Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-22 Cont ID  
Sent By mwennerg Date 2008-10-22 Time 10:03 Rev Time 0.00
Received By mwennerg Date 2008-10-22 Time 10:03 Sent To  
Notes
2008-10-22 10:04:19ONE SET OF PLANS AND SUPPORTING DOCUMENTS RE-STAMPED
 FOR FINAL INSPECTION ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-30 Cont ID  
Sent By mwennerg Date 2007-11-30 Time 13:20 Rev Time 0.00
Received By mwennerg Date 2007-11-30 Time 13:20 Sent To  
Notes
2007-11-30 13:22:17PLANS APPROVED AND STAMPED TO BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE PRIOR TO FINAL INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-15 Cont ID  
Sent By mwennerg Date 2007-11-15 Time 15:43 Rev Time 0.00
Received By mwennerg Date 2007-11-15 Time 15:43 Sent To  
Notes
2007-11-15 15:50:11***DENIED***
  
 1) OK, PLEASE PROVIDE DIAGRAM ON FIRST FLOOR THAT
 IDENTIFIES THE LOCATION OF THE FIRE ALARM PANEL.
  
 2) THIS BUILDING APPEARS TO BE PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM. PLEASE PROVIDE
 APPLICABLE EQUIPMENT INFORMATION ON THE RISER DIAGRAM.
  
 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE. SYTEM
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE IF
 SUPERVISING A FIRE SPRINKLER SYSTEM.
  
 NEW COMMENT:
  
 1) A MINIMUM OF TWO (2) SETS OF PLANS TO BE SUBMITTED
 FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mwennerg Date 2007-10-26 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2007-10-26 Time 15:08 Sent To  
Notes
2007-10-26 15:12:12***DENIED***
  
 1) PLANS INDICATE THE INSTALLATION OF A FIRE ALARM
 PANEL. THE PANEL AND LOCATION IS NOT ILLUSTRATED ON THE
 DRAWINGS. IF EQUIPMENT IS LOCATED ON ANOTHER LEVEL,
 PLEASE ADVISE AND SUBMIT A DRAWING.
  
 2) IT APPEARS THAT THE ALARM WILL SUPERVISE AN
 AUTOMATIC FIRE SPRINKLER SYSTEM. FIRE ALARM TO BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 16:26 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 16:26 Sent To FIRE
Notes
2008-09-24 16:27:13TO "F" BOX/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 12:14 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 12:14 Sent To FIRE
Notes
2007-11-28 12:14:39TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 11:48 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 11:48 Sent To FIRE
Notes
2007-11-06 11:49:05TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-26 Cont ID  
Sent By mwennerg Date 2007-10-26 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2007-10-16 Time 10:40 Sent To  
Notes
2007-10-16 10:40:53TO "F" BOX