Plan Review Details - Permit 07100424
Plan Review Stops For Permit 07100424
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-10-26 Cont ID  
Sent By lursu Date 2007-10-26 Time 11:59 Rev Time 0.00
Received By lursu Date 2007-10-26 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-07-23 Cont ID  
Sent By mjacobs Date 2008-07-23 Time 11:24 Rev Time 0.00
Received By mjacobs Date 2008-07-23 Time 10:52 Sent To PC
Notes
2008-07-23 11:24:19BUILDING PLAN REVIEW
 PERMIT: 07100424
 ADD: 1641 WORTHINGTON ROAD #100
 CONT: HEDRICK BROTHERS CONST.
 TEL: (561)389-2270
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-23-08
 REVIEW: REVISION
 ACTION: DENIED
  
 PROVIDE THE NEW ARCHITECTURAL SHEETS FOR SUITE #100
 SHOWING ALL CHANGES. THERE ARE NEW MEP SHEETS SHOWING
 THE NEW LAYOUT; HOWEVER THE ARCHITECTURAL SHEETS WITH
 THE NEW CHANGES WERE NOT SUBMITTED. THE PLANS SUBMITTED
 ARE FOR THE FIRE SPRINKLER. PLEASE INDICATE THE CORRECT
 PERMIT NUMBER (07100424) ON THE RESUBMITTAL SHEET FOR
 EACH REVISION CONCERNING SUITE #100.
 1)NOW THE FLOOR PLAN HAS BEEN ALTERED, THE MEP
 SHEETS AND ALL OTHER SHEETS SHALL MATCH THE NEW FLOOR
 PLAN SHOWING ALL THE CHANGES. A NEW SCHEMATIC FIRE
 SPRINKLER SHALL BE SUBMITTED TO OUR OFFICE SHOWING HOW
 THE NEW LAY OUT AFFECT THE SPRINKLER HEADS; THIS CAN BE
 SHOWN ON THE NEW CEILING PLANS PER FBC 106.1.5.1.1(5)
 AND FS 553.79(2)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-21 Cont ID  
Sent By mjacobs Date 2008-05-21 Time 15:11 Rev Time 0.00
Received By mjacobs Date 2008-05-21 Time 11:36 Sent To  
Notes
2008-05-21 15:11:45BUILDING PLAN REVIEW
 PERMIT: 07100424
 ADD: 1641 WORTHINGTON ROAD #100
 CONT: HEDRICK BROTHERS CONST.
 TEL: (561)389-2270
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-21-08
 REVIEW: REVISION
 ACTION: DENIED
  
 1)NOW THE FLOOR PLAN HAS BEEN ALTERED, THE MEP
 SHEETS AND ALL OTHER SHEETS SHALL MATCH THE NEW FLOOR
 PLAN SHOWING ALL THE CHANGES. A NEW SCHEMATIC FIRE
 SPRINKLER SHALL BE SUBMITTED TO OUR OFFICE SHOWING HOW
 THE NEW LAY OUT AFFECT THE SPRINKLER HEADS; THIS CAN BE
 SHOWN ON THE NEW CEILING PLANS PER FBC 106.1.5.1.1(5)
 AND FS 553.79(2)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-21 Cont ID  
Sent By mjacobs Date 2007-12-21 Time 10:26 Rev Time 0.00
Received By mjacobs Date 2007-12-21 Time 10:05 Sent To PC
Notes
2007-12-21 10:14:35PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-18 Cont ID  
Sent By mjacobs Date 2007-12-18 Time 12:45 Rev Time 0.00
Received By mjacobs Date 2007-12-18 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By mjacobs Date 2007-10-29 Time 15:32 Rev Time 0.00
Received By mjacobs Date 2007-10-29 Time 09:11 Sent To  
Notes
2007-10-29 11:42:19 
 BUILDING PLAN REVIEW
 PERMIT: 07100424
 ADD: 1641 WORTHINGTON ROAD
 CONT: HEDRICK BROTHERS CONST.
 TEL: (561)389-2270
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)IT APPEARS THAT THERE WILL BE TWO SEPARATE UNITS,
 THE DEMOUNTABLE PARTITION SEPARATE TWO SECTIONS OF THE
 SPACE AND NO OPENING IS SHOWN. IF THE SPACE WILL BE
 OPERATED BY ONE TENANT, SHOW THE OPENING JOINING THE
 TWO SPACES. IF THERE ARE TWO INDIVIDUAL TENANTS, A
 SEPARATION WALL WILL BE REQUIRED IN CONFORMANCE WITH
 FBC 708. THE CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE NATURE, LOCATION AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1
  
 3)NOTE: THE BUILDING IS HAS NOT RECEIVED A
 CERTIFICATE OF OCCUPANCY, WHICH MEANS IT IS STILL THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM. EACH
 SHEET OF THE BUILD-OUT DRAWINGS SHALL BE STAMPED AND
 APPROVED BY THAT DESIGN TEAM. THE ARCHITECT FIRM OF
 SMITH AND MOORE SHALL APPROVE ALL ARCHITECTURAL SHEETS
 WITH THEIR STAMP OF APPROVAL.
  
 4)THE PERMIT APPLICATION IS INCOMPLETE. THE
 APPLICATION WHICH HAS THE SIGNATURE OF THE CONTRACTOR
 /AGENT IS MISSING ALL THE NECESSARY INFORMATION ON THE
 FRONT OF THE APPLICATION. CHECK THE APPLICATION FOR ALL
 NECESSARY INFORMATION AND SIGNATURES WHEN RESUBMITTING.
 THE SUITE OR UNIT NUMBER SHALL ALSO BE INDICATED ON THE
 PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-14 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 10:40 Sent To PC
Notes
2008-07-14 10:44:36** DENIEDREVISIONS **
  
  
 1) NOTE:PLEASE BE SURE THE BASE BUILDING ENGINEER OF
 RECORD REVIEWS AND PROVIDES *SHOP DRAWING* REVIEW STAMP
 ON PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 15:56 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 15:56 Sent To  
Notes
2008-05-22 15:58:01REVISIONS #2, IF OK W/ FIRE, WILL RETAIN PLANS FOR FILE
 ONCE DONE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 12:47 Sent To  
Notes
2007-12-13 12:47:33OK, STAMPED ALL THREE SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By dpalmer Date 2007-10-22 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2007-10-22 Time 12:02 Sent To  
Notes
2007-10-22 17:13:19*** DENIED ***
  
 ** PLEASE KNOW ONLY THREE SETS OF PLANS ARE NEEDED TO
 BE SUBMITTED FOR REVIEW AND STAMPING.
 AS THIS PROJECT CONTAINS A SPECIAL INSPECTOR THREE ARE
 NEEDED BUT NOT FOUR SETS AS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION NEEDS TO
 CONTAIN THE SIGNATURE OF THE CONTRACTOR/QUALIFIER ON
 THE BACK OF THE APPLICATION. PLEASE SEE THE SHEET IN
 WHICH THE QUALIFIER SIGNED ON IS ACTUALLY A BLANK
 PERMIT APPLICATION.
 THE SECOND OTHER SIGNED SHEET IS SIGNED FROM AN
 AUTHORIZED AGENT WHO IS NO LONGER CURRENT WITH THE
 CITY.
 PLEASE SUPPLY A NEW APPLICATION, OR UPDATE AUTHORIZED
 AGENT WHO SIGNED ON SECOND PART OF APPLICATION.
 (BENJAMIN CLEMENS IS CURRETNLY ON SECOND APPLICATION
 SHEET )
  
 2) NOTE: PLEASE SHOW THE LOCATIONS OF THE FIRE ALARM
 DEVICES TO MEET FBC FOR ADA COMPLIANCE. PLEASE BE SURE
 THE LEVELS FOR HORNS/STROBES MEET THE MINIMUM LEVELS AS
 REQUIRED.
 PLEASE SEE FBC 11-4.28.1, .2, AND .3(4).
 ** THIS IS REQUIRED ON THE BASE PLANS EVEN AS THE FIRE
 ALARM IS UNDER SEPARATE PERMITS.
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE TANK-LESS WATER HEATER.
 110.3, 90.7.
 PLEASE SEE 422.13 IF THIS UNIT IS A STORAGE TYPE WATER
 HEATER, PLEASE BE SURE THE LOAD IS FIGURED AT 125%.
  
 4) NOTE: PLEASE SEE THE PLANS INDICATE A STANDARD
 LIGHTING SWITCH WHICH IS NOT PART OF THE LIGHTING
 CONTROL LEGEND FOR AUTOMATED DEVICES.
 PLEASE KNOW THAT MOST OF THE DEVICES ARE OK, HOWEVER
 THE STANDARD SWITCHES AS LISTED ON THE PLANS NEEDS TO
 BE CLARIFIED AND ADJUSTED TO MEET 13-415.1.ABC.1.1 AND
 .1.2.
 PLEASE SEE SECTION13-413.1.ABC.2.2 FOR REQUIRED
 CONSTRUCTION DOCUMENTS AND NOTES ON PLANS.
  
 5) NOTE: PLEASE SEE AS MENTIONED ON OTHER REVIEW FOR
 BUILD OUTS BEING APPLIED FOR BEFORE THE CERTIFICATE OF
 OCCUPANCY IS ISSUED ON THE BASED BUILDING. PLEASE KNOW
 AS THE BUILDING IS STILL UNDER THE RESPONSIBILITY OF
 THE BASE BUILDING DESIGN TEAM, ALL PLANS/SHEETS WILL BE
 REQUIRED TO BE STAMPED WITH SOME SORT OF SHOP DRAWING
 REVIEW STAMP OR BY OTHER MEANS WHICH WILL HAVE THE SAME
 AFFECT.THIS MUST BE DONE FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
 ** THIS CAN BE CONFIRMED WITH MR. ROBERT BROWN AND MR.
 NEIL MELICK.
 FS 471/481
 ** IT IS ALSO NOTED THAT THERE ARE LETTERS ATTACHED
 FROM BASE BUILDING DESIGN TEAM WHICH INDICATE
 COMMENTS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-27 Cont ID  
Sent By mwennerg Date 2008-05-27 Time 14:05 Rev Time 0.00
Received By mwennerg Date 2008-05-27 Time 14:05 Sent To  
Notes
2008-05-27 14:05:58REVISION DATED 4/30/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-22 Cont ID  
Sent By mawillia Date 2008-05-22 Time 18:55 Rev Time 0.00
Received By mawillia Date 2008-05-22 Time 18:38 Sent To  
Notes
2008-05-22 18:48:10*****UNSAT*****
  
 1.HOW WILL THE NEW FLOOR PLAN ALTER THE LOCATION OF
 THE FIRE ALARM DEVICES (AS SHOWN ON SHEET FA1.1) AND
 FIRE SPRINKLER HEADS (SEE BUILDING REVIEW COMMENT) ?
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 15:43 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 15:13 Sent To B1
Notes
2007-12-20 15:42:52*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETS LS1.0, A1.0, E1.1, AND FA1.1
 WERE STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By mawillia Date 2007-10-29 Time 18:52 Rev Time 0.00
Received By mawillia Date 2007-10-29 Time 16:26 Sent To  
Notes
2007-10-29 18:52:36*****UNSAT*****
  
 THE PLAN APPEARS TO INDICATE THAT SUITE 100 WILL BE
 SEPARATED INTO TWO UNITS BY A NEW DEMOUNTABLE PARTITION
 WALL.WHAT IS THE
  
  
 1.ON SHEET LS.1 UNDER THE LIFE SAFETY PLAN, BOTH
 3/16" = 1.0' AND 3/32" = 1.0' FOR SCALING ARE SHOWN.
 PLEASE EXPLAIN.
  
 2.THE PLAN APPEARS TO INDICATE THAT SUITE 100 WILL BE
 SEPARATED INTO TWO UNITS BY A NEW DEMOUNTABLE PARTITION
 WALL.WHAT IS THE FIRE RATING FOR THIS WALL?
  
 3.ON SHEET FA1.1, A FIRE ALARM MANUAL STATION IS
 NOTED IN THE LOBBY (101) ROOM.PLEASE EXPLAIN.
  
 4.ON SHEET FA1.1, AMEND SHEET NOTE #12 TO REFLECT
 THAT THE FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 5.IFTHE ERECTION/INSTALLATION OF THE NEW PARTITION
 WALL HAVE CAUSE FOR THE FIRE SPRINKLER HEADS OR OTHER
 DEVICES TO BE MODIFIED, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED FOR THE REMODEL.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 14:02 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 14:02 Sent To E
Notes
2008-06-13 14:02:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 15:09 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 15:09 Sent To  
Notes
2008-05-14 15:11:48TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 14:43 Sent To  
Notes
2008-05-08 14:43:58TO "COMM" BD#61

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 16:46 Sent To  
Notes
2007-12-12 16:48:44TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By mawillia Date 2007-10-29 Time 18:53 Rev Time 0.00
Received By mawillia Date 2007-10-15 Time 16:43 Sent To  
Notes
2007-10-22 10:47:49TO "BOB"#1
2007-10-15 16:44:51WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-12 Cont ID  
Sent By tgordon Date 2008-05-12 Time 08:50 Rev Time 0.35
Received By tgordon Date 2008-05-12 Time 08:50 Sent To  
Notes
2008-05-12 08:51:08REVISION TO MECH. PLANS M0.1, M1.1, AND M1.2.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-13 Cont ID  
Sent By tgordon Date 2007-12-13 Time 09:46 Rev Time 0.30
Received By tgordon Date 2007-12-13 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 14:21 Rev Time 1.00
Received By tgordon Date 2007-10-25 Time 14:21 Sent To  
Notes
2007-10-25 14:32:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, PER FBC/M
 403.2.
  
 2) NOTE: 1641 WORTHINGTON RD. IS A SHELL BUILDING.IT
 DOES NOT YET HAVE A CO SO THE SHELL BUILDING DESIGN
 PROFESSIONALS WILL BE REQUIRED TO PROVIDE A SHOP
 DRAWING REVIEW STAMP ON ANY BUILD-OUT PLANS THAT ARE
 PREPARED BY DIFFERENT DESIGNERS. SEE KAMM CONSULTING
 REVIEW NOTES DATED 9-17-07, PLEASE COMPLY.
  
 3)PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 ELECTRIC CEILING HEATERS (CH) AND MIT UNITS. PLEASE
 INDICATE WHICH UNITS ARE BEING INSTALLED IF NEEDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By jleech Date 2008-05-19 Time 08:07 Rev Time 0.00
Received By jleech Date 2008-05-19 Time 07:44 Sent To  
Notes
2008-05-19 08:08:30REVISED PLANS

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 10:05 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 10:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-10-27 Time 11:45 Rev Time 0.00
Received By jleech Date 2007-10-27 Time 11:45 Sent To  
Notes
2007-10-27 12:12:55DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'SNOTE 1.
 2. ICE MACHINE TO DRAIN INDIRECTLY INTOA FLOOR DRAIN
 OR AN AIR GAP FITTING.SEE FBC PLUMBING SECTION 802.1.
 3.WATER HAMMER ARRESTORS REQUIRED AT BREAK SINK.
 SECTION 604.9 LIST SIZE AND MANUFACTURE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-23 Cont ID  
Sent By choops Date 2007-10-23 Time 14:26 Rev Time 0.00
Received By choops Date 2007-10-23 Time 14:26 Sent To  
Notes
2007-10-23 14:26:27*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.