACCORDANCE
 WITH FBC, M 307.2.3. SHOW COMPLIANCE WITH THIS SECTION.
 A WATER LEVEL DETECTION DEVICE, SUCH AS A FLOAT SWITCH,
 MAY BE INSTALLED ON THE PRIMARY DRAIN PAN OF THE UNIT
 AS STATED IN FBC, M 307.2.3(2).
  
 7. RTU DETAIL CALLS FOR ?CYLINDRICAL METALLIC DUCTS?
 WHILE THE AIR CONDITIONING NOTES CALL FOR RIGID DUCT
 BOARD AND FLEX. PLEASE COORDINATE DETAILS AND NOTES.
 FBC, M601.1 AND FBC 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 08:47 Rev Time 0.00
Received By jleech Date 2007-12-03 Time 08:32 Sent To  
Notes
2007-12-03 08:47:07DENIED;
 NOTE ENOUGH INFORMATION TO DO APLUMBING PLAN REVIEW;
 1. PAGE A-3 SHOWS INTERIOR WALLS BUT NO
 BATHROOMS.
 2. SHOW ON PLANS ALTERATION LEVEL.
 3. WATER AND SANITARY RISER DIAGRAMS ARE REQUIRED.
 FBC BUILDING SEC. 106.3.5.1.3.
 4. A DRINKING FOUNTAIN IS SHOWN ON RISER DIAGRAM
 BUT NOT ON FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By adavila Date 2007-11-08 Time 17:29 Rev Time 0.00
Received By adavila Date 2007-11-08 Time 17:29 Sent To  
Notes
2007-11-08 17:29:51PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE A COPY OF A CURRENT SURVEY.SURVEY SHALL BE
 ABSTRACTED TO SHOW ALL RIGHTS-OF-WAY AND EASEMENTS.
  
 3. IT HAS BEEN BROUGHT TO THE ATTENTION OF STAFF THAT A
 NUMBER OF IMPROVEMENTS AND ALTERATIONS WILL BE DONE TO
 THE SITE UNDER DIFFERENT PERMITS.PROVIDE THE TOTAL
 AMOUNT OF WORK VALUE.
  
 A. PLEASE NOTE THAT PER SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, RENOVATIONS,
 REPAIRS, ALTERATIONS OR REDEVELOPMENT EXCEEDING 50
 PERCENT OF THE VALUE OF THE STRUCTURE SHALL BE BROUGHT
 INTO CONFORMANCE WITH THE LANDSCAPE REGULATIONS OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS. B. PROVIDE THE
 VALUE OF THE STRUCTURE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.